Venturi Tube Working Principle, Bernoulli Math & ASME Specs

Contents

Venturi tube working principle showing converging, throat, and diverging sections

What a Venturi Tube Does

A venturi tube is a short pipe section with a narrowed middle, used to measure fluid flow rate by sensing the pressure drop across the constriction. The device was described by Italian physicist Giovanni Battista Venturi in 1797 and remains one of the most accurate primary elements for measuring water, steam, oil, and gas flow.

Three sections do all the work: a converging inlet that accelerates the fluid, a cylindrical throat where pressure reaches its lowest value, and a diverging outlet that recovers most of the kinetic energy as static pressure. Two pressure taps — one upstream, one at the throat — feed a differential pressure transmitter that outputs a 4–20 mA signal proportional to the square root of flow.

You will see venturi tubes in municipal water mains, power plant feedwater lines, chiller plants, custody-transfer crude oil headers, and wherever pumping cost makes the pressure loss of an orifice plate unacceptable.

The Venturi Effect and Bernoulli Equation

The physics is one equation. For an incompressible, steady, frictionless flow along a streamline, Bernoulli’s equation between the upstream tap (section 1) and the throat (section 2) gives:

P₁ + ½ρv₁² = P₂ + ½ρv₂²

Combine with continuity (A₁v₁ = A₂v₂) and you get the working form most engineers use day-to-day:

Q = Cd · A₂ · √[ 2·ΔP / (ρ · (1 − β⁴)) ]

Where Q is volumetric flow (m³/s), A₂ is throat area (m²), ΔP is the measured pressure differential (Pa), ρ is fluid density (kg/m³), β is the throat-to-pipe diameter ratio (d/D), and Cd is the discharge coefficient — typically 0.984 for a classical Venturi with machined convergent and rough cast iron throat per ISO 5167-4. The β⁴ term in the denominator is the velocity-of-approach correction; you cannot ignore it when β > 0.3.

Anatomy of a Classical Venturi Tube

Three sections by length and angle:

  • Convergent cone: total included angle 21° ± 1°. Length about 2.7 × (D − d).
  • Throat: length equal to the throat diameter d. Two diametrically opposed pressure taps (or four equispaced taps connected to a piezometer ring) sit at the midpoint.
  • Divergent cone: total included angle 7° to 15°. Shorter angles recover more pressure but add cost and weight; 7° is the textbook value for maximum recovery.

The upstream pressure tap sits at a distance of ½D from the start of the convergent section. This is the geometry of the “classical” Venturi tube as defined in ASME MFC-3M. Get the cone angles wrong and the discharge coefficient drifts outside the standard’s ±0.7% tolerance, requiring individual calibration.

Five Venturi Tube Designs by Geometry

DesignConstructionTypical βCdUse case
Classical machinedBronze or stainless, machined convergent0.4–0.750.995Lab, custody transfer
Classical rough castCast iron, as-cast convergent0.3–0.750.984Large water mains
Classical welded sheetFabricated steel, β-ring throat0.4–0.70.985Power plant feedwater
Short-form (Herschel)Shortened divergent, 21° angle0.4–0.70.97–0.99Tight installations
RectangularFlat-sided, non-circularvaries0.95–0.99HVAC ducts, open channels

The short-form (Herschel) Venturi trades 5–10% of pressure recovery for half the lay length. That tradeoff often makes sense in retrofit jobs where there is no room for a 5-meter classical tube. The rectangular variant shows up in HVAC supply ducts and water canals where a circular flow element does not fit. For more on duct-mounted DP sensing, see our guide on static vs dynamic pressure.

Worked Flow Calculation: From ΔP to Q

Water at 20 °C flows through a 200 mm classical Venturi with a 100 mm throat. The DP transmitter reads 25 kPa. What is the flow rate?

  • D = 0.200 m, d = 0.100 m, so β = 0.5
  • A₂ = π × (0.100)² / 4 = 0.007854 m²
  • ρ = 998 kg/m³ (water at 20 °C)
  • ΔP = 25,000 Pa
  • Cd = 0.984 (rough cast convergent per ISO 5167-4)
  • 1 − β⁴ = 1 − 0.0625 = 0.9375

Plug in: Q = 0.984 × 0.007854 × √[ (2 × 25,000) / (998 × 0.9375) ] = 0.984 × 0.007854 × √(53.45) = 0.984 × 0.007854 × 7.311 = 0.0565 m³/s ≈ 203 m³/h.

