Sludge Flow Meter for Return Activated Sludge

A sludge flow meter refers to a flow meter that can be used to measure the flow of sludge.

What kind of flowmeter can be used for sludge flow measurement?

According to the characteristics of the sludge medium, the flow rate of the sludge can be measured by using an electromagnetic flowmeter. The electrode material uses a tantalum electrode. The lining material uses a ceramic material or tetrafluoroethylene. This can solve the flow measurement condition of the sludge.

Sludge flow meter for sludge treatment

Sludge treatment (sludge treatment) refers to the reduction, stabilization, and harmless processing of sludge such as thickening, tempering, dewatering, stabilization, drying, or incineration. The higher the degree of sewage treatment, the more sludge residues that need to be treated.

Why use an electromagnetic flowmeter to measure the sludge flow rate?

The main reason for using an electromagnetic flowmeter to solve the flow of sludge is its low cost, high measurement accuracy, and good stability. Many flows measuring instruments can meet this requirement.

Featured Sludge Flow Meters

Read more about: Different Types of Flowmeters – Technical and Application Analysis

Return Activated Sludge

The wastewater treatment plant uses a secondary treatment process called activated sludge. This process converts non-sedimentable substances into biological flocs. This substance is produced in the aeration tank and settled in the final sedimentation tank.

Activated sludge is an aerobic process. It can promote the health of microorganisms and ensure effective treatment. The balance between food and oxygen and microorganisms must be maintained for optimal treatment. An element of maintaining biomass is to return a part of the sedimentation sludge from the final sedimentation tank to the aeration tank to maintain the balance of the biological system. This part of activated sludge is called RAS (Returned Activated Sludge).

The RAS is returned to the aeration tank via a variable-speed centrifugal pump. Accurate flow rate measurement is essential to ensure that the proper ratio of “food to microorganisms” is maintained. The RAS flow rate is determined by a microbiological health laboratory analysis, and the flow rate is adjusted accordingly.

Extended reading: Insertion Ultrasonic Water Flow Meter – Designed for Agricultural Irrigation, Garden Management

Sludge Flow Measurement of Return Activated Sludge Pipe

1 Project background

  • DN 400mm stainless steel pipe;
  • Full tube
  • High pollution load, suspended solids content as high as 1%.

2 Measurement requirements

  • Trouble-free and stable measurement of the horizontal conveying pipe of the return sludge conveyed by the screw pump lifting equipment;
  • Due to high pollution load and gas load. The two existing measurements. Electromagnetic flowmeter + external clamp ultrasonic time difference method. Neither can work reliably or at all;
  • The installation cost is low.

3 Solution

  • Use NFP type cross-correlation flow measurement system;
  • A hole was drilled upstream of the existing electromagnetic flowmeter. The NFP mounting piece was welded to the existing pipeline;
  • Install a ball valve that can remove the sensor during operation, adjust and fix the cross-correlation sensor.

4 Advantages

  • Simple and fast upgrade and transformation of existing facilities;
  • The old flow measurement equipment does not necessarily need to be dismantled;
  • Although the concentration of suspended solids in the water is high, the flow measurement is still reliable.

Read more about: Shop 101: Key Factors In Selecting A Pipe Flow Meter

Extended reading: Micro flow meters for low flow liquids

Advantages of electromagnetic flowmeter in sludge measurement

  1. The electromagnetic flowmeter has no mechanical inertia. Responsive. Can measure instantaneous pulsating flow. It can also measure the flow in both directions.
  2. The output of the electromagnetic flowmeter is only proportional to the average flow rate of the measured medium. It has nothing to do with the flow state (laminar or turbulent) under symmetrical distribution. Therefore, the electromagnetic flowmeter has a very wide range. The measurement range can reach 100:1, and some even reach the operable flow range of 1000:1.
  3. The sensor structure of the electromagnetic flowmeter is simple. There are no moving parts in the measuring tube, nor any throttling parts that hinder fluid flow. So when the fluid passes through the flow meter, it will not cause any additional pressure loss. It is one of the flow meters with low energy consumption in the flowmeter.
  4. The industrial electromagnetic flowmeter has a very wide caliber range. From a few millimeters to a few meters. Moreover, there are real-flow calibration equipment with a diameter of 3m in China. Laid a foundation for the application and development of electromagnetic flowmeters.
  5. The electromagnetic flowmeter is a volume flow measuring instrument. During the measurement process, it is not affected by the temperature, viscosity, density and conductivity (in a certain range) of the measured medium. Therefore, the electromagnetic flowmeter only needs to be calibrated by water. It can be used to measure the flow of other conductive liquids.
  6. It can measure the flow of dirty medium, corrosive medium and suspended liquid-solid two-phase flow. This is because there are no obstructing flow parts inside the meter measuring tube. The fluid to be measured is only in contact with the inner lining of the measuring tube and the electrode, and the material can be selected according to the nature of the fluid to be measured.

For example, use polytrifluoroethylene or polytetrafluoroethylene as the lining. It can measure various corrosive media such as acid, alkali and salt. The use of wear-resistant rubber as the inner lining is particularly suitable for measuring liquid-solid two-phase flows such as mineral slurry and cement slurry with solid particles and greater wear, as well as various suspended liquids such as fiber-containing liquids and pulps.

Extended reading: Orifice Plate Flow Meter

Can electromagnetic flowmeter measure sludge fluid with 85% moisture content?

Yes, there is no problem at all. I am the technology of the electromagnetic flowmeter manufacturer, and the measurement is no problem. It is only when the density of the sediment particles reaches a certain level. There will be peak fluctuations. However, the measurement is no problem.

Extended reading: ultrasonic sludge level meter

Which lining material electromagnetic flowmeter is used for sludge flow meter?

What kind of flowmeter can be used for sludge flow measurement. According to the characteristics of the sludge medium, the flow rate of the sludge can be measured by using an electromagnetic flowmeter. The electrode material uses tantalum electrode, and the lining material uses ceramic material or tetrafluoroethylene. In this way, the sludge flow measurement conditions can be solved.

More about:

Learn More about Sludge Treatment

Before sludge treatment, we must first understand the classification of sludge:

  1. Treatment of physicochemical sludge discharged from sedimentation tank or thickening tank of waterworks. It is a medium and fine-grained organic and inorganic mixed sludge. The compressibility and dehydration performance are average.
  2. The remaining activated sludge discharged from the secondary settling tank of the domestic sewage plant is hydrophilic, fine-grained organic sludge, with poor compressibility and poor dehydration performance.
  3. Treatment of physicochemical and biochemical mixed sludge discharged from the thickening tank produced by industrial wastewater treatment. It is a medium-fine-grained mixed sludge. The dewatering performance of the fiber-containing body is better. The other compressibility and dewatering performance are average.
  4. The physical and chemical fine-grained sludge produced by the physical method and chemical method discharged from the thickening tank from the industrial wastewater treatment. It belongs to the fine-grained inorganic sludge. The compressibility and dewatering performance are general.
  5. Physical and chemical precipitation of coarse-grained sludge produced by industrial wastewater treatment. It belongs to coarse-grained hydrophobic inorganic sludge. It has good compressibility and dewatering performance.

Extended reading: Stainless steel flow meters|304-316 optional

You may like:

Extended Reading: Special Magnetic Flowmeter Installation situation

Sino-Inst offers Sludge flow meter products. About 85% of these are Magnetic flow meters, 3% are Ultrasonic water meters. A wide variety of Sludge flow meter options are available to you, such as free samples, paid samples.

The top-selling countries or regions are China, India, and Israel, which supply 99%, 1%, and 1% of sewage flow meter respectively. Sludge flow meter products are most popular in Domestic Market, Mid East, and North America. You can ensure product safety by selecting from certified suppliers, with ISO9001, and Other certifications.

Request a Quote

Please enable JavaScript in your browser to submit the form

Paddle wheel flow meter technology

What is a Paddle wheel flow meter?

Paddle wheel flow meter is a mechanical flow meter that uses an impeller as a flow sensor component. The impeller-type flow meter is a meter that measures flow according to the principle of fluid momentum moment. Paddle wheel flow meter is also called an impeller flow meter, rotary wheel flow meter, etc. Typical Paddle wheel flow meters are water meters and turbine flow meters. It can be a mechanical transmission output type or an electric pulse output type. It is suitable for the measurement and control of industrial process clean water pipelines or low-concentration acid-base, low-viscosity single-phase fluid non-trade settlement process.

Paddle wheel flow meter Features

  1. Has good anti-interference
  2. Strong signal transmission capability (the farthest transmission is 300 meters)
  3. Stable quality and low failure rate
  4. Superior performance-price ratio
  5. Wide range measurement.
  6. All measurement parameters can be adjusted independently.
  7. Output 4-20mA or RS485 communication output, two pairs of alarm output contacts.
  8. Display real-time flow and cumulative flow.
  9. Insertion installation.

