4-20 mA to 0-10 V Converter: Resistor Table, Wiring & PLC Scaling

A 4-20 mA current loop carries a sensor signal across hundreds of meters with near-zero drift. A 0-10 V PLC card cannot accept that current directly. Converting between the two is a five-cent fix on the bench (one resistor) or a forty-dollar fix in the panel (a signal converter). This guide gives you the resistor table, the wiring diagram, the PLC wiring conventions, and the decision rule for picking each.

Contents

4-20 mA to 0-10 V Conversion at a Glance

4-20 mA to 0-10 V signal converter direction diagram

Two paths exist. A precision resistor across the PLC analog input converts current to voltage by Ohm's law. An active signal converter does the same job but adds galvanic isolation and a true zero-based output. Pick the resistor for short cable runs and grounded single-PLC systems. Pick the converter when ground loops, long runs, or true 0-10 V output matter. Reviewing how a 4-20 mA transmitter generates the loop helps clarify why the live-zero matters.

One trap catches new technicians weekly: a 500 Ω resistor produces 2-10 V, not 0-10 V. The 4 mA live zero of the loop drops 2 V across 500 Ω. If the PLC card requires the input to start at 0 V (some 12-bit modules do, others scale from any value), the resistor method needs software offset or an active converter with zero adjustment.

Resistor Sizing Table for Common Output Ranges

Voltage at the PLC input equals current times resistance. The 4 mA endpoint sets the low voltage; 20 mA sets the high. Most plants standardize on 250 Ω (1-5 V) or 500 Ω (2-10 V) so spares interchange.

ResistorOutput @ 4 mAOutput @ 20 mASpanTypical PLC card
125 Ω0.5 V2.5 V0.5-2.5 VLow-voltage ADC, microcontroller
250 Ω1.0 V5.0 V1-5 VAllen-Bradley 1492-IFM, legacy DCS
500 Ω2.0 V10.0 V2-10 VSiemens S7-1200/1500 0-10 V mode
250 Ω + opamp offset0 V4 V0-4 VCustom analog front-end

Specify 1% or 0.1% metal-film resistors at 0.25 W or higher. At 20 mA through 500 Ω the dissipation is I²R = 0.0004 × 500 = 0.2 W, so a quarter-watt part is borderline; jump to 0.5 W if the resistor sits inside a hot panel. Wirewound and carbon-film parts drift with temperature and should not be used for analog instrumentation. The same precision rule applies whenever you read engineering units back from a sensor — resistor error multiplies straight into reported value.

Wiring the Resistor Across the PLC Analog Input

Three terminals do the work: the transmitter positive (+), the PLC analog input (AI), and the PLC common (COM). The resistor goes between AI and COM, the transmitter loop closes through the AI terminal.

  • Wire the transmitter + to the 24 VDC supply positive (most transmitters are loop-powered).
  • Wire the transmitter (current return) to the PLC AI terminal.
  • Wire the PLC COM terminal to the 24 VDC supply negative.
  • Install the precision resistor across AI and COM (parallel to the input impedance).
  • Keep the resistor lead length under 20 mm to limit thermal EMF and pickup noise.

On terminal blocks, mount the resistor on the panel side, not at the transmitter side. This keeps the 4-20 mA loop full-length (high immunity) and only the short voltage span sees the PLC. Our pressure transmitter installation guide covers the loop-powered vs self-powered (4-wire) wiring variants for reference.

PLC Scaling: Why 500 Ω Gives 2-10 V, Not 0-10 V

The 4 mA live zero is the cause. 4 mA × 500 Ω = 2 V. The PLC reads 2 V at the bottom of the sensor range, not 0 V. Two options correct this in software:

  • Two-point scaling: Engineering value = (raw_V − 2) / 8 × full_scale. The 8 is the 10-2 V span. Built into most modern PLC scale function blocks (SCL, SCP, FC105).
  • Offset correction: Add a -2 V offset before the standard 0-10 V scale block. Works on older HMIs that lack two-point scaling.

A common error is mapping 0-10 V raw counts directly to 0-100% engineering units. This compresses the live signal range to 80% and shifts zero by 20%. Field calibration will look fine at mid-scale and fail at endpoints, which is hard to diagnose without a multi-point bench calibration.

Signal Converter vs Resistor: Decision Matrix

A passive resistor wins on cost and simplicity. An active signal converter wins on isolation, true zero-based output, and long cable immunity. Use the matrix to pick.

CriterionResistor (passive)Signal converter (active)
Cost per channel< $1$30-$120
Galvanic isolationNone1500-3000 V typical
True 0-10 V outputNo (gives 2-10 V)Yes
Ground loop immunityVulnerableImmune
Cable length tolerance< 50 m typical> 500 m with shielded twisted pair
Field calibrationNone neededTrim pots or DIP switches
Failure modeOpen = no signal; short = full-scaleDiagnostic LED, fault output

A DIN-rail signal converter handles 4-20 mA ↔ 0-10 V either direction, with 24 VDC loop power, 2500 V isolation, and 0.1% accuracy. For hazardous-area service, look for an IECEx/ATEX zener barrier with isolated output in the same form factor. When the signal then feeds a SCADA-level analog input bank, the isolated converter also limits common-mode voltage entering the supervisory layer.

Reverse Path: 0-10 V to 4-20 mA

VFDs, lab power supplies, and HMI analog outputs often produce 0-10 V. Sending that signal to a DCS that expects 4-20 mA requires the reverse converter: a V/I converter chip (XTR110, AD694) on a board, or a packaged DIN-rail unit. Passive conversion is not possible — a resistor cannot generate a current loop. Loop power must come from somewhere, typically the DCS analog input itself or an external 24 VDC supply.

Common Mistakes in Field Installations

  • Resistor on the wrong side of the loop. Mounting at the transmitter cuts loop length immunity in half.
  • Using 250 Ω on a 0-10 V card. Output peaks at 5 V; PLC reads 50% at full sensor span.
  • Mixing carbon and metal-film resistors in spare-parts inventory. Temperature drift kills accuracy on outdoor panels.
  • Skipping isolation when sharing 0 V reference between multiple PLC racks. Ground loops appear as 50/60 Hz noise on the voltage signal.
  • Forgetting the live zero in PLC code. Process readings stuck at −25% LRV at idle are the symptom.

SI-300 Pressure Transducer (4-20 mA / Voltage)

Ranges 0-1000 bar | Output 4-20 mA, 0-5 V, 0-10 V | Accuracy ±0.25% FS — ships with selectable output for direct PLC wiring.

R7100 Universal-Input Paperless Recorder

Accepts 4-20 mA, 0-10 V, mV, RTD, thermocouple on the same channel — no resistor or converter required to log mixed-signal field instruments.

SI-512H High-Temperature Pressure Sensor

Process temp up to 800 °C | 4-20 mA two-wire output | Cooling fin design — for steam, hot oil, furnace headers feeding PLC analog inputs.

FAQ

What resistor converts 4-20 mA to 0-10 V?

A 500 Ω precision resistor gives 2-10 V, not 0-10 V, because the 4 mA live zero drops 2 V across 500 Ω. For a true 0-10 V output, use an active signal converter with zero adjustment, or apply two-point scaling in PLC code to handle the 2 V offset.

Why does 500 Ω not give 0 V at 4 mA?

Ohm's law: 4 mA × 500 Ω = 2 V. The 4 mA "live zero" is intentional. It lets the receiver detect a broken loop (0 mA = fault) versus a valid low reading. The 2 V offset must be handled in software or by an active converter.

What resistor for 4-20 mA to 1-5 V?

250 Ω. 4 mA × 250 Ω = 1 V; 20 mA × 250 Ω = 5 V. Specify 0.1% tolerance metal film, 0.25 W. The 1-5 V range was common on legacy DCS systems and still appears on some older Allen-Bradley 1771 modules.

Do I need an isolator between the sensor and PLC?

Yes, if the sensor and PLC share a long cable run (over ~50 m), if either device has a separate ground reference, or if 50/60 Hz hum appears on the signal. A DIN-rail signal isolator with 1500-3000 V galvanic isolation breaks the ground path.

Need spec help, a wiring drawing for a specific PLC, or a price on a DIN-rail signal converter? Send your project details — our instrumentation engineers reply within one business day.

Request a Quote

Please enable JavaScript in your browser to submit the form

RTD vs Thermocouple: Decision Matrix, Wiring & TCO Guide

An RTD (resistance temperature detector) measures temperature by tracking how the resistance of a platinum element rises with temperature. A thermocouple measures temperature by reading the millivolt signal produced when two dissimilar metal wires join at a hot end. Same goal, very different physics — and that difference is what makes one right for your tank, oven, or pipeline and the other a poor fit.

This guide gives you a 5-application decision matrix, the wiring rules that trip up most installers, and a 5-year cost comparison so you can make a defensible choice the next time procurement asks why you specified one over the other.

Contents

RTD and Thermocouple: Core Difference in One Sentence

An RTD changes its electrical resistance with temperature; a thermocouple generates a small voltage when its hot junction sees a different temperature than its cold junction. That single sentence drives every spec-sheet number that follows — accuracy, range, wiring complexity, drift, and cost.

The reference standards are IEC 60751 for platinum RTDs (Pt100 at 0 °C resistance of 100 Ω, α = 0.00385 Ω/Ω/°C) and IEC 60584 for thermocouples (covering Types K, J, T, N, S, R, B). Anyone selling you a sensor outside those standards is selling you trouble.

Working Principle: Resistance vs Voltage

A Pt100 RTD is a small platinum film or wire-wound coil whose resistance follows the Callendar−Van Dusen equation. Above 0 °C: R(T) = R₀[1 + AT + BT²], where R₀ = 100 Ω, A = 3.9083 × 10⁻³, B = −5.775 × 10⁻⁷. Drive a small constant current (typically 1 mA) through the platinum and you measure the resulting voltage; resistance follows by Ohm’s law.

A thermocouple is built from two dissimilar metal wires welded at one end (the measuring junction). When that junction is at a different temperature than the open end (cold junction), a millivolt-level Seebeck voltage appears. The relationship is non-linear, so the converter or transmitter uses a polynomial reference table from NIST ITS-90 to translate millivolts into temperature.

Accuracy and Stability Over Temperature

An IEC 60751 Class A Pt100 is rated to ±(0.15 + 0.002·|T|) °C. At 100 °C, that’s ±0.35 °C. A Class B Pt100 is ±(0.30 + 0.005·|T|) °C — about three times looser. RTDs drift by less than 0.05 °C per year if treated gently.

A Class 1 Type K thermocouple is rated to ±1.5 °C below 375 °C, then ±0.4% of reading above. At 1000 °C, that’s ±4 °C. Type T is the most accurate thermocouple, ±0.5 °C below 125 °C, but it only goes to 400 °C. Type S (platinum/platinum-rhodium) is more stable than K above 1000 °C but ten times the price.

Bottom line: below 600 °C, RTDs win on accuracy by a factor of five to ten. Above 600 °C, thermocouples are the only practical choice — RTDs cannot survive there long.