Throat velocity v₂ = Q / A₂ = 0.0565 / 0.007854 = 7.2 m/s, which is well inside the 1.5–10 m/s sweet spot for Venturi tubes. Below 1.5 m/s, DP gets noisy. Above 10 m/s, you start seeing cavitation risk on the throat for liquids. For the DP side of the math, our explainer on how DP transmitters work covers signal conditioning.

Venturi vs Orifice Plate vs Flow Nozzle

ParameterClassical VenturiOrifice PlateFlow Nozzle
Permanent pressure loss5–20% of ΔP40–95% of ΔP30–80% of ΔP
Discharge coefficient0.984–0.9950.60–0.620.93–0.99
Accuracy (uncalibrated)±0.7%±0.6%±1.0%
Turndown ratio3:1 to 5:13:1 to 5:13:1 to 4:1
Straight pipe upstream5–10 D10–44 D10–30 D
Capital cost (200 mm)$$$ (high)$ (low)$$ (mid)
Best forLarge lines, slurriesClean fluids, retrofitSteam, high temperature

The orifice plate wins on price and is fine when you do not care about pump head. The Venturi wins when permanent pressure loss costs real money — a 1000 mm water main saving 20 kPa year-round is worth tens of kilowatts of pump power. Flow nozzles fit in between, popular for high-temperature steam where orifice edge wear becomes a calibration problem. For thicker comparison content, see our piece on flow meter K-factor.

ASME MFC-3M and ISO 5167-4 Standards

Two documents govern Venturi tube design and calibration:

  • ASME MFC-3M-2004: “Measurement of Fluid Flow in Pipes Using Orifice, Nozzle, and Venturi.” Defines convergent angle 21° ± 1°, divergent angle 7° to 15°, throat surface roughness, and the Cd equations.
  • ISO 5167-4:2022: “Measurement of fluid flow by means of pressure differential devices — Part 4: Venturi tubes.” Sets the diameter range 50 mm ≤ D ≤ 1200 mm and Reynolds number range 2×10⁵ ≤ Re ≤ 2×10⁶ for uncalibrated use.

Outside those bounds — small lines, low flows, high-temperature gas, or β below 0.3 — you cannot use the tabulated Cd. The tube must be wet-calibrated on a flow rig traceable to NIST. Calibration adds about $3,000–$8,000 to a 200 mm classical Venturi.

Installation: Straight Runs and Tap Orientation

The Venturi is forgiving compared with an orifice plate, but it still needs straight pipe:

  • 5 D upstream of a single 90° elbow
  • 10 D upstream of two elbows in perpendicular planes
  • 20 D upstream of a partly closed valve
  • 4 D downstream before any disturbance

Pressure tap orientation depends on the fluid. For clean liquids, taps at 3 and 9 o’clock (horizontal pipe). For gas with possible condensate, taps at 12 o’clock. For steam, taps at 3 and 9 with condensate pots installed below. Get this wrong and you get either a slugged transmitter or a permanently water-logged impulse line. Our DP transmitter installation guide covers impulse line slopes and 3-valve manifold sequencing.

For straight-pipe rules of thumb on every meter type, see our flow meter straight pipe guide.

Pressure Recovery: Venturi’s Energy Advantage

The diverging cone is where Venturi tubes earn their cost. By gradually expanding the flow from throat to pipe diameter at a 7° included angle, the fluid decelerates without turbulent separation and most of the kinetic energy converts back to static pressure. Typical permanent pressure loss is 10% of the measured ΔP at β = 0.5, dropping to 5% at β = 0.7. Compare that with an orifice plate at the same β, which dumps 70–95% of ΔP as friction loss.

Over a year, a 600 mm Venturi at 0.5 m/s saving 15 kPa of pump head represents roughly 4 kW of continuous pump power. At $0.12/kWh that is about $4,200 per year — payback on the Venturi premium often inside 2 years. This is the math behind every chilled water plant retrofit replacing orifices with Venturis.