Application range of impeller flowmeter

  • Flow monitoring of industrial water treatment process
  • Industrial circulating cooling water and make-up water flow monitoring
  • Reclaimed water flow monitoring
  • Process flow monitoring after wastewater treatment
  • Agricultural irrigation water flow measurement
  • Multi-way valve and multi-valve system flow monitoring for softening, filtering, etc.
  • Other water flow detection and control

Extended reading: Insertion Ultrasonic Water Flow Meter – Designed for Agricultural Irrigation, Garden Management

Paddle wheel flow meters parameters

Picture
ModelKF11 Corrosion-resistant flow sensorKF11 series impeller flow meter
DescriptionSuitable for highly corrosive fluids, sulfuric acid, nitric acid, hydrofluoric acid, hydrochloric acid, mixed acid, strong alkali and other places;
The flow parts are made of corrosion-resistant materials such as PVDF·PTFE·Hastelloy·Titanium alloy; there is almost no pressure loss and maintenance-free;
Flow velocity range 0.3-6m/s, can measure fluid with flow velocity greater than 0.3m/s;
Not applicable to media containing particles and fibrous impurities;
The impeller adopts a five-piece runner design
PP/PVDF/PTFE material
Better guarantee the dynamic balance characteristics, greatly improving the linear accuracy and repeatability accuracy of the sensor;
The minimum flow rate is 0.1m/s; NPN open collector output, which can be directly transmitted to a flow transmitter or PLC, a standard square wave signal and a maximum distance of 300m;
Applicable caliber: DN25-DN600 (1″-24″);
Not suitable for particles and fibrous impurities
The medium;
Caliber rangeDN25-DN600(1″-24″)DN25-DN600(1″-24″)
Flow rate range0.3-5m/s0.1-8m/s
Output signalSquare wave pulse signal: (40-45Hz) nominal flow rate per m/sSquare wave pulse signal: (40-45Hz) nominal flow rate per m/s
Equipped with pulse conversion components can output 4-20mA
CharacteristicHall pulse output, open collector NPN, strong driving ability
Has high chemical resistance
Minimum flow rate 0.3m/s
IP68 protection grade suitable for harsh on-site environment
Hall pulse output, open collector NPN, strong driving ability
Has high chemical resistance
IP68 protection grade suitable for harsh on-site environment
Plug-in type, easy installation, good reliability, almost maintenance-free
Linear accuracy L
Repeatability accuracy R
L=±1%
R=±0.5%
L=±1%
R=±0.5%
OntologyPVDF/PTFEPP plus glass fiber/CPVC
ImpellerPVDF/PTFEPP/PVC/PVDF/PTFE
Shaft and bearingHastelloy C/Titanium Alloy/ZrO2Al2O3/ZrO2/SS316L/Hastelloy C/Titanium Alloy
O-ringfluororubberFPM/EPDM/Fluorine rubber
Temperature and pressurePVDF body: 12.5bar@25℃-2.5bar@100℃
PTFE body: 12.5bar@25℃-2.5bar@100°
PP body: 12.5bar@25℃-1.7bar@80℃
CPVC body: 12.5bar@25℃-1.7bar@80℃
Power supply systemDC 5-24VDC5-24V
Protection levelIP68IP68
Application fieldSulfuric acid ratio and delivery flow monitoring
Copper sulfate monitoring in electroplating bath
Nitric acid mixture
Intermediate
Chemical waste
Pure Water Process/Reverse Osmosis/Ultrafiltration/EDI
Water purification and filtration system
Cooling water and boiler water monitoring
Chemical industry
Agricultural irrigation
Cleaning system and single crystal silicon cleaning
Pump protection

Check more Choosing The Right 1 Inch Flow Meter.

Paddle wheel flow meter working principle

The sensor is divided into two parts: the transmitter and the impeller. The impeller is in direct contact with the fluid, and the transmitter is isolated from the fluid. The liquid flow drives the impeller to rotate, and there are four evenly distributed magnetic blades on the impeller. The rotating magnetic blade induction Hall switch generates a frequency signal proportional to the flow rate, and the transmitter converts the frequency signal into a 4-20mA current signal.

Typical Paddle wheel flow meters are water meters and turbine flow meters. The structure can be a mechanical transmission output type or an electric pulse output type.

The accuracy of water meters with general mechanical transmission output is low, with an error of about ±2%. However, the structure is simple and the cost is low. It has been mass-produced in China, and is standardized, generalized and serialized. The accuracy of the turbine flowmeter output by the electric pulse signal is relatively high, and the general error is ±0.2%-0.5%

The five-piece impeller design is in line with the principle of fluid mechanics, and the uniform force angle produces a better dynamic balance, ensuring better linear accuracy and repeatability accuracy

Various shafts and bearings:
Shaft and bearing: ZrO2, SS316L, Hastelloy C
Impeller material: PTFE, PP, PVDF, ABS
Body material: PP plus glass fiber, ABS, CPVC, PTFE, SS316L, brass

Real flow calibration
Calibration range: DN10-DN1000
Each sensor has undergone strict calibration and quality inspection. When leaving the factory, each sensor guarantees that the K factor is 2% of the standard value, and the repeatability accuracy is 0.5%;

Read more about: What is an inline flow meter?

Paddle wheel flow meter advantages and disadvantages

Advantage

  • Excellent reproducibility and responsiveness.
  • Simple structure and low price.
  • Small size, large-capacity measurement is possible.

Disadvantage

  • Extremely sensitive to foreign objects. (Causing blockage)
  • Due to the high-speed rotation of the impeller, regular maintenance is required to cope with axial wear or to replace the impeller.

Extended reading: How to Select the Right Agriculture Flow Meter

Paddle wheel flow meter installation

  • The straight section behind the flange must meet the measuring distance of the first 10 and the rear 5 times the pipe diameter;
  • After reducing the diameter (only allowed to change from large to small, but not allowed to change from small to large), the straight line segment needs to meet the measurement distance of the first 15 and the back 5 times the pipe diameter;
  • The straight section behind the first-level equal-diameter elbow needs to meet the measuring distance of the first 20 and 5 times the pipe diameter;
  • The straight section behind the two-stage continuous equal-diameter elbow on the same plane must meet the measurement distance of the first 25 and the rear 5 times the pipe diameter;
  • The straight section behind the non-coplanar two-stage continuous equal-diameter elbow needs to meet the measuring distance of the first 40 and the back 5 times the pipe diameter;
  • The straight section behind the valve must meet the measurement distance of the first 50 and the last 5 times the pipe diameter;
  • The probe is recommended to be installed perpendicular to the pipe, and not at the bottom of the pipe;
  • The probe can be installed on a vertical pipe where the liquid flows upward, but it must also meet the requirements of the above-mentioned straight section;
  • The probe is not allowed to be installed on a vertical pipe where the liquid flows downward;
  • The liquid in the tested pipeline must be full of flow, and no gas and liquid can flow at the same time;
  • The cost of the body must be consistent with the bayonet (open slot) to ensure the correct installation position;
  • The O-ring has a good sealing effect. When the installation is tight, it needs to be wetted with silicone oil or water for installation;
  • The sensor locking cap must be tightened to prevent excessive pressure in the pipeline from leaking or ejecting;
  • When installing outdoors, pay attention to waterproof treatment; keep the cables dry to avoid moisture damage;
  • Do not lay the sensor cable and AC power cable in the same protective tube to avoid electrical interference

Extended reading: Industrial VS Residential inline water flow meters

More Featured Paddlewheel flowmeters

You may like:

Sino-Inst, paddle wheel flow meter manufacturer. It can measure a single sound-conducting liquid medium of Velocity range: 0.1~6m/s; Pipe diameter: DN15 to DN600.

Sino-Inst’s paddle wheel flow meter, made in China, Having good Quality, With a better price. Our flow measurement instruments are widely used in China, India, Pakistan, the US, and other countries.

How Does a Piston Flow Meter Work?

What is a piston flow meter?

A piston flow meter is a positive displacement flowmeter, which is mainly used to measure liquid flow. The piston flow meter is composed of a shell, piston mechanism, and other parts. The measured fluid fills a space with a certain volume, and these volume increments are counted and accumulated. It has the advantages of simple structure, reliable work, high accuracy, large range ratio, and little influence on viscosity. It is mostly used for measuring non-corrosive liquids, such as heavy oil or other oils, on small-diameter pipelines.

Piston flow meter technology

Piston-type flowmeters are commonly used for flow measurement of fuel dispensers. Its structure includes a housing, an upper cover, a lower cover, a piston, a crankshaft, and a distribution valve. The inner cavity of the housing is equipped with four-piston cylinders that cooperate with the piston dynamic seal. The four-piston cylinders are evenly distributed in the circumferential direction on the vertical plane of the crankshaft rotation centerline.

The piston is connected to the crankshaft by a connecting rod. The piston rodless cavity is connected to the inlet and outlet on the upper cover through the distribution valve. A side cover is installed on the casing outside the piston cylinder. The upper cover is equipped with an output shaft that rotates synchronously with the crankshaft. By right Count the number of revolutions of the output shaft to achieve flow measurement.

  • The main disadvantages are:
  • The outer circular surface of the output shaft of the existing piston flowmeter and the upper cover adopts O-ring dynamic sealing cooperation.
  • The high-speed rotation of the output shaft is likely to cause wear to the sealing ring, resulting in a decrease in sealing performance and even leakage.
  • In addition, there are errors in the machining dimensions of the inner cavity of the piston-cylinder of each product. Lead to the measurement error of the piston flowmeter.

Read more General-purpose Flow Totalizer for Data collection and calculation

Features and applications of Piston flow meter

The piston flow meter has a simple structure, reliable work, and a large measuring range.
The measurement accuracy is high and is not affected by viscosity. It can be changed remotely and other advantages.

However, the main components of the measurement part are not corrosion-resistant. Therefore, it can only measure non-corrosive media, such as heavy oil and other petroleum products.

Extended reading: Cylinder Gear flow meter for micro flow measurement.

Piston flow meter working principle

A piston flow meter is a positive displacement flow meter, which is based on the fact that the piston and the metering chamber have been kept in a tangential sealed state. And there is a fixed eccentric distance metering element piston.

Under the action of the pressure difference, a rotational torque is generated on the piston, which makes the piston perform an eccentric rotation movement.

The number of revolutions of the piston is proportional to the flow rate of the fluid. The piston revolution ratio is recorded by the counting mechanism. Then the total flow of fluid can be measured.

The inlet and outlet of the Piston flow meter are separated by a partition. When the measured fluid enters the metering chamber from the inlet, a pressure difference is formed at the inlet and outlet, forcing the piston to rotate counterclockwise as shown in the figure.

The continuous flow of fluid forces the piston to rotate as shown in the figure, forming two and a half-crescent cavities. The piston is forced to rotate under the action of the pressure difference as shown in the figure. V2 fluid is discharged from the outlet. Rotate under the action of pressure difference. V1 fluid is discharged from the outlet, and the fluid bursting out every revolution of the piston is equal to the sum of V1+V2.

Tool: Volumetric Flow Rate & Pipe Diameter to Flow Speed Calculator

Piston flowmeter output signal, such as 4-20mA. The flow signal can be connected to a paperless recorder. Carry out multi-channel flow signal monitoring. What Is A Paperless Recorder?