Temperature Range and Sensor Limits

SensorOperating RangeContinuous Use Limit
Pt100 RTD (thin film)−50 to +500 °C+400 °C
Pt100 RTD (wire-wound)−200 to +650 °C+600 °C
Type T thermocouple−200 to +400 °C+350 °C
Type J thermocouple−40 to +750 °C+700 °C
Type K thermocouple−200 to +1260 °C+1100 °C
Type N thermocouple−270 to +1300 °C+1200 °C
Type S / R / B0 to +1700 °C+1600 °C

Beyond the continuous limit, the platinum migrates in an RTD and the thermocouple wire alloys degrade. A K-type pushed past 1100 °C in air drifts at roughly 1–2 °C per 100 hours of operation. We’ve seen factory floors blame “controller drift” when the real problem was an exhausted K-type that nobody documented.

Response Time and Self-Heating

Thermocouples are faster. A 1.5 mm sheathed Type K reaches 63% of a step change in about 0.5 second in water, 5–7 seconds in air. A 6 mm sheathed Pt100 takes 3–4 seconds in water, 30+ seconds in still air. If you’re tuning a fast loop or chasing a transient, that gap matters.

RTDs also suffer self-heating: the 1 mA excitation current dissipates I²R in the element. A typical 100 Ω element with 1 mA gives 0.1 mW. In still air that’s enough to raise the reading by 0.05–0.1 °C, which is more than the Class A error budget. Thermocouples have no excitation current and no self-heating.

Wiring: 2/3/4-Wire RTD vs Type K/J/T Thermocouple

An RTD reading is just a resistance, so lead wire resistance adds directly to the measurement. A 2-wire RTD adds the full lead resistance — about 0.4 Ω per 10 m of 22 AWG copper, which is roughly 1 °C error. A 3-wire RTD subtracts one lead from the resistance bridge and cuts the lead error by about 90%. A 4-wire RTD passes current through two leads and measures voltage on the other two; lead resistance disappears from the math entirely. Use 4-wire for laboratory accuracy, 3-wire for everything else.

Thermocouples use extension wire of the same alloy as the thermocouple itself — never plain copper. Substituting copper extension on a Type K creates a second junction at the head, and that junction reads room temperature into your loop as a 4–6 °C offset. Color codes are international (IEC 60584): Type K is green positive / white negative; Type J is black/white; Type T is brown/white. For background on extension wiring conventions and shielded cables, see our note on shielded twisted-pair cables for industrial instrumentation.

For full Type K reference values, see the Type K thermocouple chart with mV reference and tolerance bands. For Pt100 element construction, see our WZP Pt100 series assembled thermal resistance page.

5-Year Cost of Ownership

Cost ItemPt100 RTD (Class A, 3-wire)Type K Thermocouple (Class 1)
Initial sensor + thermowell$140$70
Transmitter (4-20 mA)$110$95
3-wire cable (50 m)$95$210 (Type K extension)
Annual calibration (5 yrs)$60 × 5 = $300$40 × 5 = $200
Replacement during 5 yrs0 (typical)1 (high-temp service)
5-yr total$645$645 + $70 = $715

RTD wins on TCO in service below 600 °C even though the sensor itself costs twice as much. Two reasons: copper cable is much cheaper than Type K extension cable, and RTDs rarely need mid-service replacement. The math flips above 800 °C — RTDs cannot survive there, so the comparison ends.

Decision Matrix: 5 Common Industrial Applications

ApplicationTypical RangeRecommended SensorWhy
HVAC chiller water4 to 12 °CPt100 Class ATight accuracy needed for BTU calc
Boiler feedwater80 to 150 °CPt100 Class BStable, easy 3-wire run to PLC
Plastic injection mold180 to 280 °CType J or Pt100 wire-woundEither works; J is cheaper if many sensors
Heat-treat furnace700 to 1100 °CType K Class 1RTD cannot survive
Glass / kiln / cement1200 to 1600 °CType S or BOnly platinum-alloy TCs handle this

Common Selection Mistakes

  • Specifying Pt100 for a 1200 °C kiln. The platinum will diffuse into the sheath in weeks. Use Type S.
  • Running 2-wire RTD for a 30 m cable run. Lead-wire error swamps Class A accuracy. Use 3-wire minimum, 4-wire for lab work.
  • Reusing copper cable as Type K extension. You just put a 4–6 °C junction error at the head.
  • Mixing Type K and Type J how a pressure transmitter works. A Type J transmitter reading a Type K sensor under-reads by 30–40 °C at 500 °C.
  • Ignoring sheath material. Inconel 600 is fine in oxidizing air; in sulfur-bearing flue gas it pits in months. Spec Hastelloy or ceramic.

Featured Sensors from Sino-Inst

Pt100 Thermal Resistance RTD

IEC 60751 Class A | −200 to +650 °C | 2/3/4-wire — Pt100 element for HVAC, process, and lab measurement.

Industrial Thermocouple (K/J/N/T/S)

IEC 60584 Class 1 | Up to +1700 °C | Inconel / ceramic sheath — furnaces, kilns, and high-temperature process.

Universal-Input Temperature Transmitter

RTD or TC input | 4-20 mA / HART output | DIN-rail or head-mount — pairs with any sensor on this page.

Need help picking? Send your service conditions (medium, temperature range, pipe size, connection) to our engineers using the form below — we typically reply within one working day with a sized quote.

FAQ

Which is more accurate, RTD or thermocouple?

Below 600 °C, an IEC Class A Pt100 RTD beats any thermocouple by a factor of 5 to 10. Above 600 °C, RTDs degrade and thermocouples become the only practical choice.

Can I replace a thermocouple with an RTD?

Only if the service temperature stays under the RTD’s continuous limit (typically 600 °C wire-wound or 400 °C thin-film) and the transmitter accepts RTD input. You’ll also need to swap from thermocouple extension wire to plain copper.

What is the difference between Pt100 and Pt1000?

Both are platinum RTDs following IEC 60751. Pt100 has 100 Ω at 0 °C and is the industrial standard. Pt1000 has 1000 Ω at 0 °C; the higher base resistance makes lead-wire error 10x less important, so it’s popular in HVAC and 2-wire installations.

What is RTD full form?

RTD stands for Resistance Temperature Detector. It is a temperature sensor whose electrical resistance changes predictably with temperature. The most common type is the platinum Pt100 defined by IEC 60751.

Which thermocouple type should I use for general industrial work?

Type K is the default workhorse for 0–1100 °C — wide range, cheap, readily available. Use Type T if you need accuracy below 200 °C, Type J for older European installations, Type N for long-term stability above 800 °C, and Type S/R/B above 1100 °C.

How long does an RTD last in service?

Properly specified Pt100 RTDs in non-cycling service routinely last 10+ years with drift under 0.05 °C/year. Thermal cycling, vibration, and sheath corrosion shorten that life. We recommend a 12-month calibration check for any sensor in custody-transfer or food/pharma service.

Request a Quote

Please enable JavaScript in your browser to submit the form

Paperless Recorders for Industrial Measure & Control System

Paperless recorders are data loggers that record and trend measurement data over time — replacing strip-chart and circular recorders with a touchscreen, internal flash storage, and Ethernet/Modbus TCP/OPC UA export.

Sino-Inst supplies industrial paperless recorders with 4 to 64 universal-input channels (thermocouple, RTD, mV, 4–20 mA, 0–10 V, pulse). Models cover general-process duty (R7100), temperature-focused heat-treat / pharmaceutical service (R7600), and dedicated flow-totalizer applications (F3000X). 21 CFR Part 11 audit trail and AMS 2750E compliance options are available, with Modbus TCP, OPC UA, and MQTT for SCADA / MES integration.

Sino-Inst offers a variety of low pressure transducers for industrial pressure measurement. If you have any questions, please contact our sales engineers.

For the underlying control algorithm running inside this recorder, see our explainer on the PID controller working principle and Ziegler-Nichols tuning.

Description

The paperless recorder is an electronic instrument that samples industrial process signals through a 24-bit ADC, applies the standard linearization (IEC 60584 for thermocouples, Callendar-Van Dusen for RTDs, scaled engineering units for 4–20 mA), and writes the result to internal flash storage. Up to 64 channels per chassis with 3-way galvanic isolation between channel-channel, channel-power, and channel-comms.

Front-panel touchscreen for live trend, alarm history and configuration. Trend stored as a tamper-evident binary file plus CSV; signed-PDF export available for 21 CFR Part 11 batch reporting. Communications include Ethernet 10/100, Modbus TCP slave, OPC UA server, MQTT publisher, USB host, and RS-485 Modbus RTU.

Features of Paperless Recorder

  • Universal input: K/J/T/E/N/S/R/B thermocouple, Pt100/Pt1000 RTD, 4–20 mA, 0–10 V, ±100 mV, pulse 0.1 Hz–10 kHz.
  • 4 / 8 / 16 / 32 / 48 / 64-channel models — pluggable hot-swap input cards.
  • 24-bit sigma-delta ADC, 100 ms–1 s sampling, configurable per-channel storage interval.
  • 3-way galvanic isolation (channel-channel, channel-power, channel-comms).
  • 21 CFR Part 11 audit trail, AMS 2750E heat-treat, GAMP 5, IEC 61010-1 compliance options.
  • Communications: Ethernet, Modbus TCP, OPC UA, MQTT, RS-485 Modbus RTU, USB host/device.
  • Front-panel IP65 for wash-down food and pharmaceutical service.
  • 3.5" / 5.6" / 7" / 10.4" / 12" TFT touchscreen, 4 GB flash + SD card.

Specifications of Paperless Recorder

ParameterR7100 UniversalR7600 TemperatureF3000X Flow Totalizer
Channels4 / 8 / 16 / 32 / 648 / 16 / 322 / 4 (pulse + 4–20 mA)
Display5.6" / 7" / 10.4"7" / 10.4"5.6"
Memory4 GB + SD card4 / 8 GB + SD2 GB + SD
Sampling100 ms / 200 ms / 1 s200 ms / 1 s100 ms (pulse) / 1 s
Compliance21 CFR Part 11AMS 2750E + 21 CFR Part 11OIML R117 (custody)
CommunicationsEthernet, Modbus TCP, OPC UA, MQTTEthernet, Modbus TCP, OPC UAEthernet, Modbus TCP, RS-485
Power90–264 VAC / 24 VDC90–264 VAC / 24 VDC90–264 VAC / 24 VDC
Panel cutout144 × 144 / 144 × 288 mm144 × 144 / 288 × 288 mm96 × 96 / 144 × 144 mm
Front panel ratingIP65IP65IP65

Read more about: Common Units Of Pressure

Applications of Paperless Recorder

  • Heat-treat furnace AMS 2750E TUS — 9 thermocouples + 1 control = 16-channel R7600 with Class 1 calibration.
  • Pharmaceutical sterilizer / autoclave — 21 CFR Part 11 mode, F0 calculation, signed batch report.
  • Food retort cook-cool validation — 1-minute storage, F0 trend, IP65 wash-down front.
  • HVAC and energy monitoring — temperature + flow + pulse from kWh, Modbus TCP to BMS.
  • Boiler / CHP plant — steam temperature, drum level, fuel-flow trending.
  • Custody flow measurement — F3000X with density/temperature compensation, batch totalizer.

What is a paperless recorder?