Cleaning Venturi Tubes (Industrial + BBQ Grill)

Two completely different cleaning jobs share the name. The industrial Venturi flow meter rarely needs cleaning if the fluid is clean; for slurries or scaling water, a yearly inspection and high-pressure rinse of the throat are normal. Pressure taps are the failure point — they plug with debris and bias the reading low. Most modern Venturis include flush connections on the tap legs.

Gas grills are the other context. Each burner has a small Venturi tube where propane or natural gas accelerates and pulls in primary air. Spiders love these tubes; webs and egg sacs block airflow and produce yellow flames or backfiring. To clean a grill Venturi: shut off gas, remove the burner, slide the Venturi off the orifice spud, push a pipe cleaner or bottle brush through the tube, blow out with compressed air, reassemble. Inspect every spring before first use.

Venturi Flow Meters from Sino-Inst

Venturi Flow Meter

DN50 to DN1200 | β 0.4–0.75 | ±0.5% — classical and short-form geometries for water, oil, gas service.

Verabar Flow Meter

Averaging pitot | hot tap insertion | low pressure loss — alternative to Venturi for large pipes with retrofit constraints.

V-Cone Flow Meter

Conditioning DP element | 0–3D straight run | tolerates swirl — compact replacement for Venturi in tight installations.

For sizing help or a quotation on any of these flow elements, contact our engineering team using the form below. Provide pipe size, fluid, design flow, and operating pressure-temperature; we typically reply within one business day.

FAQ

What is a venturi tube used for?

Measuring flow rate by sensing the pressure drop across a constricted throat. Common applications are municipal water, power plant feedwater, chilled water HVAC, oil custody transfer, and grill burner air entrainment.

How does a venturi tube work?

The fluid accelerates through a converging cone, causing static pressure to drop in the throat (Bernoulli’s equation). A DP transmitter reads the pressure difference between upstream and throat taps; volumetric flow is proportional to the square root of that differential.

How do you clean venturi tubes on a gas grill?

Shut off the gas, lift out the burner, slide the Venturi tube off the orifice spud, push a long-handled bottle brush or pipe cleaner through the tube to remove spider webs and debris, blow clean with compressed air, and reassemble. Inspect every spring before the first cookout.

What is the difference between a venturi tube and an orifice plate?

Both create a differential pressure for flow measurement. A Venturi recovers most of the pressure (5–20% permanent loss) thanks to its diverging cone; an orifice plate dumps 40–95% as turbulent loss. Venturi costs 5–10× more but pays back in pump energy on large lines.

What pressure recovery does a venturi tube achieve?

About 80–95% of the differential pressure is recovered as static pressure downstream, depending on β (throat/pipe diameter ratio) and divergent cone angle. A β = 0.7 classical Venturi with 7° divergent angle gives roughly 95% recovery, while β = 0.4 at 15° recovers about 80%.

Request a Quote

Please enable JavaScript in your browser to submit the form

LPM to GPM & GPM to LPM: Conversion Table, Formula & Decoder

GPM and LPM are the two flow-rate units printed on almost every industrial pump, valve, and flow meter datasheet. GPM means gallons per minute (US gallons unless the label says otherwise). LPM means litres per minute. The conversion between them is one multiplication, but a small slip — the wrong gallon, the wrong rounding, mass instead of volume — turns a sized line item into the wrong meter on the skid. This page gives the conversion both ways, the lookup tables, and the industrial context the calculator sites don’t.

Contents

The Conversion Number You Need

One US gallon equals 3.785411784 litres exactly (NIST). Per minute, the conversion is the same number:

  • LPM → GPM (US): multiply LPM by 0.264172. Or divide LPM by 3.7854.
  • GPM (US) → LPM: multiply GPM by 3.7854.
  • LPM → GPM (UK): multiply LPM by 0.219969. UK gallon is 4.54609 L.
  • GPM (UK) → LPM: multiply GPM by 4.54609.

For a quick worked example: a chilled-water pump rated at 150 LPM puts out 150 × 0.264172 = 39.6 US GPM, or 33.0 UK GPM. That 6.6 GPM gap is the gotcha discussed below.

LPM ↔ GPM Conversion Tables (Both Directions)

Common values, rounded to two decimals. Use US gallons unless your meter or local code specifies UK Imperial.