Piston flowmeter VS gear type flowmeter

Gear flow meters are a type of positive displacement flow meters, used for precise continuous or intermittent measurement of the flow or instantaneous flow of liquid in the pipeline. It is especially suitable for the flow measurement of heavy oil, polyvinyl alcohol, resin, and other high viscosity media.

Piston type flowmeter is an online installation, mechanical flow switch, used for liquid or gas medium. Very small pressure loss, good repeatability, anti-fouling ability, mechanical part, and electronic part are completely isolated, suitable for small flow economy type.

If the flow rate you want to measure is not large, the piston type is better.
If you want to measure a large flow rate, just use a gear type.
If the gas flow is measured, only the piston type can be used

Extended reading: Positive displacement flow meter working principle.

Guess you like: What is Reynolds number?

A Piston Flow Meter is an innovative device that accurately measures fluid flow in pipelines. Sino-Inst, a well-established manufacturer and supplier of Piston Flow Meters, boasts a wealth of experience in the field.

With our top-notch product line, Sino-Inst is the perfect partner for all your flow measurement needs. If you’re in the market for a reliable and efficient Piston Flow Meter, look no further! Contact Sino-Inst today and let them show you what they can do.

And that’s not all, Sino-Inst also offers a range of other flow meters, including turbine flow meters, magnetic flow meters, and more. Let Sino-Inst help you find the perfect flow meter solution for your specific application!

Bidirectional Flow Measurement

What is bidirectional flow?

Bidirectional flow refers to forward and directional flow. Bi-directional flow lines are not common in most process plants. The measurement of unidirectional flow is easy to understand and is applicable to all types of flow technologies. However, most flow technologies cannot accurately measure two-way flow.
They always cause difficulties for process and instrument designers. For two-way flow, the pipeline scheme uses the same pipeline to achieve the transport and/or control function of the opposite flow (forward or reverse flow) according to the process conditions and goals.

Can the flow meter perform bidirectional measurement?

If the flow direction of the medium in the pipeline is reversed. Does the flow meter need to be installed with a flow meter for forwarding use and a flow meter for reverse use accordingly? Is there a flow meter for normal measurement that does not consider the flow direction?

  1. If you just look at the flow rate, you can. For example, an electromagnetic flowmeter. It doesn’t matter if you measure in the whole direction or in the reverse direction. Change the reverse measurement to allow in the prerequisite electromagnetic flowmeter settings.
  2. It’s hard to say if you still need a cumulative amount. How do you convert the cumulative amount you measured forward and the cumulative amount you measured backward? Whether to subtract or add depends on your actual situation.

Extended reading: Insertion Ultrasonic Water Flow Meter – Designed for Agricultural Irrigation, Garden Management

How does the ultrasonic flowmeter realize bidirectional flow measurement?

The principle of the ultrasonic flowmeter is to calculate the fluid flow rate using the difference in sound velocity. And multiply the fluid velocity by the area to calculate the volume flow.

Usually, there is an incident angle between the probe of the ultrasonic flowmeter, that is, the transducer and the meter body. From 60 degrees to 45 degrees. Ultrasonic waves propagate between a pair of probes if there is no fluid, that is, at zero flow. The travel time back and forth is the same. It is equivalent to a zero flow rate.

Extended reading: Ultrasonic Flow Meters Types & Technical Guide

Once there is fluid, the speed of the ultrasonic flowmeter back and forth between a pair of probes is different. Regardless of the direction of fluid flow, there will be a difference in sound velocity. If one direction is set as the normal flow direction, then the normal sound velocity should be a positive number. If the sound velocity difference is negative, the flow is in the opposite direction. That is reverse measurement. The measurement accuracy of the two directions is the same.

Extended Reading: Inline Ultrasonic Flow Meter

Can a vortex flowmeter measure bidirectional flow?

You cannot measure bidirectional flow with just one vortex flowmeter. But in some applications, you can use two for this.

The vortex flowmeter has a bluff body in front of the sensor, which is used to generate the vortex in the flow. As far as I know, no flowmeter has two bluff bodies to measure bidirectional flow.

If you have a two-way steam application. Then you can install two vortex flowmeters in the same line, as long as you respect the inlet and outlet operation of both. However, depending on the size of the line, this setting may become expensive.

Read more General-purpose Flow Totalizer for Data collection and calculation

Bidirectional orifice flowmeter

The bidirectional orifice flowmeter is a differential pressure flowmeter. Mainly used for flow measurement of liquid and gas. According to the characteristics of the orifice flowmeter, it has the advantage of high temperature and high pressure. Therefore, the orifice flowmeter is widely used in the field of high temperature and high-pressure measurement. The orifice flowmeter has high accuracy and good stability and is unanimously recognized by users.

What kind of measurement conditions will use an orifice flowmeter to measure? It can be used according to the requirements of the site, such as typical boiler steam, the general temperature can be close to about 500 degrees, and general flow meters cannot be used. However, the orifice flowmeter can effectively solve this high-temperature working condition, and the only disadvantage is its high cost of use.

Extended reading: 2 inch Water Flow Meter

You may like:

Extended reading: Integral DP Flow Meter|Gas, liquid, steam|Compact structure

Sino-Inst offers over 50 flow meters for flow measurement. About 50% of these are differential pressure flow meters, 40% are the liquid flow sensor, and 20% are Ultrasonic Level Transmitter and mass flow meters.

A wide variety of flow meters options are available to you, such as free samples, paid samples.

Sino-Instrument is a globally recognized supplier and manufacturer of flow measurement instrumentation, located in China.

What is Modbus Protocol?

What is meant by Modbus protocol?

Modbus Protocol is a serial communication protocol, which was published by Modicon company (now Schneider Electric) in 1979 for the use of programmable logic controller (PLC) communication. Modbus has become the industry standard (De facto) of communication protocols in the industrial field and is now a common connection method between industrial electronic devices.

Modbus Protocol Features

The main reasons why Modbus is more widely used than other communication protocols are:

  • Published publicly and without copyright requirements
  • Easy to deploy and maintain
  • For suppliers, there are not many restrictions on modifying mobile local bits or bytes

Modbus allows multiple (approximately 240) devices to be connected on the same network to communicate. For example, a device that measures temperature and humidity and sends the results to a computer. In the data acquisition and monitoring control system (SCADA), Modbus is usually used to connect the monitoring computer and the remote terminal control system (RTU).

How does a Modbus work?

Modbus is a master/slave communication mode with a single master station. There can only be one master station on the Modbus network, and the master station has no address on the Modbus network. The address range of the slave station is 0-247, where 0 is the broadcast address. The actual address range of the slave station is 1-247. Modbus communication standard protocol can be transmitted through various transmission methods, such as RS232C, RS485, optical fiber, radio, etc.

Modbus has two serial transmission modes, ASCII and RTU. They define different ways of how data is packaged and decoded. Devices that support Modbus protocol generally support the RTU format. Both communication parties must support one of the above modes at the same time.

The above is the official definition, let’s use ordinary words to explain:

This is actually the communication protocol, and any protocol is similar. There are only two communication formats and communication specifications.

If you want, you can also define a communication specification yourself. Use PLC or VB language to process according to this specification defined by yourself. If the reliability exceeds Modbus, then your communication specification is the most popular!

The difference and connection between RS 485 and MODBUS

I often see RS485 and MODBUS written together, and Sino-Inst will talk to you about the difference and connection between RS485 and MODBUS.

RS485 is a physical interface, which is simply hardware.

MODBUS is an international standard communication protocol used to exchange data between devices of different manufacturers (usually for industrial purposes); the so-called protocol can also be understood as the “language” someone said above, or simply software.

Under normal circumstances, two devices transmit data through the MODBUS protocol: RS232C was first used as the hardware interface, (that is, the serial communication port (serial port) on an ordinary computer). There is also RS422, and there is also commonly used RS485. This interface The transmission distance is long, and it is often used in general industrial scenes.

The MODBUS protocol is divided into three modes: MODBUS RTU, MODBUS ASCII and the later developed MODBUS TCP.

The physical hardware interfaces used by the first two (MODBUS RTU, MODBUS ASCII) are serial (Serial) communication ports (RS232, RS422, RS485).

And MODBUS TCP is to conform to the development trend of the world today. Anything can be connected by Ethernet or Internet to transmit data.

The hardware interface of MODBUS TCP mode is the Ethernet (Ethernet) port, which is the network port generally used on our computer.

We categorize industrial networks into three categories: RS485 network, HART network and fieldbus network.

HART network

HART is a transitional bus standard proposed by Emerson. It mainly superimposes a digital signal on top of a 4-20 mA current signal.

The physical layer uses BELL202 frequency shift keying technology. In order to realize the functions of some smart meters. But this agreement is not a truly open standard, and you have to join his foundation to get the agreement. Part of the cost of joining the foundation.

The technology is mainly monopolized by several large foreign companies, and in the past two years, some domestic companies have started to do it again. But it has not yet reached the level of foreign companies.

Nowadays, a large part of smart meters are equipped with HART round cards and all have HART communication function.

But from the domestic point of view, this part of the function has not been really used, at most it is only used to set the parameters of the handheld communicator. The HART intelligent instrument has not played its due function, and it has not been connected to the Internet for equipment monitoring.

In the long run, due to the low communication rate of HART, the networking is difficult and other reasons. The procurement volume of HART instruments will experience a downward trend.

However, because HART instruments have a history of more than ten years, the number of instruments installed is very large. For some system integrators, there is still a lot of room for use.

Fieldbus network

Fieldbus technology is one of the hotspots of technology development in the field of automation today. Known as the computer local area network in the field of automation. Its appearance marks the beginning of a new era of automation control technology.

Fieldbus is a digital, serial, multi-station communication network that connects the instruments installed in the control site and the control equipment installed in the control room. The key symbol is the ability to support bidirectional, multi-node, bus-style all-digital communication.