The paperless recorder is a stand-alone process data logger that replaces a strip-chart or circular recorder. Where the older instrument drew an ink trace on paper as the chart wheel rotated, the paperless recorder samples the same inputs at 100 ms–1 s, displays the trend on a touchscreen, and stores the values to internal flash for compliance and audit retrieval.

The recorded data are written as a tamper-evident binary file plus a CSV companion. The binary is the legally defensible record (signed checksum); the CSV is the convenience export for spreadsheets. Trend data and configuration changes are timestamped against an NTP-synced clock so the audit trail satisfies FDA 21 CFR Part 11 and AMS 2750E requirements for pharmaceutical and aerospace heat-treat work.

How does a paperless recorder work?

The paperless recorder is built around an industrial microprocessor, a 24-bit sigma-delta ADC, RAM and flash storage, and a touchscreen front. Each input channel is multiplexed through the ADC at the configured sampling rate (typical: 1 s per channel for compliance work, 100–200 ms for combustion and compressor monitoring).

The microprocessor applies the appropriate linearization curve (IEC 60584-1 for thermocouples, Callendar-Van Dusen for Pt100/Pt1000 RTDs, scaled engineering units for 4–20 mA inputs), computes alarm logic (HiHi / Hi / Lo / LoLo with deadband and on-delay), and writes the storage-interval-averaged value to internal flash. On alarm, a burst-capture routine stores the full sampling-rate data around the event so post-incident analysis sees the raw waveform.

Q&A

Is a paperless recorder the same as a data logger?

Closely related but not identical. A data logger is typically a small standalone unit with battery power and limited inputs; a paperless recorder is panel-mounted, plant-powered, with a touchscreen, more channels, built-in alarms, and SCADA integration.

How many channels do I need for a typical heat-treat furnace?

AMS 2750E TUS (temperature uniformity survey) calls for 9 thermocouples on a 60-225 cubic-foot furnace plus the control thermocouple – 10 channels active. Allow one card-slot of headroom and pick a 16-channel R7100 or R7600.

What protocols are available for SCADA integration?

Modbus TCP slave is standard. OPC UA server, MQTT publisher, and Modbus RTU (RS-485) are option keys. USB host accepts a flash drive for ad-hoc CSV export; Ethernet web server allows browser-based trend download.

Do paperless recorders need calibration?

Yes – annually for compliance work, every 2 years for non-critical applications. Calibration is per channel and includes the cold-junction reference for thermocouple inputs. Field calibrators (Fluke 754, Ametek MC) inject known signals and write the verification result to the audit trail.

What if I lose power mid-batch?

Internal flash memory is non-volatile, so the recorded data up to the power-off instant is preserved. The recorder reboots and resumes; a power-loss event is logged in the audit trail. For absolute continuity, a small UPS or 24 VDC battery backup is the recommended add-on.

R7100 Universal-Input Recorder

4 to 64 channels, universal input (TC/RTD/mA/V), 7″ or 10.4″ touchscreen, 4 GB internal + SD, Ethernet + Modbus TCP.

R7600 Temperature Recorder

8 / 16 / 32-channel temperature-focused recorder. 24-bit ADC, 3-way galvanic isolation, AMS 2750E-ready trend export.

F3000X Flow Totalizer

Specialized flow-totalizer recorder: pulse + 4–20 mA input, density/temp compensation, batch totalizer, RS-485 Modbus.

Sino-Inst supplies paperless recorders globally — heat-treat, pharma, food, HVAC, boiler, custody flow.

Channel counts from 4 to 64. Universal-input cards. 21 CFR Part 11 / AMS 2750E compliance options. Modbus TCP, OPC UA, and MQTT for modern SCADA / MES / IIoT integration.

Sino-Inst is a Chinese manufacturer with a global distribution network. Paperless recorders are most popular in heat-treatment, pharmaceutical, food, HVAC, and boiler / CHP markets across North America, Europe, India, and Southeast Asia. Send your channel mix, panel cutout, communication protocol and certification target — our team will configure and quote within 24 hours.

Request a Quote

Please enable JavaScript in your browser to submit the form

Type K Thermocouple Chart: mV Reference, Tolerance, and Color Codes

A Type K thermocouple chart converts the millivolt output of a chromel/alumel junction into a temperature reading at 0 °C cold-junction reference. The chart is the IEC 60584-1 reference table — the same numbers used inside every Type K transmitter and recorder for cold-junction compensation. To use the chart correctly you need the formula Thot = chart−1(Vmeasured + Vcold-junction), the IEC tolerance class for your wire, and the regional color code so you do not reverse polarity.

Contents

How to Read the Chart with Cold-Junction Compensation

A Type K thermocouple does not directly measure the hot junction temperature — it measures the difference between the hot junction and the cold (reference) junction. The chart assumes the cold junction is at exactly 0 °C. In practice it is at room temperature, so the measurement procedure has three steps.

  1. Measure the thermocouple voltage Vtc with a high-impedance meter (>1 MΩ).
  2. Measure the cold-junction (terminal-block) temperature Tcj with a separate sensor — typically an internal RTD on the recorder or transmitter.
  3. Look up Vcj from the chart at Tcj, add to Vtc, then look up the temperature for the corrected mV. Thot = chart−1(Vtc + Vcj).

Worked example. The wire reads Vtc = 8.000 mV. The terminal block is at Tcj = 25 °C, which on the chart is Vcj = 1.000 mV. Total = 9.000 mV. From the Type K chart, 9.000 mV corresponds to about 221 °C. That is the hot-junction temperature. Skipping the cold-junction step in this example would have given 196 °C — 25 °C low, exactly the terminal-block error. Modern transmitters and recorders perform this correction automatically; if you ever read a Type K with a bench multimeter, do it manually.

For the broader comparison between resistance and voltage-based temperature sensors, see when to choose RTD over a Type K thermocouple.

Type K mV Reference Table (−200 to +1372 °C)

The full IEC 60584-1 chart for Type K covers 1572 °C of range in 1 °C steps. The condensed reference points below cover most engineering reads.

Temp (°C)EMF (mV)Temp (°C)EMF (mV)Temp (°C)EMF (mV)
−200−5.8912008.13880033.275
−100−3.55425010.15390037.326
−50−1.88930012.209100041.276
00.00040016.397110045.119
251.00050020.644120048.838
502.02360024.905130052.410
1004.09670029.129137254.886

The Seebeck coefficient (slope of the curve, dV/dT) is approximately 41 µV/°C across the working range — the highest among the base-metal types. That is why Type K is the workhorse of industrial temperature measurement: high signal-to-noise and a 41 µV resolution per 1 °C, comfortably above the ~10 µV input noise of any decent transmitter. For long-term recording on a multi-channel system see our paperless recorder selection guide.

Eight Thermocouple Types Compared at a Glance

The IEC standard defines eight letter-coded thermocouple types. Type K covers most general industry; the others fill out the high-temperature, vacuum, and precision corners.

TypeConductors (+ / −)Range (°C)Sensitivity at 25 °C (µV/°C)Best fit
KChromel / Alumel−200 to +137241General industry; oxidising atmosphere up to 1100 °C
JIron / Constantan−210 to +120052Vacuum, inert, reducing atmospheres; sensitive to oxidation above 540 °C
TCopper / Constantan−270 to +40043Cryogenic and food-process service; resists moisture corrosion
EChromel / Constantan−270 to +100068Highest sensitivity of the base-metal types; cryogenic precision
NNicrosil / Nisil−270 to +130039Drift-resistant alternative to K above 800 °C; aerospace and metallurgy
SPt-10%Rh / Pt0 to +176810Calibration standard; clean oxidising atmospheres up to 1450 °C
RPt-13%Rh / Pt−50 to +176811Industrial high-temperature reference; petrochemical, glass
BPt-30%Rh / Pt-6%Rh0 to +182010 (above 600 °C)Steel-mill, glass-melt; insensitive below 50 °C — no cold-junction compensation needed

Read the comparison this way: K is default, T for sub-zero, E for highest sensitivity, N when K drifts, S/R/B for very high temperatures. For the deeper trade-off vs platinum RTDs see our RTD vs thermocouple comparison.

IEC 60584 and ASTM E230 Tolerance Classes

Tolerance is the maximum permitted deviation between the actual emf and the standard table emf. IEC 60584-2 and ASTM E230 define three classes; the figure quoted on a thermocouple datasheet is the worst-case error before any in-house calibration.

ClassType K toleranceApplication
Class 1 (IEC) / Special (ASTM)±1.5 °C up to +375 °C, then ±0.4 % of readingLab, calibration, precision process
Class 2 (IEC) / Standard (ASTM)±2.5 °C up to +333 °C, then ±0.75 % of readingDefault industrial spec, most commercial wire
Class 3 (IEC, sub-zero only)±2.5 °C up to −167 °C, then ±1.5 % of readingCryogenic service; not a US-recognised class

A 1000 °C process measured with a Class 2 K thermocouple has up to ±7.5 °C tolerance from the wire alone. Add the transmitter’s ±0.1 % FS, the cold-junction compensation error of ±0.5 °C, and the cable termination drift, and the loop accuracy is around ±10 °C in the worst case. Class 1 wire halves the wire-side error to about ±4 °C and is worth the price premium for furnace control loops where a 5 °C swing changes the metallurgical result.

Color Codes: ANSI, IEC, JIS, BS

Color code is the most common cause of installation error. Type K wire is yellow under ANSI MC96.1 (US) but green under IEC 60584-3 (Europe). The negative leg is red under ANSI but white under IEC. Crossing the standards results in a polarity reversal and an apparent negative reading.

StandardRegionType K positiveType K negativeOuter jacket
ANSI MC96.1USAYellowRedYellow
IEC 60584-3Europe, IEC countriesGreenWhiteGreen
BS 1843UK (legacy)BrownBlueRed
JIS C 1610JapanRedWhiteBlue
DIN 43710Germany (legacy, replaced by IEC)RedGreenGreen

Two practical rules. First, always check the printed standard on the cable jacket before terminating; assume nothing from color alone. Second, the negative leg of every magnetic-iron type (K, J) is the magnetic conductor — alumel and constantan are weakly attracted to a small magnet, while chromel and iron-positive K are not. A field magnet test resolves polarity confusion in seconds.

Five Common Mistakes Reading a Thermocouple Chart

  1. Skipping cold-junction compensation. Reading the chart with only the field mV ignores the terminal-block temperature and produces an error equal to the room temperature in °C. Always add Vcj before the lookup.
  2. Using the wrong thermocouple type’s chart. Confusing K with J or N looks identical on a multimeter. Identifying by color or jacket print is mandatory; “looked like K” loses 5–10 % accuracy.
  3. Reversed polarity on extension wire. Connecting K-positive (yellow/green) to the transmitter’s negative input swings the reading symmetrically — a 200 °C source reads as if at the cold-junction temperature. Drift suddenly looks like the process is cold.
  4. Using copper extension wire on a Type K loop. Copper introduces a parasitic junction at the terminal block. The reading is right at room temperature and wrong everywhere else. Always use matching K extension wire (KX) up to the cold-junction reference point.
  5. Ignoring the upper limit. Type K above 1100 °C in oxidizing atmosphere drifts +1 to +2 °C per 100 hours from “green-rot” of the chromel leg. The chart is mathematically correct; the wire is not. For continuous service above 1100 °C use Type N or platinum-rhodium types.