LPMGPM (US)GPM (UK)
10.260.22
51.321.10
102.642.20
205.284.40
5013.2111.00
10026.4222.00
15039.6333.00
20052.8343.99
25066.0454.99
500132.09109.98
1000264.17219.97
GPM (US)LPMGPM (UK)
13.790.83
518.934.16
1037.858.33
1556.7812.49
2594.6420.82
50189.2741.63
75283.9162.45
100378.5483.27
200757.08166.53
5001892.71416.34

If your application is around flow rate and pressure sizing — for instance HVAC chilled-water or boiler feed — confirm which gallon the pump curve uses before you multiply.

What “GPM” Actually Means as a Unit

GPM is the symbol for gallons per minute. It is a volumetric flow rate — volume per unit time — not a mass flow rate. The “G” is gallons, which is a non-SI unit used mostly in the United States and the United Kingdom. The “PM” is per minute. The full ISO-equivalent expression is gal/min, sometimes written gpm or USgpm to disambiguate the gallon.

The SI counterpart is m³/s, but at industrial flow rates the operational units are LPM (L/min), m³/h, or GPM. On a chilled-water loop the same flow can be written 150 LPM, 9 m³/h, or 39.6 US GPM — same fluid, same pipe, three labels.

US Gallon vs UK Gallon: The 20% Gotcha

The US liquid gallon is 3.7854 L. The UK Imperial gallon is 4.5461 L. The Imperial gallon is about 20.1% larger. That means 100 GPM (UK) is 120 GPM (US) — same physical flow, different number on the label.

Procurement pitfalls we see in field installations:

  • A UK-sourced pump rated 40 GPM is actually 48 US GPM. Sizing the meter to 40 US GPM under-ranges the meter and clips the high end.
  • Conversion code that hard-codes the US factor (0.2642) treats Imperial gallons as US, producing a 20% under-reading.
  • Auto-translated datasheets from European OEMs sometimes drop the “UK” prefix when localising for North America. Always confirm by checking against L/min on the same sheet.

GPM vs LPM on Flow-Meter Spec Sheets

Which unit appears on the meter face depends on where it’s sold and what fluid it handles. Practical pattern after looking at hundreds of vendor PDFs:

Meter TypeTypical Native UnitNotes
Magmeter (water, slurry)m³/h or LPM (EU/Asia); GPM (US)Configurable on the transmitter display.
Variable-area rotameterGPM or LPM on the etched scaleScale is fluid- and SG-specific; not switchable.
Ultrasonic clamp-onm³/h or LPM (EU); GPM (US)Software-switchable.
Turbine / paddle wheelPulses, scaled to GPM in US, LPM in EUK-factor sets the pulse-to-volume ratio.
Corioliskg/h or g/s (native mass); GPM/LPM via densityGPM only valid at the configured density.

Variable-area meters such as the metal-tube rotameter are the only common type where the unit is physically etched onto the body. Anything with a display can usually toggle between LPM, GPM, and m³/h in the transmitter settings.

Spec-Sheet Decoder: 0.5–25 GPM in Pipe-Size Terms

A range like “0.5 to 25 GPM” tells you the meter, not the pipe. To pick the right line size you cross-reference target velocity. For water, the design rule of thumb is 1–3 m/s in process lines and 1.5–2.5 m/s in chilled-water mains.

Flow Range (GPM)LPMSuggested Line Size (Water, ~2 m/s)
0.5–52–19DN15 (½”)
2–208–76DN20 (¾”)
5–5019–189DN25 (1″)
15–15057–568DN40 (1½”)
30–300114–1136DN50 (2″)
80–800303–3028DN80 (3″)

Velocity has to land inside the meter’s specified turndown — typically 10:1 for vortex, 20:1 for paddle wheel, 100:1 for magmeter and Coriolis. The straight pipe requirements upstream and downstream of the meter also matter; under-piped installs invalidate the accuracy curve even when the range looks right on paper.

For pulse-output turbine and paddle-wheel meters, the displayed GPM or LPM depends on the configured K-factor. A K-factor entered in pulses/litre while the display reads GPM throws everything off by the 0.2642 factor.