In recent years, fieldbus technology has become a hot spot in the development of automation and instrumentation in the world. The appearance of the fieldbus network is a revolutionary change in the traditional control system structure. It is the automatic control system that is moving in the direction of intelligence, digitization, informationization, networking, and decentralization. Form a new type of network integrated fully distributed control system-Fieldbus Control System FCS (Fieldbus Control System).

However, various standards of current fieldbus exist in parallel and have their own areas of survival. There has not yet been a truly unified standard. The key is that we cannot see when a unified standard will be formed, and the technology is not mature enough.

In addition, the types of fieldbus instruments are still relatively small, and the room for selection is small, and the price is relatively high. From the perspective of end users, most of them are still on the sidelines. I want to wait until the technology is mature and consider it, but now there are few implementations.

RS485 network

RS485/MODBUS is a popular way of network layout. Its characteristic is simple and convenient to implement. And now there are many instruments that support RS485, especially in the oil industry.

RS485/MODBUS is simply dominating the world. Current instrument vendors have also switched to support RS485/MODBUS. The reason is simple, like the original HART instrument, it is very difficult and expensive to buy a conversion port. The RS485 conversion interface is much cheaper and has a wide variety.

At least in the low-end market, RS485/MODBUS will still be the most important networking method, and it will not change in the past two to three years.

Features of 4-20mA current loop and RS485 communication (Modbus RTU protocol) data acquisition

4-20mA current loop data acquisition characteristics

Use pressure, temperature transmitter and current acquisition module (RTU) or acquisition card on site for data acquisition and then communicate and transmit with the industrial computer. The data acquisition system using 4-20mA current loop instrument has the following characteristics:

  1. The construction is complicated, data cables need to be buried in advance, the number of cables is large, and the construction period is long
  2. The computer terminal needs a current acquisition card or a data acquisition module
  3. Complicated replacement and maintenance operations, troublesome expansion
  4. 4-20mA current loop data acquisition accuracy is low, and the error comes from 4-20mA output instrument and acquisition card (or data acquisition module)

RS485 communication (Modbus protocol) data acquisition characteristics

Use smart meters, transmitters, actuators, etc. with RS485 communication to directly communicate with the serial port of the industrial computer. The use of RS485 communication digital sensor meter network system has the following characteristics:

  1. The construction complexity is reduced, data cables need to be buried in advance, the number of cables is small, and the construction period is reduced
  2. The computer terminal only needs an isolated RS485/RS232 converter
  3. Easy to replace and maintain, and easy to expand
  4. High acquisition accuracy, eliminating the error of RTU, the system error only comes from the transmitter itself
  5. RS485 communication has good transmission stability and less network maintenance
  6. The cost of use is greatly reduced|
  7. The maximum communication distance of RS485 is 1200 meters

RS485 communication transmission of electromagnetic flowmeter Modbus protocol

The RS485 communication data transmission interface of the electromagnetic flowmeter is half-duplex. The standard rate is greater than 250kHz. The communication direction conversion time is 3.5us. Usually 16-way load can be connected. It can also be expanded to 32 channels. Standard shielded twisted pair cable is 1000m. Use master-slave multi-machine communication. When multiple electromagnetic flowmeters are interconnected. It can save signal lines and facilitate high-speed transmission.

RS-485 communication has good anti-noise interference. Long transmission distance and multi-station capability. Will not affect the synchronization of on-site and remote data due to PLC failure.

However, the electromagnetic flowmeter must have a 485 interface and support the MODBUS RTU protocol.

In order to maintain stability, it is better to use electromagnetic flowmeters of the same manufacturer and the same brand when communicating with multiple flowmeters.

RS485 is a kind of industrial data bus. The electromagnetic flowmeter has RS485 serial communication so that digital communication replaces the transmission of PLC analog signals and ordinary switch signals. The PLC simulation calculation is reduced, and the accurate data collection and transmission are realized.

RS485 precession vortex flowmeter

Precession vortex flowmeter is a new type of gas flowmeter. It can be used for the measurement of natural gas, propane, air, nitrogen and other gases.

The converter can output frequency pulse, 4 ~ 20mA analog signal, and has RS485 interface, can be directly connected to the computer network, transmission distance up to 1.2km;

Precession Vortex Gas Flowmeter, like vortex flowmeter, is a velocity flowmeter. The cost performance of the intelligent precession vortex flowmeter is higher than vortex flowmeter. The intelligent precession vortex flowmeter can only measure gas. Precession Vortex Gas Flowmeter can be made into an integrated temperature and pressure compensation. And can measure various gases. Such as compressed air, oxygen, biogas, natural gas, coal gas, etc.

Read more about Everything You Need To Know About Electronic Flow Meters

Guide: Magnetic Flowmeter Installation

Magnetic flowmeters are mainly used to measure the flow of conductive media with good fluidity. Magnetic flowmeters are divided into insertion type and pipeline type. Pipeline electromagnetic flowmeter and insertion electromagnetic flowmeter has the same requirements for installation. There are also different places. Generally speaking, there are requirements for the external environment and installation methods.

A magnetic Flow Meter is a flow meter that measures the flow of conductive fluids. Abbreviated as EMF, also called Electromagnetic flowmeters. It is a kind of Volumetric flow meter. A magnetic flow meter measures the velocity of conductive liquids moving through a pipe or conduit. In the wastewater treatment industry, a Magnetic Flow Meter is the best flow meter choice.

Electromagnetic flowmeters have been used for more than 50 years and have been widely used worldwide. The fields involve water/sewage, chemical, pharmaceutical, paper, food, and other industries.

  • Water / Wastewater Industry
  • Food and Beverage
  • Metals
  • Brewing, Distilling, and Wine makening
  • HVAC
  • Chemical
  • Pulp and Paper
  • Pharmaceutical
  • Mining, Mineral Processing

Extended reading: How to Select the Right Agriculture Flow Meter

Magnetic flowmeters use the principle of Faraday’s Law of Electromagnetic Induction to measure the flow rate of liquid in a pipe. In the magnetic flowmeter pipe parts, a magnetic field is generated and channeled into the liquid flowing through the pipe. 

Faraday’s Law states that the voltage generated is proportional to the movement of the flowing liquid. A conductor moving through a magnetic field produces an electric signal within the conductor. And the singal is proportional to the velocity of the water moving through the field. 

As fluid flows through the magnetic field, conductive particles in the fluid create changes. This variation is used to measure and calculate the velocity of water flow through the pipe. When the fluid moves faster, more voltage is generated. The electronic transmitter processes the voltage signal to determine the liquid flow.

To learn more about Magnetic Flow Meters, this video by Emerson gives a good explanation.
Video source: https://www.youtube.com/watch?reload=9&v=lRSjYjg9WRo

Read more about Everything You Need To Know About Electronic Flow Meters

The premise of using an electromagnetic flowmeter is that the liquid to be measured must be conductive and cannot be lower than the threshold (ie, the lower limit). If the conductivity is lower than the threshold value, measurement errors will occur until it cannot be used. The threshold value of general-purpose electromagnetic flowmeters is between 10-4~(5×10-6)S/cm, depending on the model. The general conductivity threshold is 5×10-6S/cm=5μS/cm. the

The conductivity of industrial water and its aqueous solution is greater than 10-4S/cm. The conductivity of acid, alkali and salt solution is between 10-4 and 10-1S/cm. There is no problem in use, and the low-grade distilled water is 10-5S/cm cm is also not a problem.

Petroleum products and organic solvents cannot be used if their conductivity is too low.

Some pure liquids or aqueous solutions have low conductivity and are considered unusable. However, in the actual work of electromagnetic flowmeters, there will be instances where they can be used because they contain impurities, which are beneficial to increase the conductivity.

For the aqueous solution, the conductivity in the data is measured in the laboratory with pure water. The actual aqueous solution may be mixed with industrial water. The conductivity will be higher than that found. It is also conducive to flow measurement.

Step 1: Magnetic Flowmeter Installation environment requirements

In order to make the electromagnetic flowmeter work stable and reliable, the following requirements should be paid attention to when choosing the installation location:

  1. Try to avoid ferromagnetic objects and equipment with strong electromagnetic fields (large motors, large transformers, etc.). In order to prevent the magnetic field from affecting the working magnetic field and flow signal of the sensor.
  2. Install in a dry and ventilated place as much as possible. Avoid sun and rain. The ambient temperature should be -20 ~ +60 ℃. The relative humidity is less than 85%.
  3. There should be ample space around the flowmeter. Easy to install and maintain.

Extended reading: Ultrasonic Insertion Flow Meter for Lined/Large Pipes

Step 2: Magnetic Flowmeter Installation Location selection

The electromagnetic flowmeter can be installed on a horizontal pipe or a vertical pipe.

  1. Choose a straight pipe section filled with liquid, such as the vertical section of the pipeline (flow direction from bottom to top is appropriate) or a liquid-filled horizontal pipe (the lowest point in the entire pipeline is appropriate). The position must ensure that the pipeline is always filled with the measured fluid . In the process of installation and measurement, there must be no partial full pipe.
  2. Select the place where the fluid flow pulse is small. That is, it should be far away from pumps, valves, elbows and other local resistance parts.
  3. When measuring two-phase (solid, liquid or gas, liquid) fluids, choose a place that is not easy to cause phase separation.
  4. Avoid negative pressure at the measurement site.
  5. The diameter or circumference of the side pipe is easy to measure, and the ovality should be small.
  6. Straight pipe length: The length of the straight pipe on the upstream side of the sensor installation pipeline should be greater than or equal to 10D, and the downstream side should be no less than 5D.
  7. There are two methods for inserting the insertion point of the plug-in electromagnetic flow sensor: one is to insert it on the central axis of the pipe under test, and the other is to insert it at 0.25D where the inner wall of the pipe is the pipe.
  8. Vertical installation: when the sensor is inserted into the pipe, the angle between the vertical diameter of the pipe section and the pipe section should be less than 5°, which is suitable for measuring clean media with small pipe vibration.
  9. Tilt installation: the angle between the axis of the sensor and the axis of the pipeline being measured is 45°. It is suitable for liquid flow measurement with large pipe diameter and other impurities in the measuring medium. This installation method has low water resistance and is not suitable for entanglement.