Most of these errors are hidden by a transmitter’s burnout-protection and CJC logic; on a bench multimeter they are exposed. If a junior engineer is building a calibration rig from a multimeter and a thermocouple, walk through these five with them on day one. For the wiring side see our 4–20 mA transmitter wiring types guide.

Pt-Rh Type S/R/B Thermocouple

Standard platinum-rhodium element for service above 1300 °C. Type S/R/B options, ceramic or metal sheath, calibration certificate to IEC 60584 Class 1. Used where Type K drifts: glass-melt, steel ladle, gas-turbine combustor.

Furnace Thermocouple Assembly

Type K mineral-insulated assembly for kiln, furnace, and heat-treat service to 1200 °C. Inconel 600 sheath, optional alumina protection tube for atmosphere isolation, AMS 2750E calibration option for aerospace heat-treat lines.

Integrated Temperature Transmitter

Head-mounted 4–20 mA / HART transmitter for K, J, N, T, E, R, S, B thermocouples and Pt100/Pt1000 RTDs. Built-in cold-junction compensation, burnout detection, and IEC 60584 chart linearization. ATEX intrinsically safe option.

FAQ

How do you read a Type K thermocouple table?

Measure the thermocouple millivolts with a high-impedance meter, then add the cold-junction compensation millivolts read from the same chart at the terminal-block temperature. Look up the corrected total in the table to get the hot-junction temperature. Modern transmitters do this automatically; for a bench multimeter you do it by hand.

What is the temperature range of a Type K thermocouple?

−200 to +1372 °C per IEC 60584-1. Continuous service in oxidising atmosphere is rated to 1100 °C; intermittent service to 1300 °C. In reducing or sulfurous atmospheres the upper limit drops to about 800 °C because of green-rot drift in the chromel leg.

What is the millivolt output of a Type K at 100 °C?

4.096 mV at 100 °C with a 0 °C cold-junction reference, per the IEC 60584-1 table. Sensitivity is approximately 41 µV/°C across the working range, so each 1 °C change moves the output 41 µV — easily resolvable by a 16-bit transmitter.

Why is my Type K reading negative when the process is hot?

Polarity is reversed at the terminal block. The Type K positive leg is yellow under ANSI MC96.1 (US) and green under IEC 60584-3 (Europe). Connecting the wrong leg to the positive input swings the reading symmetrically. Swap the leads and verify with a small magnet — the alumel (negative) leg is magnetic.

What is the difference between Type K and Type J thermocouples?

Type K is chromel/alumel, range −200 to +1372 °C, sensitivity 41 µV/°C, default for general industry. Type J is iron/constantan, range −210 to +1200 °C, sensitivity 52 µV/°C, but the iron leg oxidises rapidly above 540 °C and so is restricted to vacuum, reducing, or inert atmospheres.

Do I need extension wire matching the thermocouple type?

Yes. Use Type KX extension wire on Type K loops, JX on Type J, and so on. Copper extension wire introduces a parasitic junction at the terminal block; the reading is right at room temperature and wrong everywhere else. The KX wire has lower-grade alloys than KP/KN element wire but matches the Seebeck curve over 0–200 °C.

What is “green-rot” in a Type K thermocouple?

Selective oxidation of the chromium in the chromel (positive) leg above 800–1100 °C. The leg turns greenish, the Seebeck coefficient drops, and the reading drifts low. Use Type N (nicrosil/nisil) above 1100 °C continuous service or platinum-rhodium types (S/R/B) for atmospheres rich in chromium-attacking species.

Need a thermocouple, transmitter, or paperless recorder configured for your temperature range and accuracy class? Send the temperature range, atmosphere, output requirement, and certification target — our engineering team will quote within 24 hours.

Request a Quote

Please enable JavaScript in your browser to submit the form

Natural Gas Pipeline Monitoring: Pressure-Temperature-Flow

As a clean energy, natural gas is widely used in many aspects such as industrial production, thermal power generation and residential gas heating.

Although natural gas pipeline transportation has many advantages, there are also risks such as leakage and failure. This can lead to interruptions or leaks in the delivery, causing significant financial losses and further safety risks. Therefore, sensors and data acquisition equipment are used for monitoring to achieve the purpose of leakage prevention and failure prevention. At the same time, risk issues such as distributed gas quality and consumption balance are monitored.

In the entire gas pipeline monitoring system, the detection of pressure-temperature-flow ensures operation, thereby preventing gas interruption.

Natural Gas Pipeline Pressure Measurement

In the oil and gas sector, pressure sensors are fundamental components for a wide range of applications. The pressure sensor can be used to monitor the pipeline pressure in real time. Not only that, the pressure sensor is also used in the gas furnace to measure the pressure of the gas in the gas supply pipeline, so as to judge whether the gas is sufficient or whether it is leaking.

  • Pressure transmitters play an important role in moving natural gas through thousands of natural gas pipelines. For monitoring natural gas pressure, measuring very low inlet and outlet pressures;
  • Various pressure types are also involved in the measurement process. Such as gauge pressure, absolute pressure, differential pressure, high pressure and differential pressure, etc.;
  • Special approval options such as ATEX Intrinsic Safety are available where natural gas may be present in the local atmosphere;
  • Leaks and even explosions may occur if the gas pressure in gas and gas pipelines is too high;
  • If the air pressure is too low, it will affect people’s daily use. Therefore, it is necessary to monitor the air pressure of each node through the pressure sensor, so that the air pressure is within a reasonable range;
  • The gas pipeline pressure sensor generally adopts the threaded installation form, which is simple and convenient and easy to ensure the sealing of the product. The signal output of the gas pipeline pressure sensor has analog signal and digital signal, which belong to the remote transmission type signal.

Sino-Inst’s pressure transmitter can be matched with industrial control system PLC or configuration system to ensure the accuracy and reliability of the automation system. The most important thing to choose a gas pipeline pressure sensor is to consider the quality of the product. The Sino-Inst gas pipeline pressure sensor is made of a corrosion-resistant pressure core and a stainless steel outer protective shell thread to ensure the durability of the product. The signal expansion transmitter also uses imported electronic components to ensure the stability of the gas pipeline pressure sensor.

Regardless of oil drilling, extraction, or transportation, there are various challenges and difficulties in the application of pressure sensors in the oil and gas industry. For example, key issues such as cost control, safe construction and environmental protection. Our engineers have rich practical experience in this industry, can fully understand the problems and difficulties you actually encounter in the oil and gas industry, and provide you with pressure measurement solutions based on your needs, combined with our own technology.

Featured Natural Gas Pressure Transmitters

Monitoring of Natural Gas Pipeline Temperature

General-purpose temperature transmitter, suitable for temperature measurement of gas or liquid, such as air, natural gas, steam, water or engine oil and other non-corrosive media. At the same time, a variety of analog and digital signal outputs are available for selection. It is convenient for users to form a measurement and control system with other equipment.

The temperature transmitter is based on a standardized Pt100 or Pt1000 temperature sensing element, providing customers with accurate and stable temperature measurement. The product is cost-effective and can meet various application requirements. It is an ideal product for temperature measurement.

In addition to gas pressure detection, we also provide Industrial Gas Measurement with Digital Gas Mass Flow Meters.

Featured Temperature Transmitters

Natural Gas Pipeline Flow Monitoring

The flow measurement of natural gas is currently mainly used in trade settlement and is relatively common. my country’s natural gas trade measurement is based on the volume or energy method under the legally required quality indicators for transfer measurement. At this stage, volume measurement is basically the main method.

At present, the flowmeter products used for natural gas flow measurement generally include: gas waist wheel flowmeter, gas turbine flowmeter, precession vortex flowmeter, vortex flowmeter, ultrasonic flowmeter and orifice flowmeter.

Let’s make a simple comparison on the use of these flow meters.

Natural Gas Flow Meter Types

Featured Natural Gas Flow Meters

More Gas Measurement Solution

In the entire gas pipeline monitoring system, the detection of pressure-temperature-flow is to ensure correct operation, thereby preventing gas interruption.

For the above characteristics, Sino-Inst provides high precision, good stability, low power consumption, easy to connect and supports customized pressure sensors, temperature sensors, flow meters, etc. Provide reliable pressure, temperature and flow monitoring support for gas pipeline monitoring.

Request a Quote

Please enable JavaScript in your browser to submit the form

RTD vs. Thermocouple: What’s the Difference, and Which Should You Use?

What is the difference between a resistance temperature detector (RTD) and a thermocouple? Both RTDs and thermocouples are sensors used to measure heat such as Fahrenheit and Kelvin. These devices are used in a wide range of applications and settings, often presenting people with the dilemma of choosing between RTDs or thermocouples. Each temperature sensor has its own advantages and disadvantages that make it suitable for certain conditions and environments.

What is RTD?

RTDs are made of metal wires, usually copper or platinum, that offer resistance to the flow of electricity. The RTD’s resistance changes when its temperature changes, allowing it to be used as a gauge for measuring heat. RTDs are considered to be more accurate than thermocouples as they have a linear relationship between resistance and temperature. RTDs are also less affected by electromagnetic fields than thermocouples.

RTD Working Principle

The full English name of RTD is “Resistance Temperature Detector”, so to be precise, it should be translated as “Resistance Temperature Detector”.

For a 5-application decision matrix and a 5-year cost-of-ownership comparison, see our decision matrix on RTD vs Thermocouple selection.

RTD is a special kind of resistor whose resistance value increases as the temperature increases and decreases as the temperature decreases. In industry, this feature is used for temperature measurement, so RTD is also commonly known as “thermal resistance”.

Not all metals are suitable for making RTDs. Materials that meet this characteristic need to meet the following requirements:

  • The resistance value of the metal has a linear relationship with the temperature change energy;
  • The metal is more sensitive to temperature changes, that is, the resistance change (temperature coefficient) caused by unit temperature changes is relatively large;
  • The metal can resist fatigue caused by temperature changes and has good durability;

There are not many metals that meet this requirement. Common RTD materials are: platinum (Pt), nickel (Ni), and copper (Cu).

Take platinum thermal resistance as an example. According to the different resistance values, it can be divided into Pt50, Pt100, Pt200, Pt500 and Pt1000.

The numerical value in the name indicates the resistance value of the thermal resistance at 0°C.

For example: Pt100, indicating that the resistance value of the sensor at 0°C is 100Ω.
And Pt1000, it means that the resistance value of the sensor at 0 ℃ is 1000Ω.
The resistance value of RTD thermal resistance at different temperatures can be approximated by the formula: R=R0(1+αT).

in:
1) R0 represents the resistance value of RTD at 0℃;
2) a is called the temperature coefficient, which represents the change value of the resistance at unit temperature;
3) T represents the measurement temperature, the unit is °C;

According to the number of lead wires of RTD thermal resistance, RTD can be divided into two-wire, three-wire and four-wire.

The lead of the two-wire RTD is to directly lead out two wires at both ends of the resistor to the temperature measurement module. The temperature measurement module adopts the principle of bridge balance, and RTD is used as one arm of the bridge to measure.