Other Flow-Rate Units: m³/h, CFM, BPH

GPM and LPM are not the only labels you will see. The common cross-references:

  • m³/h (cubic metres per hour): 1 m³/h = 16.667 LPM = 4.403 US GPM. Standard for water utilities and EU process plants.
  • L/s (litres per second): 1 L/s = 60 LPM = 15.85 US GPM. Used in firefighting and large pumps.
  • CFM / SCFM: cubic feet per minute. Gas units — not interchangeable with GPM. 1 CFM ≈ 28.32 LPM only for actual volume, not standard volume.
  • BPH (barrels per hour): oil & gas. 1 US barrel = 42 US gal, so 1 BPH = 0.7 GPM = 2.65 LPM.
  • BTU/h: not flow, but flow-derived; for a chilled-water loop, see how the math chains in our BTU meter for chilled water note.

Mass vs Volumetric: When GPM Misleads

GPM is volume per minute. Volume changes with temperature and pressure, so for gases and compressible or hot liquids, the GPM number tells you less than you think.

  • Hot water at 90 °C is about 3.6% less dense than at 20 °C. A pump rated 100 GPM cold delivers ~96 GPM of cold-water-equivalent mass when hot.
  • For hydrocarbons the temperature correction is bigger (β around 0.001/°C for light products). Custody-transfer specs in oil & gas always state the reference temperature.
  • For gases, “GPM” is meaningless unless converted to Nm³/h or kg/h at a stated reference condition. Don’t size a gas process on a GPM figure.

Coriolis and thermal mass meters measure mass directly and avoid this problem. For volumetric meters, apply a density correction or use the inverse-square-root scaling from our linear-to-sqrt converter tool when working with DP-type meters.

Three Common Conversion Mistakes

  1. Mixing US and UK gallons. An OEM datasheet that says “GPM” with no qualifier in a UK or Commonwealth context is usually UK Imperial. North American docs are usually US. When in doubt, compute the LPM equivalent both ways and see which one matches the rest of the sheet.
  2. Using GPM for gas flow. GPM is volumetric and only meaningful for incompressible liquids at a known density. For air, nitrogen, or refrigerant gas, work in Nm³/h, kg/h, or SCFM and document the reference conditions.
  3. Rounding 0.2642 to 0.25. The shortcut “divide by 4” gives a 5.4% error. For custody transfer and BTU calculations that error is enough to fail audit. Use 0.26417 or the full factor.

FAQ

How many LPM is 1 GPM?

1 US GPM is 3.7854 LPM. 1 UK GPM is 4.5461 LPM. If the unit is not specified, US is the safer default for North American equipment and UK for UK/Commonwealth equipment.

How do you convert LPM to GPM by hand?

Multiply litres per minute by 0.2642 for US gallons. Multiply by 0.2200 for UK Imperial gallons. To go the other way, multiply GPM by 3.7854 (US) or 4.5461 (UK) to get LPM.

What’s the difference between GPM and LPM?

Both are volumetric flow-rate units. GPM is gallons per minute (3.7854 L per US gallon, 4.5461 L per UK gallon). LPM is litres per minute. LPM is SI-derived and used globally except in US and UK pumping/HVAC contexts.

Is GPM US or UK by default?

Defaults depend on the document’s origin. US OEM datasheets and most online calculators default to US GPM. UK and historically Commonwealth specs default to UK Imperial. ISO standards always state SI units; if a non-SI gallon is used, the document should specify US or UK explicitly.

Does the conversion factor change with temperature?

The volume-to-volume factor (0.2642 LPM-to-GPM US) is a pure unit conversion and does not change with temperature. Mass flow does change with temperature because density changes — that is a separate correction layered on top of the volumetric conversion.

Magnetic Flow Meter

DN15–DN3000 | ±0.2–0.5% | Configurable GPM, LPM, m³/h — switchable on the transmitter for conductive liquids and slurries.

Metal Tube Rotameter

DN15–DN200 | ±1.5–2.5% | Direct GPM or LPM etched scale — variable area for high-temp or opaque fluids.

Ultrasonic Water Meter

DN15–DN50 | ±2% | Battery-powered ultrasonic, displays GPM/LPM/m³/h, suitable for residential and commercial water billing.