Step 3: Mounting flange for Magnetic Flowmeter Installation

A. Select the installation location and select the front and rear straight pipe sections of appropriate length. Cut the pipe section where the flowmeter is installed;
B. Weld a flange on each of the front and rear straight pipe sections. After adding gaskets at both ends of the sensor, connect the sensor to the flange with stud bolts (note that the direction of the arrow on the meter body should be consistent with the direction of fluid flow);
C. Weld the front and rear straight pipe sections of the sensor to the original pipe.

Note:

  1. When welding, ensure that the flange end face is perpendicular to the centerline of the pipeline;
  2. The place where the mounting hole pitch is larger is the meter rod mounting position. And the direction of the mounting holes of the two flanges should be the same;
  3. After the flange is welded, the pipeline should be cleaned up and there should be no welding slag and other sundries.

Extended reading: Magnetic Large Dia. Pipe Flow Meter

Step 4: Converter installation and connection cables

Power and signal wiring. Please refer to the product manual accompanying the goods.

The converter of the split electromagnetic flowmeter should be installed near the sensor where it is convenient for reading and maintenance. It can also be installed in the instrument room, and its environmental conditions can be much better than the sensor.

The distance between the converter and the sensor is limited by the conductivity of the measured medium and the signal of the signal cable. That is, the distributed capacitance of the cable, the cross-section of the wire, and the number of shielding layers. Use the information cable provided with the instrument by the manufacturer.

For liquids with lower conductivity and longer transmission distances, three-layer shielded cables are also specified.

The general instrument “Instruction Manual” gives the corresponding transmission distance range for liquids with different conductivity.

When a single-layer shielded cable is used for industrial water or acid-base liquids, the transmission distance is usually 100m.

In order to avoid signal interference, the signal cable must be worn separately in a well-grounded steel protection tube. Never put the signal cable and the power cord in the same steel pipe.

Guess you like: Insertion Magnetic Flow Meter-Large diameter online install

Special Magnetic Flowmeter Installation situation

For pipelines that do not allow flow interruption in the process, a bypass pipe should be installed and cleaned when the flow meter is installed. As shown in the figure, this device ensures continuous operation of the equipment system when the flow meter is withdrawn from use.

The inner diameter measured by the flowmeter should be consistent with the inner diameter of the pipe. If the inner diameter cannot be the same, the inner diameter of the pipe should be greater than the inner diameter of the flowmeter. And install a tapered tube or expansion tube with a cone angle not greater than 15 between them, as shown in the figure.

When the flowmeter is installed inclined or vertically, the flow direction should be from top to bottom, as shown in the figure.

All Magnetic Flowmeter Installations. It cannot be described in detail here. If you encounter problems with the Magnetic Flowmeter Installation. Please contact our engineers in time. We will guide the Magnetic Flowmeter Installation for you.

Featured Magnetic Flowmeters for Sale

Frequently
Asked
Questions

Generally speaking, there will be an indication of the fluid flow direction on the main body of various flowmeters. When we install the flowmeter, just follow the instructions to install it.

Generally speaking, there are two principles for the installation direction of the flowmeter.

  1. Make sure to measure full of fluid. Because absolutely most of the flowmeters need to be in a full pipe state to ensure the measurement effect.
  2. Install according to the instructions of the flowmeter.

Electromagnetic flowmeters can be installed vertically. However, vertical installation needs to pay attention to the following aspects, whether it is installed at the water inlet or the water outlet. Standard installed in the middle of the vertical position where the water flows upwards. This installation complies with gravity.

If it is installed downstream, it will not be a full pipe, and the water flow from bottom to top is always full. This facilitates accurate measurement of the flow meter. The straight pipe section is required to be 10D in front and 5D in back to ensure the use and accuracy requirements of the electromagnetic flowmeter.

Electromagnetic flowmeter vertical installation requirements:

  1. Installed at the inlet of the pipeline (that is, upstream), so that the pipeline is always full.
  2. The electromagnetic flowmeter should be installed in the lower part of the horizontal pipeline, vertically upward. Avoid installing at high places and vertically downward positions in the pipeline.
  3. Requirements for straight pipe section: inlet/outlet straight pipe section: inlet ≥ 10×DN; water outlet ≥ 5×DN
  4. In order to facilitate the detection of the flowmeter, a bypass channel is set in the measuring pipeline.
  5. Grounding point requirements: In order to make the instrument work reliably, improve the measurement accuracy, and not be disturbed by strong external electromagnetic fields, the sensor should be well grounded, and the grounding resistance should be less than 10 ohms.

Generally speaking, there is no other cost to install a flow meter.
However, the actual situation needs to be determined according to the user’s pipeline situation.

The pump outlet flow meter should be installed after the pump outlet valve. But before regulating the valve. In this way, the regulating valve will not affect the measurement of the flowmeter.

The flowmeter is not allowed to be installed in front of the pump, because there will be negative pressure in front of the pump, which will affect the accuracy of the electromagnetic flowmeter. Therefore, the electromagnetic flowmeter must be installed behind the pump.

The installation distance depends on the length and width of your pipeline, and the flowmeter has certain requirements for the straight pipe sections before and after it. At least the straight pipe section in front of the flowmeter is 10 times the diameter of the flowmeter. The straight pipe section behind the flowmeter is 5 times the diameter of the flowmeter. The farther away from the straight pipe, the better.

More Flow Measurement Solutions

  • Irrigation Flow Meters for Agriculture Water System

    What is an irrigation flow meter? The irrigation flow meter is a flow meter designed for agricultural irrigation water counting. Agriculture, horticulture, etc. require water for irrigation. And water is…
  • How does a residential water meter work?

    What does a residential water meter look like? A residential water meter is a legal meter for measuring water consumption in residential communities, residential buildings, bungalows, and other places. What…
  • Chilled Water Flow Meter

    Application What is a Chilled Water Flow Meter? A chilled water flow meter refers to a flow meter that can be used to measure low-temperature water. Common chilled water flow…
  • 3 inch (3″) Water Meter

    Low cost 3″ Water Meter 3″ water meter is also DN80 water meter. Easy to read. Totalizing water volume. Intelligent large-caliber remote water meter includes wired remote transmission and wireless…
  • 2 inch Water Flow Meter

    2 inch water flow meter is also written as 2″ flow meter. If you are planning to buy a 2 inch water flow meter, please be sure to read this…
  • Inline water flow meters

    Featured inline water flow meters Strap on flow meter X3  External clamp-on flow sensor. Easy to install. Suitable for measuring pipe diameter Φ9.53~Φ90. Ultrasonic Water Meter for Residential Water DN15-DN40,…
  • Hot Water Flow Meters

    Hot Water Flow Meters Improve Heating-Boiler System Hot water flow meters refer to flow meters that can measure and indicate the flow of high temperature water. Hot water is widely…
  • Digital Water Flow Meters

    What is a digital water flow meter? A Digital Water flow meter is a flow meter that can display the water flow rate, and have the output for the flow…

Sino-Inst offer over 50 Magnetic Flow Meters, with Best Price.

A wide variety of Magnetic Flow Meters options are available to you, such as free samples, paid samples.

About 13% of these are magnetic flow meter, 14% are Insertion Magnetic Flow Meter, 25% are Venturi flow meter, 13% are ultrasonic flow meter, and others are Liquid Turbine Flow Meters.

Electromagnetic flowmeters can be divided into insertion electromagnetic flowmeters and pipeline electromagnetic flowmeters. The Magnetic Flowmeter Installation methods of insertion electromagnetic flowmeters and pipeline electromagnetic flowmeters have the same place, but there are also differences.

First of all, what we need is that the shielded wire of the electromagnetic flowmeter cannot be routed together with the cable, because this will cause interference. Under normal circumstances, the parameters of the inner head of the electromagnetic flowmeter are set in advance, so no other adjustments are required.

Magnetic Flowmeter Installation should avoid places where the temperature rises and falls too much, and places where there are magnetic fields and strong vibration sources.

Sino-Inst is Magnetic Flow Meters supplier, located in China. Magnetic Flow Meters products are most popular in North America, Mid East, and Eastern Europe. The United States, and India, which export 99%, 1%, and 1% of Magnetic Flow Meters respectively.

For how to install the electromagnetic flowmeter, the details of Magnetic Flowmeter Installation, if you have any questions and ideas, please feel free to contact us.

Solvent flow meters

The solvent flow meter is a flow meter that can measure solvent volume or mass flow. In the industrial production process, it is very important to accurately measure the amount of solvent. Solvents are divided into organic solvents and inorganic solvents according to their chemical composition. Solvents are commonly used raw materials in various industries such as coatings, paints, and dyes.

Solvent refers to a substance that can dissolve other solids, liquids, gases, and other solutes. The most common solvent in our daily lives is water. Generally, the solvent has a low boiling point and is easy to volatilize, and the solvent cannot produce a chemical reaction to the solute. Solvents are generally colorless and transparent liquids with unique odors.

Solvents play a very important role in adhesives.

Organic solvents are a large class of organic compounds that are widely used in life and production. They have a small molecular weight and are liquid at room temperature. Organic solvents include many types of substances, such as paraffin, alkenes, alcohols, aldehydes, amines, esters, ethers, ketones, aromatic hydrocarbons, hydrogenated hydrocarbons, terpene olefins, halogenated hydrocarbons, heterocyclic compounds, nitrogen-containing compounds, and sulfur-containing compounds, etc. Etc. Most of them are toxic to the human body.

Solvents are generally found in paints, adhesives, lacquers, and cleaners. Commonly used organic solvents include DMF, cyclohexanone, acetonitrile, acetic acid, methyl acetate, ethyl acetate, isopropanol, vinyl acetate, cyclohexane, n-hexane, n-heptane, etc.

Organic solvents are a class of organic compounds that can dissolve some water-insoluble substances (such as grease, wax, resin, rubber, dyes, etc.). Its characteristic is that it is liquid at room temperature and pressure. It has greater volatility. In dissolution During the process, the properties of the solute and solvent are unchanged.