A three-wire RTD can largely eliminate the influence of the sensor leads themselves on the measurement results. The detection accuracy is greatly improved compared to the two-wire system.

Resistance Temperature Detector advantages

No compensation line is required, and the price is cheap;
It can transmit electrical signals over long distances;
High sensitivity and strong stability;
Good interchangeability and high precision.

Disadvantages of thermal resistance:

Although thermal resistance is widely used in industry. But it requires power excitation.
Temperature changes cannot be measured instantaneously.
The temperature measurement range is limited and the application is limited.

What is Thermocouple?

Thermocouples, on the other hand, are made of two different types of metals that are joined together at the sensor end. The junction between these two metals produces a voltage that is proportional to the temperature difference between the junction and the measuring point. Thermocouples are less expensive than RTDs and can measure a wider range of temperatures. They are also faster at responding to changes in temperature.

Thermocouple Working Principle

A thermocouple is a temperature sensing element. It converts the temperature signal into a thermoelectromotive force signal and converts it into the temperature of the measured medium through an electrical instrument.

The basic principle of thermocouple temperature measurement is that two homogeneous conductors of different compositions form a closed loop. When there is a temperature gradient at both ends, a current will flow through the loop. At this time, there is a seebeck electromotive force – thermal electromotive force between the two ends. This is called the Seebeck effect.

The two homogeneous conductors with different compositions are the hot electrodes, and the end with the higher temperature is the working end. The end with the lower temperature is the free end. The free end is usually at some constant temperature.

According to the functional relationship between thermoelectromotive force and temperature, a thermocouple indexing table is made. The index table is obtained under the condition that the free end temperature is at 0°C. Different thermocouples have different scales.

When a third metal material is inserted into the thermocouple loop. As long as the temperature of both junctions of the material is the same. The thermoelectric potential generated by the thermocouple will remain constant. That is, it is not affected by the access of the third metal into the loop.

Therefore, when measuring the temperature of the thermocouple, the measuring instrument can be connected. After measuring the thermoelectromotive force, the temperature of the measured medium can be known.

Thermocouple Advantages:

  1. High measurement accuracy: The thermocouple is in direct contact with the measured object and is not affected by the intermediate medium.
  2. Fast thermal response time: Thermocouples are sensitive to temperature changes.
  3. Large measurement range: thermocouples can measure temperature continuously from -40 to +1600 °C.
  4. Reliable performance and good mechanical strength.
  5. Long service life and easy installation.

Types and structures of thermocouples

Types of thermocouples Thermocouples include k type (nickel-chromium-nickel-silicon), n-type (nickel-chromium-silicon-nickel-silicon-magnesium), e-type (nickel-chromium-copper-nickel), j-type (iron-copper-nickel) , t-type (copper-copper-nickel), s-type (platinum-rhodium 10-platinum), r-type (platinum-rhodium 13-platinum), b-type (platinum-rhodium 30-platinum-rhodium 6) and so on.

Structural form of thermocouple: The basic structure of a thermocouple is a thermal electrode, an insulating material and a protective tube. Display instrument, recording instrument or computer and other supporting use. In field use, thermocouples suitable for various environments are developed according to various factors such as the environment and the measured medium.

Frequently
Asked
Questions

RTD stands for Resistance Temperature Detector, but is also known as PRT (Platinum Resistance Thermometer).

A platinum resistance thermometer (PRT) is an RTD that uses platinum as the sensing element. The most common PRTs are Pt100, Pt500 and Pt1000. (PRT is just a more specific name for RTD)

The first step in identifying an RTD is to find out how many lines it has (2, 3 or 4).
Then you can connect the RTD to the multimeter.
If it’s a pt100, it should read between 107-110Ω at room temperature.
But if it’s a pt1000. You should get a reading of 1007 – 1100Ω. This confirms it’s a Pt1000.

PLEASE NOTE: These readings are standard for new RTD sensors. If the sensor is damaged or used continuously. The readings may vary.

The international standard IEC 60751:2008 defines the resistance versus temperature characteristics of RTDs. Within this standard, in order to provide good interchangeability, there are standards of accuracy. Class A and Class B are two accuracy standards. We provide a tolerance reference table.

We get asked this question a lot, but Pt100s and Pt1000s are two types of RTDs (Pt500s are another type of RTD, but now obsolete).

RTDs use cables because they detect temperature by calculating resistance changes in the material. So you can simply order RTDs with long leads or buy additional cables to expand on your own.

When choosing an RTD, the following factors must be considered:

  • What temperature are you measuring (surface or immersion in solid, liquid or gas)?
  • If a fast response time is a must, see the RTD Technology page for various factors in selecting a response time.
  • Fits the specific dimensions required for your application, such as probe diameter, probe length, compression fittings, required connector types, etc.
  • Do you need special sheath materials?
  • Do you need to calibrate the sensor?
  • Does the sensor need to be resistant to chemicals/abrasion/vibration or any other environmental factors?
  • Is there high electromotive force (electromagnetic interference) in power switching, rectification or radio waves?
  • Any other installation considerations? (eg sensor needs to be bent to form before installation)
  • Distance between sensing area and instrument
  • Sensing ambient temperature over sensor length
  • Connection Preferences
  • Current wiring configurations such as 4-wire sensors will not be compatible with 3-wire configurations.

As a rule of thumb, RTDs should be immersed 4 times the length of the element. (Flat-film elements are typically 2-3mm, while wire-wound elements are about 15mm or more).

We are often asked this question, but Pt100 thermocouples do not exist. A thermocouple is a type of sensor, and a Pt100 is a type of RTD, another type of sensor.

A Pt200 sensor is an RTD, Pt200s have a resistance of 200 ohms (Ω) at 0ºC. The Pt200 sensor is now obsolete and has been replaced by the Pt100 and Pt1000 sensors. The Pt500 sensor is also an outdated RTD.

A Pt500 sensor is an RTD, Pt500s have a resistance of 500 ohms (Ω) at 0ºC. The Pt500 sensor is now obsolete and has been replaced by the Pt100 and Pt1000 sensors. The Pt200 sensor is also an outdated RTD.

Conclusions, which one should you use?

It really depends on the specific application and what is more important: accuracy or speed. If you need to measure very high or very low temperatures, a thermocouple is the better choice. If you need more accuracy, then an RTD is the way to go.

Read more about: What Is 0-10V Signal Output?

Temperature Measurement Solutions

  • Standard Platinum Rhodium Thermocouple

    Standard Platinum Rhodium Thermocouple-Platinum Thermocouple Standard Platinum Rhodium Thermocouple is a temperature measurement standard device produced by our company. There are two types of standard platinum-rhodium 10-platinum thermocouple and standard…
  • Furnace thermocouple Topics

    How does a furnace thermocouple work? In industrial furnaces, armored thermocouples are often used as Furnace thermocouples. The thermocouple body has a metal sheath, which can directly measure the temperature…
  • Guidebook: Bimetallic Stemmed Thermometer

    A bimetallic stemmed thermometer is a simple but effective tool used in a variety of industries, including food, HVAC, medical, and automotive. It’s easy to use, requires no external power…
  • Temperature Sensor Transmitter—-Do You Know?

    Temperature sensor transmitter is a combination of temperature sensor and temperature transmitter. It can be used in chemistry and medicine. Thermocouple, thermal resistance and temperature transmitter of SBW series are…

Sino-Inst is Manufacturer of RTD & Thermocouples for temperature measurement. We supply more than 20 kinds of RTD & Thermocouples. 40% RTD, 60% Thermocouples.

RTD & Thermocouples for diesel fuel measurement are mainly used for temperature measurement of various meadium.

RTD & Thermocouples enable stable temperature measurement. This greatly meets the measurement needs of many applications.

Sino-Inst’s RTD & Thermocouples for temperature measurement, made in China. Having good Quality, With better price. Our temperature measurement instruments are widely used in China, India, Pakistan, the US, and other countries.

The entire team at Sino-Inst’s has received excellent training, so we can ensure that every client’s needs are met. For assistance with your product requirements, whether it’s a RTD & Thermocouples for temperature measurement, flow sensor, or other device, give us a call.

Request a Quote

Please enable JavaScript in your browser to submit the form

Standard Platinum Rhodium Thermocouple

Standard Platinum Rhodium Thermocouple-Platinum Thermocouple

Standard Platinum Rhodium Thermocouple is a temperature measurement standard device produced by our company. There are two types of standard platinum-rhodium 10-platinum thermocouple and standard platinum-rhodium 30-platinum rhodium 6 thermocouple.


First-class standard thermocouple WRPB-1


Second-class standard platinum rhodium 30-platinum rhodium 6 thermocouple


Second-class standard thermocouple WRPB-2

The standard platinum rhodium 10-platinum thermocouple is used to realize the thermocouple temperature measurement value transfer and precise temperature measurement in the temperature range of 419.527~1084.62 ℃. The accuracy grades are first-class and second-class standards.

The standard platinum rhodium 30-platinum rhodium 6 thermocouple is used for the value transfer and precision temperature measurement of the current thermocouple in the temperature range of 1100~1500℃. The accuracy grade has the second-class standard.

First-Class Standard Thermocouple WRPB-1

The first-class standard thermocouple is also called the first-class standard platinum rhodium 10-platinum thermocouple. The first-class standard thermocouple is used to verify the second-class standard thermocouple. The first-class standard platinum-rhodium 10-platinum thermocouple verifies the second-class standard platinum-rhodium 10-platinum thermocouple.

The first-class standard thermocouple WRPB-1 is one of the world’s first-class temperature measurement standard devices.

Standard thermocouples are divided into first-class standard thermocouples and second-class standard thermocouples.

The standard thermocouple is of higher precision in the thermocouple series and has good physical and chemical properties. Good oxidation resistance at high temperatures. Thermocouple with good stability and reproducibility of term electromotive force.

  1. Model: WRPB-1
  2. First-class standard thermocouple length: L=Φ0.5×1000mm
  3. The temperature range of the first-class standard thermocouple: 300-1300℃
  4. First-class standard thermocouple indexing number: S type (platinum rhodium 10-platinum)
  5. First-class standard thermocouple electric potential value requirements:
    The measuring end of the standard thermocouple (WRPB-1) is at the copper point (1084.62℃) or the antimony point (630.63℃) and the zinc point (419.527℃).
    When the reference junction temperature is 0℃, its thermoelectric potential should meet the following requirements:
    E(tCu)=10.575±0.015mv
    E(tAl)=5.860+0.37[E(tCu)-10.575]±0.005mV
    E(tAsb)=5.553+0.37[E(tCu)-10.575] ±0.005mV
    E(tZn)=3.447+0.18[E(tCu)-10.575] ±0.005 mV  
  6. The stability of the first-class standard platinum-rhodium 10-platinum thermocouple is determined by the difference between the two thermoelectric potentials and does not exceed 3uV. The annual variation of the thermoelectric potential of the copper point of WRPB-1 does not exceed 5uV.

The first-class standard platinum-rhodium 10-platinum thermocouple has a platinum-rhodium wire for the anode and a platinum wire for the anode. A double-hole insulated porcelain tube with a length of 550 mm is sheathed on it.
Refer to the positive terminal to cover the red or pink plastic tube; the negative terminal to cover the white or blue plastic tube.
The whole product is stored in an ordinary glass outer tube.