Need a Flow Meter Sized in Your Units?

If your pump curve is in LPM and your local procurement spec is in GPM (or vice versa), send the line size, fluid, and design flow to our engineers — we’ll quote a meter with the display configured in the unit your operators read.

Request a Quote

Please enable JavaScript in your browser to submit the form

Stilling Well for Tank Level Measurement: Sizing, Hole Pattern & Install

A stilling well is a metal pipe installed inside a tank with calibrated holes near the bottom. It surrounds the radar antenna (or any non-contact level transmitter) and dampens the surface chaos — foam, turbulence, swirls from agitators — that throws off level readings. For radar in particular, the pipe also doubles as a low-loss waveguide, recovering 20–40% signal strength on low-dielectric liquids like LPG, hydrocarbons, and condensate. This page covers what a stilling well is, why it matters, and how to size and install one for tank level measurement. On chemical service such as sulfuric acid storage tank level radar, the same stilling-well technique applies once the antenna material is upgraded to PTFE or Hastelloy.

Contents

What Is a Stilling Well

A stilling well — also called a still pipe, stilling tube, or bypass chamber — is a vertical pipe mounted inside a tank with one end above the maximum liquid level and the other end submerged near the bottom. Small holes (typically 4–10 mm) drilled along the lower section let liquid in. The liquid inside the pipe rises to the same level as the tank but without the turbulence, foam, or floating debris of the open surface.

The pipe is usually 304 / 316 stainless steel for chemical service, carbon steel for hydrocarbons, or PVC for water in atmospheric tanks. Diameter ranges from DN50 (2″) for small chemical tanks to DN200 (8″) for large crude oil storage. Length matches the tank height plus a 200–400 mm extension above the level transmitter flange.

Why Radar Level Transmitters Need a Stilling Well

Non-contact radar measures the time-of-flight of a microwave pulse reflected off the liquid surface. Three things break that reflection:

  • Foam. A 50 mm foam layer can scatter 30 dB of the return signal. Low-dielectric foam (oils, surfactants) is the worst.
  • Turbulence and agitators. A mixer-driven surface moves 100 mm/s or more; the radar averages out as noise.
  • Low dielectric constant. Liquids with εr < 2.5 (LPG, propane, vacuum gas oil) reflect only 1–3% of the signal in open vessel mode.

A stilling well solves all three. The pipe shields the antenna from foam and surface motion. It also acts as a circular waveguide — the microwave concentrates inside the pipe and reflects off the calmer liquid column, boosting the return signal by 10–20 dB. For LPG and similar low-εr media, a stilling well changes radar from unusable to ±2 mm accuracy.

Stilling Wells for Other Level Transmitters

Stilling wells help more than just radar:

Transmitter TypeStilling Well BenefitRequired?
Non-contact radar (pulse / FMCW)Waveguide effect, foam isolationRecommended for εr<2.5 or foaming media
Guided wave radar (GWR)Mechanical protection of probeOptional, not for signal
UltrasonicDamps echo from turbulenceRecommended in agitated vessels
Float / displacerPrevents float side-washRequired in agitated tanks
MagnetostrictiveProbe protectionOptional
DP / hydrostaticNone (taps go through tank wall)Not used

The general rule: any non-contact technology benefits from a stilling well when the surface is foaming, agitated, or has low reflectivity. Contact technologies like DP and hydrostatic do not use them — see our DP level transmitter notes for that case.

Stilling Well Pipe Sizing and Hole Pattern

The pipe diameter must match the radar antenna’s beam angle and the level transmitter’s mounting flange. Three rules:

  1. Inner diameter ≥ 50 mm for horn-type radar. Smaller pipes attenuate the beam.
  2. Antenna radial clearance 5–10 mm from pipe wall. Too close and you get wall reflections; too far defeats the waveguide effect.
  3. Pipe straightness ≤ 1 mm per metre. Bends scatter the radar pulse and bias the level reading by tens of millimetres.