There are many types of organic solvents, which can be divided into 10 categories according to their chemical structure:

①Aromatic hydrocarbons: benzene, toluene, xylene, etc.;
②Aliphatic hydrocarbons: pentane, hexane, octane, etc.;
③ Alicyclic hydrocarbons: cyclohexane, cyclohexanone, toluene cyclohexanone, etc.;
④ Halogenated hydrocarbons: chlorobenzene, dichlorobenzene, dichloromethane, etc.;
⑤Alcohols: methanol, ethanol, isopropanol, etc.;
⑥Ethers: ether, propylene oxide, etc.;
⑦Esters: methyl acetate, ethyl acetate, propyl acetate, etc.;
⑧ Ketones: acetone, methyl butanone, methyl isobutyl ketone, etc.;
⑨Diol derivatives: ethylene glycol monomethyl ether, ethylene glycol monoethyl ether, ethylene glycol monobutyl ether, etc.;
⑩Others: acetonitrile, pyridine, phenol, etc.

Read More about: Chemical Flow Meter Guide

Solvent flow meter – Oval Gear

An Oval Gear flowmeter as a mechanical flow meter is a common type of Volumetric Flow Meter. It can measure the volume flow of high viscosity and corrosive Solvent fluids.

  • High measurement accuracy;
  • The installation pipeline conditions have no influence on the measurement accuracy;
  • Can be used for high-viscosity liquids;
  • Wide range;
  • The direct-reading meter can directly obtain the cumulative and total amount without external energy.
  • Clear and clear, easy to operate.

Extended reading: Mechanical flow meter types

Solvent flow meter – Turbine

Turbine flow meters are velocity flow meters, also called impeller flow meters. Can be used to measure the instantaneous flow and cumulative flow of Solvent liquids.

Turbine flowmeters are widely used in flow measurement: petroleum, organic liquids, inorganic liquids, liquefied gas, natural gas, coal gas and cryogenic fluids. Turbine flowmeter signals can be divided into pulse signals or current signals (4-20mA). It is suitable for use with secondary display, PLC, DCS and other computer control systems.

Turbine Flow Meter reference price: USD 200-1700/pc.

Extended reading: non contact flow meter

Solvent flow meter – Electromagnetic

Magnetic Flow Meter is a flow meter that measures the flow of conductive Solvent fluids. Abbreviated as EMF, also called Electromagnetic flowmeters. It is a kind of Volumetric flow meter. A magnetic flow meter measures the velocity of conductive liquids moving through a pipe or conduit. In the wastewater treatment industry, Magnetic Flow Meter is the best flow meter choice.

  • Measures liquids or liquid slurries that have a minimum conductivity of 5 µS/cm.
  • Sanitary type, PTFE anticorrosive materials are optional.
  • Clamps, flanges, insertion installation are optional.
  • Battery powered optional.
  • Low cost.
  • DN 6 to DN2000
  • High precision: 0.5%, 0.2% optional

Extended reading: How to Select the Right Agriculture Flow Meter

Solvent flow meter – Gear

Gear flow meter is a micro digital positive displacement flow meter. Can measure very small flow rates and quantify small volumes of liquid. High and low-temperature resistance (-196℃-200℃).

The Gear flow meter for Microflow is made of stainless steel and is used for precise continuous or intermittent measurement of the flow or instantaneous flow of liquid. It is especially suitable for the flow measurement of heavy oil, polyvinyl alcohol, grease, and other high-viscosity media. It can measure the viscosity of Fluid up to 10000Pa.s.

Generally speaking, we can choose a suitable flow meter according to the different characteristics of chemical solvents. For example, high-viscosity solvents are recommended to use gear flow meters. For example, for corrosive solvents, electromagnetic flowmeters can be used. If you need to reduce costs, you can choose a turbine flowmeter.

Of course, it needs to be based on our actual measurement conditions, such as the temperature of the medium, the temperature of the pipeline, the pressure, and so on. Select the appropriate flow meter to achieve accurate measurement.

Extended reading: Cylinder Gear flow meter for micro flow measurement.

Guess you like: What is Reynolds number?

  • Grease Flow Meters

    What is a Grease Flow Meter? Grease Flow meters are meters dedicated to measuring the volume or mass flow of industrial grease fluids. The most common Grease Flow meters are…
  • How to Select Ultrasonic flow detectors?

    What is an ultrasonic flow detector? An ultrasonic flow detector is often understood as an ultrasonic flow meter or ultrasonic transducer. In fact, an Ultrasonic flow detector refers to the…
  • Irrigation Flow Meters for Agriculture Water System

    What is an irrigation flow meter? The irrigation flow meter is a flow meter designed for agricultural irrigation water counting. Agriculture, horticulture, etc. require water for irrigation. And water is…
  • Beginner’s Guide: Variable Area flow meter

    What is a variable area flow meter? Variable area flow meters are flow meters in which the fluid must pass through a restricted area. Because the flow cross-sectional area of…
  • How does a residential water meter work?

    What does a residential water meter look like? A residential water meter is a legal meter for measuring water consumption in residential communities, residential buildings, bungalows, and other places. What…

Extended Reading: Special Magnetic Flowmeter Installation situation

Sino-Inst, Manufacuturer for Solvent flow meters.

Sino-Inst’s Solvent flow meters, made in China, Having good Quality, With better price. Our flow measurement instruments are widely used in China, India, Pakistan, US, and other countries.

Grease Flow Meters

What is a Grease Flow Meter?

Grease Flow meters are meters dedicated to measuring the volume or mass flow of industrial grease fluids.

The most common Grease Flow meters are elliptical gear flow meters, also called positive displacement flowmeters. There are turbine flow meters, gear flow meters, and so on. Industrial grease can be measured online. Including hydraulic oil, steam turbine oil, refrigeration oil, heat treatment oil and heat transfer oil, etc. In addition, there are greases with lubricating oil as base oil and thickening agent.

Industrial Grease Flow meters are different from grease guns or grease meters. Industrial Grease Flow meters need to deal with more complex conditions. The pipe diameter can range from DN10 to DN200, or even larger. So how to choose the applicable Industrial Grease Flow meters? Let’s analyze it together.

Characteristics of industrial grease

What are the types of industrial grease?

Industrial greases mainly include hydraulic oil, gear oil, turbine oil, compressor oil, refrigeration oil, transformer oil, vacuum pump oil, bearing oil, metal processing oil (liquid), anti-rust grease, cylinder oil, heat treatment oil, and heat transfer oil.

Extended reading: High Temperature Flow Meter

In addition, there are greases with lubricating oil as base oil and thickening agent. The users of industrial lubricants are companies from all walks of life, and they use many varieties and large amounts.

The basic performance and main selection principle of industrial grease is viscosity. GB/T3141-94 is the ISO viscosity classification of industrial liquid lubricants, which is equivalent to the international standard ISO3448-1992 “Industrial Liquid Lubricants-ISO Viscosity Classification”.

So, when we choose an industrial grease flow meter, we first need to consider the viscosity of the grease. Then consider the flow range and temperature. And other special requirements of users.

Our commonly used industrial grease flow meters are oval gear flow meters, turbine flow meters, and gear flow meters. There is also a mass flow meter. Next, let’s discuss separately.

Grease Flow Meters-Oval Gear

Oval gear flowmeter is a volumetric meter for continuous or intermittent measurement and control of liquid flow in a pipeline.

Oval gear flowmeter, also known as positive displacement flowmeter. A positive displacement flowmeter as a mechanical flow meter is a common type of Volumetric Flow Meter. It can measure the volume flow of high viscosity and corrosive fluids.

  • Volumetric Flow Meters
  • High measurement accuracy;
  • The installation pipeline conditions have no influence on the measurement accuracy;
  • Can be used for high-viscosity liquids;
  • Wide range;
  • The direct-reading meter can directly obtain the cumulative and total amount without external energy.
  • Clear and clear, easy to operate.

Therefore, we recommend that when the grease viscosity is high, you can first consider using an oval gear flowmeter.
Viscosity: 0.6—2mPa.s—200mPa.s—1000mPa.s-2000mPa.s.
Temperature: -20~+200℃

Extended reading: Sanitary Positive Displacement Flow Meter

Grease Flow Meters-Turbine

Turbine flow meters are velocity flow meters, also called impeller flow meters. Can be used to measure the instantaneous flow and cumulative flow of liquids and gases.

Turbine flowmeters are widely used in flow measurement: petroleum, organic liquids, inorganic liquids, liquefied gas, natural gas, coal gas, and cryogenic fluids. Turbine flowmeter signals can be divided into pulse signals or current signals (4-20mA). It is suitable for use with secondary display, PLC, DCS, and other computer control systems.

Therefore, when measuring low-viscosity oils, such as diesel, edible oil, etc., we recommend that turbine flowmeters be considered first.

Extended reading: What Is Hydraulic Flow Meter?

Grease Flow Meters-Gear

Gear flow meter is a micro digital positive displacement flow meter. Can measure very small flow rates and quantify small volumes of liquid. High and low-temperature resistance (-196℃-200℃).

The Gear flow meter for Microflow is made of stainless steel and is used for precise continuous or intermittent measurement of the flow or instantaneous flow of liquid. It is especially suitable for the flow measurement of heavy oil, polyvinyl alcohol, grease, and other high-viscosity media. It can measure the viscosity of Fluid up to 10000Pa.s.

  • High pressure resistance (1.0-45MPa)
  • High and low temperature resistance (-196℃-200℃)
  • Can measure various viscous media
  • High precision and repeatability
  • Pulse output/analog output optional
  • Wide range ratio (1:100)
  • Wide measuring range
  • Strong anti-corrosion and anti-fouling ability (acid and alkali)

Therefore, it is recommended to use Gear flow meters, when you need to measure grease in the following situations:High viscosity, low flow rate;Ultra-high temperatureUltra-low temperature;Small caliber;high pressure.