How to use first-class standard thermocouple

Before using WRPB-1, check whether the thermocouple number is consistent with the product number on the verification certificate.

When in use, take the standard couple out of the glass outer protective tube and put it into the quartz outer protective tube to measure. After use, put it back into the glass outer protective tube for storage.

When using the standard coupler WRPB-1 to verify the standard coupler WRPB-2. The reference terminal of the standard coupler and the thermocouple under test should be at 0℃. The specific method steps are carried out in accordance with the “Standard Platinum Rhodium 10-Platinum Thermocouple Verification Regulations” (JJG75-1995) approved and issued by the National Quality and Technical Supervision Bureau.

When a standard couple is used for precise temperature measurement, the temperature t is determined by the following formula: (omitted here). When measuring the temperature, you should first prepare the corresponding E(t)-t comparison table according to the approximate temperature range of the thermocouple. Then according to the thermoelectric potential value measured by the thermocouple, the temperature t can be obtained according to the comparison table compiled above. The temperature interval of the comparison table is set by the user. If the accuracy requirement is not too high, a comparison table of the entire Baidu interval can be compiled.

Precautions for the use of first-class standard thermocouples

  1. When using and storing, the porcelain tube and plastic tube on the standard thermocouple shall not be arbitrarily removed. Try to keep the standard flat and straight. The WRPB-1 thermocouple shall not be severely bent. Quartz outer protective tube should be added. During transportation and storage , The standard thermocouple WRPB-1 should be avoided from being subjected to severe mechanical shock.
  2. According to “Standard Platinum Rhodium 10-Platinum Thermocouple Verification Regulations” (JJG75-1995), regular supervisory inspection and periodic verification shall be carried out.
  3. Please keep the verification certificate attached to the Sino-Inst product when it leaves the factory. You must bring the original verification certificate with you during the next verification.

Due to the frequent changes in precious metal prices recently, our company’s production costs have changed accordingly. For the price of WRPB-1 first-class standard thermocouples, please contact Sino-Inst sales engineers directly.

Second-Class Standard Thermocouple WRPB-2

Second-class standard thermocouples are used for thermocouples and precision temperature measurement in the temperature range of 300-1300℃. The second-class standard thermocouple needs to be verified with the first-class standard thermocouple of the next higher grade.

The second-class standard thermocouple is the standard instrument for verifying industrial thermocouples. Sino-Inst is the leading manufacturer of domestic standard thermocouples. For 20 years, it has provided high-quality, high-stability second-class standard platinum-rhodium 10-platinum thermocouples to various industries . The second-class standard thermocouple model of our factory is WRPB-2, which has a good reputation for quality. Buying second-class standard thermocouples from standard thermocouple manufacturers will get technical support and products with lower prices.

  1. Second-class standard thermocouple model: WRPB-2
  2. The temperature measurement range of the second-class standard thermocouple: 300-1300℃
  3. The length of the second-class standard thermocouple: L=1000mm (the diameter of the coupler wire is Φ0.5mm)
  4. Indexing number: S type (platinum rhodium 10-platinum)
  5. Second-class standard thermocouple electric potential value requirements:
    • A. The second-class standard thermocouple (the second-class standard platinum rhodium 10-platinum thermocouple) is at the copper point (1084.62℃), aluminum point (660.323℃) or antimony point (630.63℃) and zinc point (419.527℃). When the reference junction temperature is 0℃, its thermoelectric potential should meet the following requirements:
      E(tCu)=(10.575±0.015)mv
      E(tAl)=5.860+0.37[E(tCu)-10.575]±0.005mV
      E(tAsb)=5.553+0.37[E(tCu)-10.575] ±0.005mV
      E(tZn)=3.447+0.18[E(tCu)-10.575] ±0.005 mV
    • B. The stability of the second-class standard thermocouple is determined by the change of the electromotive force of its copper point (the difference between the two thermoelectric potentials). The newly manufactured second-class standard thermocouple does not exceed 5μV, and the second-class standard thermocouple in use is of The annual change does not exceed 10μV.
    • C. For the frequently used second-class standard thermocouple (second-class standard platinum rhodium 10-platinum thermocouple), in order to ensure the accuracy and reliability of the value, the necessary supervisory verification should be carried out according to the use situation. The second-class standard thermocouple supervisory verification is based on the first-class standard thermocouple (first-class standard platinum rhodium 10-platinum thermocouple) or the infrequently used second-class standard thermocouple as the standard device, and its qualification is determined by the copper point. The difference between the measured thermoelectric potential and the thermoelectric potential given by the metrological verification certificate is determined (the difference is not more than 7μV).
    • D. The standard thermocouple certified by the third-party metrological verification agency authorized by the General Administration of Quality Supervision, Inspection and Quarantine of the People’s Republic of China in compliance with “JJG75-1995 “Standard Platinum Rhodium 10-Platinum Thermocouple” National Metrological Verification Regulations” will be issued a verification certificate. The effective digits of the second-class standard thermocouple thermoelectromotive force value given in the metrological verification certificate are 3 digits after the decimal point (see the following certificate data for details).
    • E. The verification period of the second-class standard hot platinum rhodium 10-platinum galvanic couple is one year. The product needs to be sent to a legal metrological verification agency for verification before the expiration of the metrological verification certificate to avoid delay in use.

The second-class standard thermocouple (second-class standard platinum-rhodium 10-platinum thermocouple) positive electrode is platinum rhodium 10 wire. The negative electrode is platinum wire. It is sheathed with a double-hole insulated porcelain tube with a length of 550 mm.
Reference end positive sleeve red or pink plastic tube. Negative sleeve white or blue plastic tube.
The whole product is stored in a glass outer tube.

How to use the second-class standard thermocouple

  1. Before use, check whether the second-class standard couple number is consistent with the product number on the verification certificate. The product and the measurement verification certificate are one-to-one correspondence. The product number is inconsistent with the thermocouple number on the certificate. It means that the certificate is not the thermocouple Even the certificate of metrological verification.
  2. When the product leaves the factory, there is a quartz tube (approximately 550mm long) and a common glass tube in the container. When using, take the second-class standard couple out of the glass tube and put it into the quartz outer protective tube for measurement. After use, put the second-class standard hot platinum rhodium 10-platinum galvanic couple back into the glass outer protective tube for storage.
  3. When using the second-class standard thermocouple WRPB-2 to verify the working thermocouple. The reference end of the second-class standard couple and the thermocouple under test should be at 0°C. The specific methods and steps are carried out in accordance with the verification regulations of “JJG75-95 Standard Platinum Rhodium 10-Platinum Thermocouple” approved and issued by the Quality and Technical Supervision Bureau. 
  4. When the second-class standard couple is used for precise temperature measurement, the temperature t is calculated according to the “standard thermocouple thermoelectromotive force-temperature conversion method” in the metrological verification regulations. When measuring the temperature, the second-class thermocouple should be roughly used according to the temperature range . Compile the corresponding E(t)-t comparison table. Then according to the thermoelectric potential value measured by the thermocouple, the temperature t can be obtained according to the comparison table prepared above. The temperature interval of the comparison table is set by the user. If the accuracy requirement is low, a comparison table of the entire Baidu interval can be compiled.

Precautions for the use of second-class standard thermocouples

  1. When using and storing the second-class standard thermocouple (the second-class standard platinum rhodium 10-platinum thermocouple). The porcelain tube and plastic tube on the second-class standard thermocouple shall not be arbitrarily removed. Try to keep the standard straight. Do not use The thermocouple is severely bent. Quartz outer protective tube should be added. During transportation and storage, avoid the standard second-class standard platinum rhodium 10-platinum thermocouple WRPB-2 from being subjected to severe mechanical shock.
  2. According to the verification regulations of “JJG75-95 Standard Platinum Rhodium 10-Platinum Thermocouple”, the second-class thermocouple shall be regularly inspected and periodically verified.
  3. Please keep the verification certificate attached to the second-class standard thermocouple when leaving the factory. The user must bring the original verification certificate for the next verification. If there is no certificate, it will not be used as a second-class standard thermocouple.

At present, the price of precious metals changes frequently. Sino-Inst produces standard thermocouples using precious metal wires. The cost varies with market prices. For the price of WRPB-2 second-class standard couples, please contact our sales engineers directly.

Second-Class Standard Platinum Rhodium 30-Platinum Rhodium 6 Thermocouple

The second-class standard platinum rhodium 30-platinum rhodium 6 thermocouple is a standard instrument for temperature value transfer in the temperature range of 1100-1500℃. It is usually used to verify industrial platinum and rhodium thermocouples. It is also used for the measurement range of 1100-1500℃. Precision measurement.

  1. The first-class standard platinum rhodium 30-platinum rhodium 6 thermocouple and the second-class standard platinum rhodium 30-platinum rhodium 6 thermocouple are produced with high-purity standard thermocouple wire. Its positive electrode (BP) is platinum containing 30% rhodium Rhodium alloy. The negative electrode (BN) is a platinum-rhodium alloy containing 6% rhodium.
  2. The wire diameter of the standard platinum rhodium 30-platinum rhodium 6 thermocouple (referred to as the standard double platinum rhodium thermocouple) is 0.5mm and the length is 1000mm.
  3. When the second-class standard platinum rhodium 30-platinum rhodium 6 thermocouple temperature at the measuring end is 1100°C and 1500°C, and the reference end temperature is 0°C, its thermoelectromotive force should be:
    E(1100)=(5.780±0.025)mV
    E(1500)=(10.099±0.040)mV
  4. The stability of the standard double platinum and rhodium thermocouple. Platinum and rhodium are determined by its thermoelectromotive force change at 1500℃: the first-class standard platinum-rhodium 30-platinum rhodium 6 thermocouple is not greater than 6μV. The second-class standard platinum rhodium 30-platinum The rhodium 6 thermocouple is not more than 8μV.
  5. The measuring end of the standard double platinum and rhodium thermocouple is sleeved with a double-hole 550mm high-purity alumina tube. The reference end is a pink plastic tube for the positive electrode and a white plastic tube for the negative electrode.
  6. The second-class standard platinum rhodium 30-platinum rhodium 6 thermocouple has no protective tube when it leaves the factory. When not in use, it is placed horizontally in a clean glass tube in a special container. It is stored under stress-free conditions.

Reference end positive sleeve red or pink plastic tube. Negative sleeve At present, the price of precious metals changes frequently. Sino-Inst produces standard thermocouples using precious metal wires. The cost varies with market prices. For the price of WRPB-2 second-class standard couples, please contact our sales engineers directly.

Frequently
Asked
Questions

Platinum and its alloys will withstand more adverse conditions than base metal thermocouples. But they still have their limitations. The melting point of platinum is 1769°C, and the melting point of the highest melting point of rhodium alloy used for thermocouple applications is about 1890°C.

Platinum is not equal to a thermocouple. Platinum is a material that can be used to make thermocouples.