The hole pattern is the second design variable. Holes too small respond too slowly to filling rate; too large defeat the damping. Industry practice:

Pipe DNHole DiameterSpacingTotal Open Area
DN50 (2″)4–6 mm50 mm2–3% of pipe wall
DN80 (3″)5–8 mm75 mm2–3%
DN100 (4″)6–10 mm100 mm2–4%
DN150 (6″)8–12 mm100 mm3–4%
DN200 (8″)10–14 mm150 mm3–5%

Drill the holes in a staggered helical pattern (60° offset between rows) rather than vertical columns. The helical pattern prevents resonance and damps surface waves more evenly.

Stilling Well Installation in a Tank

  • Submersion depth. The bottom of the pipe sits 80% of minimum operating level below the lowest measured point — never let holes emerge into air during normal operation.
  • Top mounting. Welded flange to a tank nozzle is the cleanest. The transmitter bolts to the nozzle’s top flange; the pipe hangs from the same flange or rests on internal brackets. Threaded NPT works for atmospheric tanks below 10 bar.
  • Bottom support. For pipes over 4 m, weld a guide ring or bracket near the bottom to prevent swinging from tank-side flow.
  • Pressure equalisation hole. Drill one 5–8 mm hole near the top of the pipe (above max level) to vent gas; otherwise pressure traps inside the pipe and falsifies the reading.
  • Antenna alignment. The radar horn axis must be parallel to the pipe centerline within 1°. A misaligned antenna throws off level by several millimetres per metre of probe distance. For a deeper look at horn vs parabolic vs rod antennas, see our radar antenna selection guide.

For a complete radar selection walkthrough see our radar water level sensor product page, which lists antenna types compatible with stilling wells.

Common Stilling Well Mistakes

  1. Using a too-small pipe. A DN40 (1½”) pipe with a DN80 horn antenna attenuates the beam by 6 dB. Match pipe to antenna size first.
  2. Drilling holes too close to a vent or mixer outlet. Local jet through one hole biases the column. Position holes 90° away from any agitator outflow.
  3. Skipping the vent hole at the top. Without venting, the column traps gas as tank pressure changes — level reading lags actual tank level by tens of mm.
  4. Mounting the pipe with a bend. Any non-vertical section becomes a microwave scatterer. Always plumb the pipe to vertical within 1°.
  5. Using PVC for hydrocarbon service. Plastic stilling wells crack and shrink against hydrocarbons over time. Stainless steel or carbon steel for any oil or solvent.

FAQ

What is a stilling well in a tank?

A stilling well is a vertical pipe installed inside a tank with calibrated holes near the bottom. Liquid inside the pipe reaches the same level as the tank but without surface turbulence or foam, giving level transmitters (especially non-contact radar) a clean measurement column.

Do I need a stilling well for a radar level transmitter?

Use a stilling well when the liquid is low-dielectric (εr below 2.5, like LPG or hydrocarbons), when foam is present, when the surface is agitated by mixers, or when the tank has internal obstructions in the radar beam path. Calm water in a quiet vessel does not need one.

What size stilling well pipe for radar?

Match the pipe inner diameter to the radar horn antenna. A DN80 antenna fits a DN100 stilling well; a DN50 antenna fits a DN80 well. Keep 5–10 mm of radial clearance between antenna edge and pipe wall.

Can a stilling well be used with ultrasonic or float level meters?

Yes. Ultrasonic meters benefit from a stilling well in agitated tanks because the pipe damps turbulence-induced echo noise. Float and displacer meters often need a stilling well to prevent side-wash from disturbing the float position.

Radar Water Level Sensor

0.05–120 m | ±3 mm | 26 GHz pulse radar. Pairs with DN50–DN200 stilling wells for foaming or low-εr liquids in tanks and reservoirs.

80 GHz FMCW Level Radar

0–120 m | ±1 mm | Narrow beam works with DN50 stilling well. VEGAPULS 64 class alternative for LPG, hydrocarbons, agitated vessels.

SI-100 Magnetostrictive Transmitter

0.3–6 m rigid probe | ±0.5 mm | Probe slides inside stilling well for mechanical protection in agitated chemical tanks.

Need a Stilling Well Spec for Your Tank?

Send us your tank dimensions, fluid (with dielectric constant if known), and whether the surface is agitated or foaming. Our engineers will recommend the pipe DN, hole pattern, and the matching radar or ultrasonic transmitter — quoted as a complete spec ready to weld in.

Request a Quote

Please enable JavaScript in your browser to submit the form