Extended Reading: Types Of Crude Oil Flow Meters

Grease Flow Meters-Mass

Mass flow meter directly measures the mass flow of the medium passing through the flow meter. It can also measure the density, temperature, and viscosity of the medium

Mass flow meter is a flow measuring instrument that measures the mass flow in the pipeline. The volume of a fluid is a function of fluid temperature and pressure and is a dependent variable. The quality of a fluid is a quantity that does not change with time, space temperature, and pressure. More about: What Is Mass Flow Rate?

The mass flow meter has high accuracy. But the price is expensive. Therefore, when you need high-precision measurement, you can choose to use a mass flow meter.

Extended reading: Fuel Flow Meter for Boat-Selection & Application

Tool: Volumetric Flow Rate & Pipe Diameter to Flow Speed Calculator

Find the most appropriate industrial grease flow meter from Sino-Inst for a variety of engineering and industrial purposes. Suitable for various fluids with different pressures and volumes. The choice of these depends on whether the volumetric or mass flow rate is to be measured. Grease flow meters offered on the site have wide minimum and maximum pressure ranges, which is considered to be a desirable quality as they can be used for a wider variety of fluids. These grease flow meters are highly accurate.

Explore Oil and Gas Flow Meters

You may like:

Extended Reading: Guide and Selection for Diesel Fuel Flow Meters

What is Flow Meter K-factor? And how to calculate?

What is the K-factor in a flow meter?

K-factor is a coefficient calculated by calibrating and comparing with other measuring devices that meet the accuracy requirements. The Flow Meter K-factor will be confirmed before it is put into use.

This coefficient is a fixed value. It is the actual coefficient obtained by the flowmeter manufacturer after verifying each instrument. Nothing to do with the initial design

The flow coefficient of the flowmeter refers to the proportional relationship between the measured flow and the flow of the standard device under certain conditions. The Flow Meter K-factor is given by the manufacturer when it is calibrated.

The K value is easily immobile. Therefore, as a manufacturer, we generally set a password for the flowmeter.

Flow meter k-factors

Liquid Turbine Flow Meter is a speed-type flow meter based on the principle of torque balance.

The fluid flows through the sensor housing. Because the blades of the impeller have a certain angle with the flow direction. The impulse of the fluid makes the blades have a rotational torque. After the friction torque and fluid resistance are overcome, the blades rotate. The speed is stable after the torque is balanced.

Under certain conditions, the speed is proportional to the flow rate.

Due to the magnetic permeability of the blade, it is in the magnetic field of the signal detector (composed of permanent magnets and coils). The rotating blade cuts the magnetic lines of force. The magnetic flux of the coil is periodically changed. Electrical pulse signals are induced at both ends of the coil.

This signal is amplified and reshaped by an amplifier. A continuous rectangular pulse wave with a certain amplitude is formed. It can be transmitted to the display instrument remotely. The instantaneous flow or total amount of the fluid is displayed.

Within a certain flow range, the pulse frequency f is proportional to the instantaneous flow Q of the fluid flowing through the sensor. The flow equation is:

Where:
f——Pulse frequency [Hz]
k——The meter coefficient of the sensor [1/m3], which is given by the calibration sheet.
Q——The instantaneous flow of fluid (under working condition) [m3/h]
3600-conversion factor in seconds

The meter coefficient of each sensor is filled in the verification certificate by the manufacturer. The k value is set in the matching display instrument. The instantaneous flow and cumulative total can be displayed.

Guess you like: What is Reynolds number?

Extended reading: Turbine Flow meter Vs Gear Flow meter

Vortex flowmeter is a speed-type flowmeter produced according to Karman’s vortex principle,
which can be used for the measurement and measurement of conventional gas, steam and
liquid.

Vortex flow sensor has high precision and wide range ratio, no moving parts in use, which can
improve mechanical stability and reduce maintenance. Vortex flowmeter is almost not affected by the temperature, pressure, and composition of medium when measuring the volume of working conditions.

Extended reading: High Pressure Rotameter for Liquids/gas-Upto 25 Mpa

Therefore, it is convenient to calibrate the instrument, so the vortex street flow sensor is widely used in production and life.

When a trigonal column vortex generator is set in the fluid, regular vortices are generated alternately on both sides of the vortex generator, which is called Carmen vortex.

The vortex columns are arranged asymmetrically downstream of the vortex generator. Vortex flowmeter is produced according to this principle.

Vortexes are generated by generating bodies and the number of vortexes is detected by high-sensitivity sensors. In a certain range, the number of vortexes generated is proportional to the flow rate.

In vortex flowmeter, the relationship between flow rate and the number of vortexes generated
can be expressed by the following formula:

Q:Operating volume flow of the measured medium. The unit is m3/h。
F:Frequency of the number of vortices produced by the generating body. The unit is Hz.
K:Refers to the calculated or calibrated flow coefficient. It represents how many frequency signals per cube. the coefficient is usually obtained by calibration.

The formula of standard table method calibration coefficient K:

The formula can also be used for flow correction.

Extended Reading: Magnetic Battery Operated Flow Meter

K coefficient of gear flow transmitter (flow coefficient) defines the number of impulses per L within the unit flow precisely.

The following formula is used:

Q=f×60/K

Q=Instantaneous flow L/min
F=Frequency of output impulse(HZ)
K= Coefficient of gear flow meter(impulse/min)

Read more General-purpose Flow Totalizer for Data collection and calculation

K-Factors calculation

1.What is a K-factor?

Simply stated a K-factor is a dividing factor. The term is usually encountered when dealing with pulse signals although analog K-factors are sometimes used.

2. Pulse Signal K-factors

All pulse output type flow meters when they are dispatched by their manufacturer will have a calibration certificate. The calibration certificate will show that the meter has been calibrated over its flow range and noted on the certificate will be the average K-factor for the meter.

This K-factor will be given in terms of the number of pulses produced by the meter for a given volumetric flow. (e.g.) 200 pulses per U.S. gallon, 150 pulses per liter, etc.

This K-factor is the value that is entered into a batch meter or indicator/totalizer in order to give a readout in engineering units.

Example 1

If the display on a rate meter is required in U.S. gallons per second, and the K-factor of the flow meter is 210 pulses per U.S. gallon, then the K-factor entered into the rate meter would be 210.

If a totalizer associated with the same flow meter was to be set up so as to totalize in U.S. gallons the totalizer K-factor would be 210.

If the totalizer was to be set to totalize in tenths of a gallon the K-factor would be 210/10 = 21

Example 2

If the display on a rate meter is required in U.S. gallons per minute, and the K-factor of the flowmeter is 210 pulses per U.S. gallon, then the K-factor entered into the rate meter would be: 210/60 = 3.5

3.K-factors for Analog Input Signals

When batching, indication or totalization has to be carried out using an analog input signal a KEP product first converts the 4 to 20 mA signal into a 0 to 10000 Hz. signal. The K-factor is then calculated by relating the engineering unit equivalent of 20 mA to the 10000 Hz. signal.

Extended Reading: Mechanical flow meter for diesel

Example 3

A vortex meter outputs 20 mA when the flow is 2000 U.S. gallons per minute, we wish to display the rate in gallons per minute.
The rate K-factor is = 10000/2000 = 5

The value of the totalizer K-factor will depend on whether the flow rate was given in units per second, a minute, or hour and whether it is desired to totalize in whole units, tenths, hundredths, etc.

If the flow rate was given in units per second the totalizer K-factor (for whole units) is obtained by multiplying the rate K-factor by 1.

If the flow rate was given in units per minute the totalizer K-factor (for whole units) is obtained by multiplying the rate K-factor by 60.

If the flow rate was given in units per hour the totalizer K-factor (for whole units) is obtained by multiplying the rate K-factor by 3600.

The totalizer K-factor in example 3 will be = 5 x 60 = 300 in order to totalize in gallons.

If we wished to totalize in tenths of a gallon the K-factor would be 5 x 60/10 = 30

Extended reading: rotameter applications

Example 4

An electromagnetic flow meter outputs 20 mA when the flow is 20 liters per second, we wish to display the flow rate in liters per second and totalize in M³.
The rate K-factor is 10000/20 = 500
The totalizer K-factor will be 500 x 1/0.001 = 500000

Extended reading: Liquid Bitumen/Asphalt Flow Meter

4.Multi-Point K-factors

Some flow applications dictate that multiple K-factors are used. Two applications that require multiple K-factors are:

  • flow meters with nonlinear outputs
  • wide turndown flow applications

KEP meters have an option available that allows the user to input from 3 to 16 K-factors. This multi-point K-factor option is available for both pulse and analog inputs.

5.Multi-Point K-factors for Pulse inputs

The first step is to calculate K-factors to cover each flow range. This is done by taking the information on the flow meter manufacturer’s calibration sheet and calculating the K-factors as per section 2. An alternative to using the manufacturers’ data is to conduct tests on-site against a calibrated standard.

The second step is to relate an incoming frequency range from the flow meter to a given calculated K-factor.

The final step is to program these values into the KEP instrument.

Read more about: what is gpm;

Example 5

A turbine flow meter has the following calibration data.

Extended reading: Orifice Plate Flow Meter

6.Multi Point K-factors for Analog Inputs

The procedure for analog inputs is essentially the same as for pulse inputs.

The first step is to calculate K-factors to cover each flow range. This is done by taking the information on the flow meter manufacturer’s calibration sheet and calculating the K-factors as per section 3. An alternative to using the manufacturer’s data is to conduct tests on site against a calibrated standard.

The second step is to relate an incoming flow value from the flow meter to a given calculated K-factor.

The final step is to program these values into the KEP instrument.

Example 6

A vortex flowmeter has the following calibration data.

Base K-factor 10000/100 = 100

Note that the point after the final one should have a flow value entered that is very much higher than the true maximum flow rate of the meter. Note also that as the last two K-factors are the same any flow above 100 gpm will be modified by a K-factor of 104. The setup is now complete.

Extended reading: Flow Totalizer F3000X for Data collection and calculation

You may like:

Sino-Inst offers over 50 flow meter for flow measurement. About 50% of these are differential pressure flow meters, 40% is the liquid flow sensor, and 20% are Ultrasonic flow Transmitter and mass flow meter.

A wide variety of flow meters options are available to you, such as free samples, paid samples.