In theory, any two different conductors (or semiconductors) can be made into thermocouples. But as a practical temperature measuring element, there are many requirements for it. In order to ensure the reliability in engineering technology and sufficient measurement accuracy. Not all materials can make up a thermocouple. Generally, the basic requirements for the electrode materials of thermocouples are:

  1. In the temperature measurement range, the thermoelectric properties are stable, do not change with time, have sufficient physical and chemical stability, and are not easy to be oxidized or corroded;
  2. The temperature coefficient of resistance is small, the conductivity is high, and the specific heat is small;
  3. The thermoelectric potential generated in temperature measurement should be large, and the relationship between thermoelectric potential and temperature is linear or close to linear single value function;
  4. The material has good reproducibility, high mechanical strength, simple manufacturing process and low price.

Platinum rhodium thermocouple is also called a high-temperature precious metal thermocouple. Platinum rhodium has single platinum rhodium (platinum rhodium 10-platinum rhodium) and double platinum rhodium (platinum rhodium 30-platinum rhodium 6). As temperature measurement sensors, they are usually used in conjunction with temperature transmitters, regulators, and display instruments. A process control system is formed to directly measure or control the temperature of fluids, steam and gaseous media, and solid surfaces in the range of 0-1700°C during various production processes.

Extended reading: RTD vs. Thermocouple: What’s the Difference, and Which Should You Use?

Related Blogs

Sino-Inst, Manufacuturer for Temperature Transmitters, like: Armoured thermocouple, assembly thermocouple, explosion-proof thermocouple, etc.

Sino-Inst’s Temperature Transmitters, made in China, Having good Quality, With better price. Our Temperature measurement instruments are widely used in China, India, Pakistan, US, and other countries.

Request a Quote

Please enable JavaScript in your browser to submit the form

Furnace thermocouple Topics

How does a furnace thermocouple work?

In industrial furnaces, armored thermocouples are often used as Furnace thermocouples. The thermocouple body has a metal sheath, which can directly measure the temperature of the medium. Or it can be placed in a protective tube as a temperature measurement core element. It has the advantages of bending, high-pressure resistance, fast thermal response time, sturdiness, and durability.

Armored thermocouples are usually used in conjunction with display instruments, paperless recorders and regulators. It can measure the temperature of liquid, vapor and gaseous media and solid surfaces in the range of 0-1600°C during various production processes.

Place the thermocouple core wire and inorganic mineral insulating material in a metal sleeve. The stretched solid assembly that can be wound becomes an MI Cable.

The armored thermocouple cable made of thermocouple wire as the core is welded to form the measuring end and assembled with the relevant junction box. The thermocouple is called the armored thermocouple. Furnace thermocouples can be manufactured into insulated, grounded, and exposed-end types as required.

Furnace thermocouple-Solution for coal chemical gasifier

The gasifier is the most representative device of the coal chemical industry. Sino-Inst is based on the special conditions of the TEXACO gasifier and the Shell gasifier. It shares the special structure and material selection of the gasifier thermocouple and other professional knowledge. Help users solve special problems The problem of temperature measurement in the occasion.

Accurate measurement and strict control of temperature are the key factors to ensure the normal operation of the process. It will directly affect whether the process is carried out under ideal conditions. It will even affect the service life, safety production and environmental protection of the overall equipment.

The temperature measurement conditions of TEXACO gasifiers and Shell gasifiers in the coal chemical industry are extremely specific due to the gasifier body structure, internal medium, reaction process, and operating conditions. Therefore, the choice of the corresponding Furnace thermocouple also highlights its special importance and complexity.

The author relies on many years of rich experience. The representative and typical working conditions of TEXACO gasifier and Shell gasifier. As well as the selection principles and precautions of the corresponding thermocouples, which I will discuss with you. It aims to provide reference guidance and suggestions for coal chemical users.

1.TEXACO gasifier

① Operating conditions of TEXACO gasifier

Representative sites of TEXACO gasifiers include Ningxia Coal Group’s 250kt/a methanol plant, Shenhua Baotou and Inner Mongolia Jiutai Energy’s coal-to-olefin project.

The above site adopts the TEXACO rapid cooling process and the whole waste boiler process, which is the most advanced energy-saving process in the world.

TEXACO gasifier has special working conditions such as high temperature, high pressure, coexistence of oxidizing and reducing atmospheres, strong scouring, and sudden changes in temperature and pressure.

The operating temperature of the combustion chamber is 1350-1500℃, and the operating pressure is 2.5-8.7 MPa.

The flame gas contains CO, H2, CO2, H2O, CH4, Ar, N2 and H2S and other components.

The melting point of coal ash is 1310-1370°C.

The shell of the combustion chamber and the lining refractory bricks are likely to shear each other due to the different coefficients of thermal expansion.

The most important thing is that the scouring and abrasion in the gasifier is extremely serious, so the measuring point of the thermometer must be located 15-25mm away from the inner wall of the furnace wall.

However, it is difficult to ensure uniformity in the furnace wall during the masonry process. Coupled with the existence of scouring and wear in the furnace. The furnace wall will be inevitably thinned gradually during the production process.

②The performance requirements of TEXACO gasifier for Furnace thermocouple:

Due to the special working conditions of the above-mentioned TEXACO furnace, the temperature sensor must be able to withstand a high temperature of 1600°C and a high pressure of 8.7MPa.

It can resist the double corrosion of oxidizing and reducing gas at the same time.

It has an adjustable insertion length and a follow-up structure. When the inner lining changes in thickness and torsion and shear, corresponding structural changes can be made.

③Temperature measurement solution for TEXACO gasifier

In response to these requirements, the Furnace thermocouple is designed with special materials and structure. It satisfies the harsh requirements of the gasifier operating conditions for the temperature sensor. It is a kind of thermocouple special for gasifiers with adjustable anti-vibration, erosion resistance, anti-oxidation, and multi-stage leakage resistance.

First of all, the main structure of the Furnace thermocouple adopts the design concept of adjustable anti-vibration.

When the thickness of the gasifier wall lining changes, the Furnace thermocouple can be adjusted within the range of ±120mm through the shrinkable threaded sleeve. In order to achieve the measurement, the element is always maintained in the best position.

When the furnace shell and the inner lining are sheared, the universal rotating ball can be used to make the probe rotate with the inclination. And under the action of the limit guide tube and the correction damping spring.

Keep the probe always in the correct position in the center of the wall bushing. It prevents the thermocouple of the gasification furnace from being broken when the furnace wall is deformed.

Multi-stage leak-proof structure design. When the thermowell is damaged, it can prevent convection between the inside of the furnace and the outside through the sleeve. Safety hazards caused by high temperature conduction or even leakage in the furnace. Reflect safety awareness and environmental protection concepts.

Secondly, the Furnace thermocouple protection tube material adopts imported silicon carbide material made by pressureless sintering of sub-micron silicon carbide powder. The material has the dual characteristics of ceramic and metal and can be used reliably even at high temperatures exceeding 1750°C.

Its thermal conductivity is equivalent to stainless steel, 5 times that of alumina. Hardness is one of the high-performance materials second only to diamond. Ultra-fine crystals smaller than 10μm have been tested by helium gas leak detection.

The porosity is almost 0, which can effectively prevent H2 and CO from damaging the Furnace thermocouple wire through the pores on the tube wall. Ultra-high hardness and density make it have ideal wear resistance and long-term resistance to material erosion. It can work in oxidizing and reducing atmospheres and corrosive environments of strong acids and alkalis even at ultra-high temperatures.

2.Shell gasifier

At present, more than ten sets of Shell gasifiers have been introduced in China. Representative sites are Henan Kaixiang Methanol Project, Yunwei Group’s synthetic ammonia and Guangxi Liuhua coal gasification plants.

①Shell gasifier operating conditions characteristics

Conditions to ensure the normal operation of Shell gasifiers:

Neither can cause damage to the over-temperature of the vaporizer. It is necessary to consume the lowest amount of oxygen as much as possible. To achieve complete carbon conversion, temperature control is essential.

However, the structural characteristics of the Shell gasifier determines that the temperature of the gasifier cannot be directly measured. It can only be controlled by indirect methods.

An “annular space” is formed between the inner membrane wall of the gasification furnace and the outer shell. Hot syngas cannot escape into the “annular space”, causing the shell to overheat. Calculating the temperature in the furnace by measuring the temperature of the water wall in the “annular space” is the characteristic of Shell gasification furnace temperature measurement.

The temperature in the “annular space” is collected at multiple points, and each temperature measurement point is the key to understanding whether the gasifier is operating normally. If there is any abnormality, find and analyze the cause immediately. And deal with it in time, otherwise it will cause major damage to the gasifier.

②Shell gasifier performance requirements for Furnace thermocouples

Because the pulverized coal of Shell gasifier is 4MPa. It is combusted with O2 and steam in a gasifier at around 1500°C. And when it was sent to the coal burner, it was already under a pressure of 2MPa. Therefore, the thermometer is required to have a pressure resistance of not less than 2MPa. It also has emergency measures in case of overpressure, and can withstand a high temperature of 1500°C.

Because the Shell gasifier is composite equipment that integrates dynamic and static equipment, as well as combustion, reaction, heat exchange, and quenching processes. Therefore, it is required that the thermocouple used must be easy to install and remove, and easy to replace. Because of its complex structure and many control points, a multi-point thermocouple must be used.

③Shell gasifier temperature measurement solution

The design solution of the special Furnace thermocouple for the multi-point core-pulling and leak-proof Shell gasifier has solved the on-site requirements.

a. Multi-point thermocouples of different lengths (up to 6m) are used to measure the temperature of different control points in one fell swoop, using 3-point or 4-point thermocouples.

b. According to the characteristics of on-site installation, 4in (1in=25.4mm) No. 600 flange mounting parts are used. This part and the temperature measurement body are separable structures. The flange installation and fixing can be completed first. Then the temperature measurement body Installation with flange.

This solution allows the bulky flange to be installed at one time. In daily maintenance, only the main part needs to be replaced, which is convenient and quick. Closely combined with this structure is the independent replaceability of the core elements. Each measuring element is a detachable individual. If any one fails, it can be taken out and replaced separately. The maintenance cost and the quantity and expense of spare parts are reduced.

c. Due to the large amount of HCl in the medium in the furnace. Incoloy and Inconel alloys are often used in equipment manufacturing. In order to maintain a high resistance to high temperature and corrosion, the selection of Furnace thermocouple protection tube materials must all use Inconel600 alloy. Keep temperature measurement components , The material consistency of the mounting flange and the sealing sleeve.

d. The thermometer must have a multi-stage leak-proof sealing structure design. That is, each element must have a double-stage leak-proof device. When any temperature measuring element is damaged, due to the existence of leak-proof, the “annular space” The high temperature and high pressure airflow will not leak. It also guarantees the safety and environmental protection on-site requirements.

3.Furnace thermocouple installation instructions

①After the gasifier is shut down, consider the decompression effect of refractory materials and pressure vessels and the problems of thermal expansion and contraction. The pressure relief and replacement process of the gasifier is carried out slowly, and the furnace pressure should be basically reduced to atmospheric pressure and completely replaced.

After that, while the molten slag has not completely solidified, the gasifier thermocouple is drawn out of the furnace.

If the slag is solidified, the thermocouple ceramic sleeve cannot be pulled out, only the metal part at the back can be pulled out. The ceramic sleeve is usually driven into the furnace with a special tool.

②When installing a new gasifier thermocouple, put the assembled gasifier thermocouple on a special bracket. The bracket is placed on the wheeled trolley so that the gasifier thermocouple is exactly aligned with the gasifier thermocouple.

The equipment takes over in the middle. Slowly push the gasifier thermocouple into the furnace, about 10mm every 5 minutes. Protect the thermocouple from thermal shock.

Related Products:

Sino-Inst, Manufacuturer for Temperature Transmitters, like: Armoured thermocouple, assembly thermocouple, explosion-proof thermocouple, etc.

Sino-Inst’s Temperature Transmitters, made in China, Having good Quality, With better price. Our Temperature measurement instruments are widely used in China, India, Pakistan, US, and other countries.

Guidebook: Bimetallic Stemmed Thermometer

A bimetallic stemmed thermometer is a simple but effective tool used in a variety of industries, including food, HVAC, medical, and automotive. It’s easy to use, requires no external power source, and is highly durable. In this guidebook, we’ll explain how a bimetallic stemmed thermometer works, its advantages and disadvantages, how to use it, and its various applications. So, whether you’re a professional or just curious about thermometers, you’ll find everything you need to know right here. Let’s get started!

What is a bimetallic stemmed thermometer?

Bimetallic stemmed thermometer is an instrument that uses two different metals to measure temperature. Combine two metals with different coefficients of linear expansion and fix one end. When the temperature changes, the two metals thermally expand differently. Drive the pointer to deflect to indicate the temperature. This is the bimetallic thermometer. It can directly measure the temperature of liquid, steam, and gaseous media in the range of -80℃~+500℃ in various production processes.

Benefits of Bimetallic stemmed thermometer

(1) The thermoelectric potential is not disturbed. The thermoelectric potential of the bimetal thermometer is not disturbed by other factors. It has strong adaptability to different measurement environments. 

(2) The structure is diverse and can meet different measurement requirements. It can be used as electric contact bimetal thermometer, explosion-proof electric contact bimetal thermometer, bimetal thermometer with remote transmission, etc.

(3) The temperature response speed is fast, and there is strong sensitivity. At the same time, temperature changes are intuitive and can be displayed and recorded on site.

(4) Small size, convenient application, and strong temperature measurement reliability. Nominal diameter of dial: 60,100 (4 inch), 150 optional;

(5) It has a long service life, can be used in the temperature detection of chemical production for a long time, and has stable physical and chemical properties.

(6) Stable anti-corrosion performance. The application of bimetallic thermometers in chemical production often needs to be used in liquid and gas environments. It has a good anti-corrosion ability to protect pipes. It will not be affected by measurement conditions and cause corrosion problems that affect measurement quality.

(7) Strong pressure bearing. It has good pressure-bearing capacity, can be measured in different pressure levels, and has strong adaptability to measurement conditions.

(8) The conductivity is high. The temperature coefficient of resistance is small, and the thermoelectric potential has a linear relationship with the temperature, and the linearity is good.

A bimetallic stemmed thermometer works by using two different metals that are joined together. When the temperature changes, the two metals expand at different rates, causing them to bend or twist. This movement is then translated into a temperature reading on the dial. It’s like when you’re trying to open a jar that’s been in the fridge – you run it under hot water to expand the lid and make it easier to open. The bimetallic thermometer works in the same way, using the different expansion rates of the two metals to measure temperature accurately. It’s a simple but effective method that has been used for many years.

Here are some benefits of using a bimetallic stemmed thermometer that you might find helpful:

Highly Accurate: A bimetallic stemmed thermometer is one of the most accurate ways to measure temperature.
Durable: These thermometers are made to last.
No External Power Source Required: You don’t need to plug a bimetallic stemmed thermometer into an electrical outlet or replace batteries.
Versatile: You can use a bimetallic stemmed thermometer in many different situations.

In summary, a bimetallic stemmed thermometer is a simple, reliable, and accurate tool that is versatile and durable. It’s a great option for anyone who needs to measure temperature regularly.

How to Calibrate a Bimetallic Thermometer

Method 1: Ice water

1. Fill the container with ice cubes, and then top up with cold distilled water to form a watery slurry.

2. Insert the thermometer probe into the container, making sure not to touch the side.

3. The temperature should be 32°F (0°C) after 30 seconds. If not, the thermometer needs to be recalibrated. Record the difference and offset the thermometer as needed.

Method 2: boiling water

1. Boil a clean container of distilled water.

2. Once the water boils, insert the thermometer probe. Make sure again that the probe does not touch the side or bottom of the pot.

3. The temperature should be 212°F (100°C). Record the difference and offset the thermometer as needed. Note that the boiling point of water varies with altitude. Use this handy water boiling point calculator to find the temperature that suits your altitude.

The bimetal thermometer is an on-site detection instrument for measuring low and medium temperatures. It can directly measure the temperature of liquid, steam and gas medium in the range of -80℃~500℃ in various production processes.

The electric contact bimetal thermometer is used in the production site for temperature control and alarm.

Directly measure the temperature of liquid, steam and gaseous media in the range of -80℃~500℃ in various production processes.

The explosion-proof bimetal thermometer can directly measure the presence of hydrocarbons and other explosives at the scene. Directly measure the temperature of liquid, steam and gaseous media in the range of -80℃~500℃ in various production processes.

The remote bimetal thermometer can directly read the field temperature. And can transmit the temperature signal to the remote control system.

Extended reading:  Tri Clamp Sanitary Thermometers

Temperature range Accuracy class Graduation value ℃ Minimum insertion depth Lmin (mm)
Φ6 Φ8 Φ10
-40℃~80℃ 1.5 2 45 55 60
0℃~50℃ 1.5 1 110 130 140
0℃~100℃ 1.5 2 55 65 70
0℃~150℃ 1.5 2 40 45 50
0℃~200℃ 1.5 5 30 35 40
0℃~300℃ 1.5 5 50 60 60
0℃~400℃ 1.5 10 40 50 50
0℃~500℃ 1.5 10 35 40 40
0℃~600℃ 1.5 10 30 35 35
customizable 1 * * * *

Related Products:

Sino-Inst, Manufacturer for Bimetallic stemmed thermometers, like Digital Thermometer/Transmitter, Digital Thermometer/Transmitter, explosion-proof thermocouple, etc.

Sino-Inst’s Bimetallic stemmed thermometers, made in China, Having good Quality, With better price. Our Temperature measurement instruments are widely used in China, India, Pakistan, the US, and other countries.

Temperature Sensor Transmitter—-Do You Know?

Temperature sensor transmitter is a combination of temperature sensor and temperature transmitter. It can be used in chemistry and medicine.

Thermocouple, thermal resistance and temperature transmitter of SBW series are the temperature transmitter units of on-site installation type in DDZ series instruments and they are used by matching with industrial thermocouple, thermal resistance. It uses dual-wire transmission mode(two conducting wires are used as the common transmission lines for power input and signal output).

It transforms the industrial thermocouple, thermal resistance signal into 4-20mA and 0-10 mA output signals which are linear with input signal and temperature signal. The transmitter can be directly installed in the junction box of the thermocouple and thermal resistance so as to form an integrated structure. As the temperature measuring instruments of new generation, it is widely used in metallurgy, petroleum, chemical industry, electric power, light industry, textile, food, national defense, scientific research and other industrial sectors.

Sino-Inst offers a variety of Temperature sensor transmitter. If you have any questions, please contact our sales engineers.

The Difference Between Temperature Sensor Transmitter

A temperature sensor refers to a sensor that can sense temperature and convert it into a usable output signal. Temperature sensor is the core part of temperature measuring instrument, and there are many types. According to the measurement method, it can be divided into two categories: contact type and non-contact type.

Temperature transmitter uses thermocouple and thermal resistance as temperature measuring elementAfter measurement, the output signal is sent to the transmitter after voltage stability filtering, operational amplification, nonlinear correction, V/I conversion, constant current and reverse

Temperature sensor transmitter is a combination of temperature sensor and temperature transmitter.

read more about Temperature sensor transmitter

The Function Of The Temperature Transmitter

A temperature transmitter is an instrument that converts a temperature variable into a standard output signal that can be transmitted.Mainly used for the measurement and control of temperature parameters in industrial processes.
The temperature current transmitter converts the signal of the temperature sensor into a current signal, and connects it to an auxiliary instrument to display the corresponding temperature.

Advantage Analysis

  • High precision
  • The range and zero point can be continuously adjusted from the outside
  • Good stability
  • Positive mobility can reach 500%, negative mobility can reach 600%
  • Two-wire system, three-wire system, four-wire system
  • Adjustable damping, overvoltage resistance
  • Solid state sensor design
  • No mechanical moving parts, less maintenance
  • Light weight (2.4kg)
  • Full series of unified structure, strong interchangeability
  • Miniaturization (total height 166mm)
  • The diaphragm material contact medium is optional
  • Unilateral overpressure
  • Low-pressure casting aluminum alloy shell
  • Superior measurement performance, used for pressure, differential pressure, liquid level, flow measurement

Technical Parameter

1. input
Thermocouple: (two wire system), voltage: connect cable:sensor lead, maximum impedance 1.5k
Thermal resistance: (three wire system, four wire system), resistance measurement: connect cable: resistance compensation can reach 50.
2.output Isolated voltage 0.5kV instead of 2.5KV
3.Transmitter input options, accuracy and environmental temperature impact.

How Does A Thermocouple Transmitter Work?

Thermocouple or thermal resistance sensor will be converted into electrical signal by the temperature and then, the signal is sent to the input network of the transmitter which is consisted of zero adjustment circuit, a thermocouple compensation circuit and other related circuits. The signal after zero adjustment will be input to the operational amplifier for signal amplification. The signal after amplification will be output as 4 ~ 20mA DC after being processed by the V/I converter in one way; in another way, it will be displayed in gauge outfit after being processed by A/D converter.

There are two kinds of linear circuit in the transmitter, both of which adopt the feedback mode. The thermal resistance sensor is corrected by the positive feedback mode while the thermocouple sensor is corrected by approximation method of multiple-segment line. There are two kinds of display modes for the temperature transmitter of integrated digital display. The temperature transmitter displayed by LCD is output by the two-wire system while the temperature transmitter displayed by LED is output by the three-wire system.

  1. Bimetal sensor:The bimetal consists of two pieces of metal with different expansion coefficients glued together. As temperature changes, material A will expand more than other metals, causing the metal plate to bend. The curvature of the bend can be converted into an output signal.
  2. Bimetal rod and metal tube sensor:As the temperature rises, the length of the metal pipe (material A) increases,but the length of the unexpanded steel pipe (metal B) does not increase, so due to the change in position, the linear expansion of the metal pipe can be transmitted. Furthermore, this linear expansion can be converted into an output signal.
  3. Sensor designed for liquid and gas deformation curve:When the temperature changes, the volume of liquid and gas will change accordingly.

Various types of structures can convert this expansion change into a position change, thereby generating a position change.

Bimetallic Thermometer
SIRD-903 26 GHz Radar level Sensor

Request a Quote

Please enable JavaScript in your browser to submit the form