Sino-Instrument is a globally recognized supplier and manufacturer of flow measurement instrumentation, located in China.

How to Select Ultrasonic flow detectors?

What is an ultrasonic flow detector?

An ultrasonic flow detector is often understood as an ultrasonic flow meter or ultrasonic transducer. In fact, an Ultrasonic flow detector refers to the probe part of the ultrasonic flow meter or sensor part. Ultrasonic flow detectors can be equipped with different ultrasonic flow detectors to meet different measurement needs. For example, a portable ultrasonic flowmeter can be equipped with a clamp Ultrasonic flow detector. commonly used in water, oil, and other single liquid flow rate detection.

Ultrasonic flow detectors types

Ultrasonic flow detectors can be divided into external paste type, insertion type, and pipe section type according to the installation method.

A) Clamp-on type

External paste type ultrasonic flowmeter is produced earlier, the user is more familiar with and more widely used ultrasonic flowmeter. Installation of the transducer without pipeline disconnection. That is posted that use, it fully embodies the ultrasonic flowmeter installation is simple, easy to use characteristics.

Extended reading: Portable ultrasonic flow meter for water

B)Pipe section type

Certain pipelines due to material sparse, poor sound conduction, rust and corrosion is serious. Lining and pipeline space with gaps and other reasons. Resulting in serious ultrasonic signal attenuation. Ultrasonic flowmeter with external paste type can not be measured normally. Generated the pipe segment ultrasonic flowmeter.

Pipe segment ultrasonic flowmeter to the converter and measuring tube composition as a whole, to solve the external paste flowmeter measurement in a problem. Measurement accuracy is also higher than other ultrasonic flowmeter. But at the same time also sacrificed the advantages of the external paste type ultrasonic flowmeter non-flow installation. Requires the installation of the transducer to cut the pipe.

Extended Reading: Inline Ultrasonic Flow Meter

C) Insertion type

Insertion type ultrasonic flowmeter in between the above two. Installation can be non-stop flow, the use of special tools have water pipes on the hole, the transducer into the pipe, complete the installation. Transducer pipeline, its signal emission, receiving only the measured medium. Its measurement is not limited by the pipe quality and pipe lining materials.

TM series standard clamp-on Ultrasonic flow detectors

  • With a strong magnet, when measuring steel and cast iron pipes, the sensor only needs to be adsorbed on the outer wall of the pipe.
  • Equipped with a ground terminal, can be used in the occasion of strong electromagnetic interference.
  • Can be fixed by a steel belt, steel wire rope, tensioning belt, special clamps.
  • The upper cover of the sensor is marked with the direction of ultrasonic signal emission.
  • The protection level can reach IP68 after the junction box is filled with glue.
  • Complete specifications, divided into large, medium, and small models, measuring pipe diameter range: DN15~DN6000mm.
  • Temperature range: -40~90℃.
  • According to the different uses, the standard clamp-on sensors are divided into two categories: portable and stationary.

1 Tensioning belt fastening groove
2 Wire rope fastening groove
3 Steel belt fastening slot
4 Top cover fastening screw
5 Signal emission direction indication arrow
6 Sound wedge
7 Powerful magnets
8 Anti-slip groove

9 Upstream and downstream sign sticker
10 Cable interface
11 Installation distance measurement starting and ending points
12 Product information label
13 Positive terminal block
14 Negative terminal block
15 Ground terminal block
16 Junction box

Clamp-on Ultrasonic Flow Meter Working Principle

Clamp on Ultrasonic Flow Meter adopts the measurement principle of time difference method. It uses the ultrasonic wave emitted by the sensor to propagate in the flowing fluid. The sound wave propagation speed in the downstream direction will increase, and the backward direction will decrease. In the same propagation distance, there will be different transmission times. According to the difference between the transmission time and the measured The relationship between fluid velocity measures the fluid velocity.

The flow rate of the fluid is different in different positions in the tube. The flow rate in the center of the tube is faster than the flow rate near the wall of the tube. The flow velocity distribution of the fluid in the pipeline can be represented by the flow velocity cross-sectional distribution diagram.

By setting the flowmeter and considering the cross-sectional distribution of the flow velocity, the average flow velocity can be calculated. Then the volume flow of the fluid can be obtained according to the cross-sectional area of the pipe.

Notes:
V measure fluid velocity
M ultrasonic reflection times
D pipe diameter
θ The angle between the ultrasonic signal and the fluid
T up The time when the downstream sensor transmits the signal to the upstream
T down Time from upstream sensor to downstream
ΔT = T up – T down

Guess You’ll Like: Ultrasonic flow meters types & technical guide

HT series high temperature clamp-on ultrasonic flowmeter sensor

  • With high temperature resistant powerful magnet, when measuring steel and cast iron pipes, the sensor only needs to be adsorbed on the outer wall of the pipe.
  • Equipped with ground terminal, can be used in the occasion of strong electromagnetic interference.
  • Can be fixed by steel belt, steel wire rope, tensioning belt, special clamps.
  • The upper cover of the sensor is marked with the direction of ultrasonic signal emission.
  • The protection level can reach IP68 after the junction box is filled with glue.
  • Complete specifications, divided into large, medium and small specifications, measuring pipe diameter range: DN15~DN6000mm,
  • Temperature range: -40~160℃.
  • According to the different uses, high temperature clamp-on sensors are divided into two categories: portable and fixed.

1 Tensioning belt fastening groove
2 Wire rope fastening groove
3 Steel belt fastening slot
4 Top cover fastening screw
5 Signal emission direction indication arrow
6 Sound wedge
7 Powerful magnets
8 Anti-slip groove

9 Upstream and downstream sign sticker
10 Cable interface
11 Installation distance measurement starting and ending points
12 Product information label
13 Positive terminal block
14 Negative terminal block
15 Ground terminal block
16 Junction box

Extended reading: Flow Totalizer F3000X for Data collection and calculation

Other commonly used ultrasonic flow detectors:

What Does an Ultrasonic Doppler Flow Detector Measure?

From the ultrasonic measurement principle, the time difference method is suitable for measuring pure and less impurity liquids. Such as tap water, river seawater, sewage treatment plant effluent, etc. The Doppler method is suitable for measuring liquids and slurries with a high impurity content. Such as urban drainage, mud, pulp and so on.

Judging from the company’s years of practical experience, the two measurement methods are relatively vague for the quantitative indicators of the impurity content of the measured medium. The main reason is that there is currently no effective instrumentation for measuring the impurity content of liquids.

Doppler ultrasonic flowmeter flow rate measurement is based on the Doppler effect. The probe emits a beam of ultrasonic waves obliquely upward. Ultrasound propagates in fluids. The fluid will contain impurities such as bubbles or particles (it can be considered that the impurities in the fluid are at the same speed as the water flow).

When the ultrasonic wave contacts the impurities in the fluid, the reflected ultrasonic wave will produce a Doppler frequency shift Δf. The Doppler shift Δf is proportional to the flow velocity. The flow velocity of the fluid can be measured by measuring the Doppler frequency shift Δf.

The Dopp ultrasonic flowmeter uses the velocity area method to measure the flow. The flow velocity V is measured using an ultrasonic flow velocity sensor. Use a pressure water level gauge to measure the water level H. The channel parameters set in the controller in advance. The controller can use the water level to automatically convert the flow area S. The formula for the flow rate of the fluid is:

Q= V×S

Wherein V- – – -flow velocity S- – – -flow area Q- – -instantaneous flow

Since the velocity area method is used to measure the flow, it can be applied to any shape of the section.

Related Blogs

Guess you like: Insertion Magnetic Flow Meter-Large diameter online install

FAQ

Ultrasonic flowmeter refers to a flowmeter developed based on the principle that the propagation velocity of ultrasonic waves in the flow medium is equal to the average flow velocity of the measured medium and the vector sum of the velocity of the sound waves in the stationary medium.

According to the principle of signal detection, ultrasonic flowmeter can be divided into propagation speed difference method (direct time difference method, time difference method, phase difference method and frequency difference method), beam shift method, Doppler method, mutual correlation method, spatial filtering method and noise method, etc.

Our time difference ultrasonic flowmeter: measuring the time difference caused by the difference in propagation velocity when propagating downstream and upstream to calculate the measured fluid velocity.

The measurement accuracy of the ultrasonic flowmeter is very high. Almost no interference from various parameters of the measured medium.

Sino-Inst manufactures and supplies ultrasonic flow meters with an accuracy of 1%. This accuracy can meet the measurement needs of most customers.

In particular, it can solve the flow measurement problems of strong corrosive, non-conductive, radioactive and flammable and explosive media that other instruments cannot.

So what causes the inaccurate measurement of the ultrasonic flowmeter?

The following are the reasons for the inaccurate measurement:
The influence of pipeline parameter equipment on the accuracy of ultrasonic flowmeter measurement.
The influence of upstream and downstream straight pipes on the accuracy of ultrasonic flowmeter measurement.
The influence of couplant on measurement accuracy.
The influence of the installation position of the ultrasonic flowmeter transducer on the measurement accuracy.

Sino-Inst produces and supplies ultrasonic flow meters mainly for measuring water, seawater, industrial sewage, acid and alkaline liquids, alcohol, beer, various oils, and other single homogeneous liquids that can conduct ultrasonic waves. Of course, there are also ultrasonic flowmeters that can measure gas.

According to the measurement method can be divided into Doppler ultrasonic flowmeter, time difference ultrasonic flowmeter, hybrid ultrasonic flowmeter.

A)Doppler type ultrasonic flowmeter

B) time difference ultrasonic flowmeter

C)Mixed ultrasonic flowmeter

Related products:

Find more Ultrasonic Flow Meters for Liquids|Clamp-on|Insertion|inline

Sino-Inst, Manufacturer for Ultrasonic flow detectors. It can measure a single sound-conducting liquid medium of DN 15—150mm. It can measure even liquids such as water, seawater, oil, and slurry.

Sino-Inst’s Ultrasonic flow detectors, made in China, Having good Quality, With better price. Our flow measurement instruments are widely used in China, India, Pakistan, the US, and other countries.