What is the K-factor in a flow meter?

K-factor is a coefficient calculated by calibrating and comparing with other measuring devices that meet the accuracy requirements. The Flow Meter K-factor will be confirmed before it is put into use.

This coefficient is a fixed value. It is the actual coefficient obtained by the flowmeter manufacturer after verifying each instrument. Nothing to do with the initial design

What is the K-factor in a flow meter?

The flow coefficient of the flowmeter refers to the proportional relationship between the measured flow and the flow of the standard device under certain conditions. The Flow Meter K-factor is given by the manufacturer when it is calibrated.

The K value is easily immobile. Therefore, as a manufacturer, we generally set a password for the flowmeter.

Flow meter k-factors

Liquid Turbine Flow Meter is a speed-type flow meter based on the principle of torque balance.

The fluid flows through the sensor housing. Because the blades of the impeller have a certain angle with the flow direction. The impulse of the fluid makes the blades have a rotational torque. After the friction torque and fluid resistance are overcome, the blades rotate. The speed is stable after the torque is balanced.

Under certain conditions, the speed is proportional to the flow rate.

Due to the magnetic permeability of the blade, it is in the magnetic field of the signal detector (composed of permanent magnets and coils). The rotating blade cuts the magnetic lines of force. The magnetic flux of the coil is periodically changed. Electrical pulse signals are induced at both ends of the coil.

This signal is amplified and reshaped by an amplifier. A continuous rectangular pulse wave with a certain amplitude is formed. It can be transmitted to the display instrument remotely. The instantaneous flow or total amount of the fluid is displayed.

Within a certain flow range, the pulse frequency f is proportional to the instantaneous flow Q of the fluid flowing through the sensor. The flow equation is:

Where:
f——Pulse frequency [Hz]
k——The meter coefficient of the sensor [1/m3], which is given by the calibration sheet.
Q——The instantaneous flow of fluid (under working condition) [m3/h]
3600-conversion factor in seconds

The meter coefficient of each sensor is filled in the verification certificate by the manufacturer. The k value is set in the matching display instrument. The instantaneous flow and cumulative total can be displayed.

Vortex flowmeter is a speed-type flowmeter produced according to Karman’s vortex principle,
which can be used for the measurement and measurement of conventional gas, steam and
liquid.

Vortex flow sensor has high precision and wide range ratio, no moving parts in use, which can
improve mechanical stability and reduce maintenance. Vortex flowmeter is almost not affected by the temperature, pressure, and composition of medium when measuring the volume of working conditions.

Therefore, it is convenient to calibrate the instrument, so the vortex street flow sensor is widely used in production and life.

When a trigonal column vortex generator is set in the fluid, regular vortices are generated alternately on both sides of the vortex generator, which is called Carmen vortex.

The vortex columns are arranged asymmetrically downstream of the vortex generator. Vortex flowmeter is produced according to this principle.

Vortexes are generated by generating bodies and the number of vortexes is detected by high-sensitivity sensors. In a certain range, the number of vortexes generated is proportional to the flow rate.

Vortex Shedding Flow Meter Working Principle

In vortex flowmeter, the relationship between flow rate and the number of vortexes generated
can be expressed by the following formula:

Q:Operating volume flow of the measured medium. The unit is m3/h。
F:Frequency of the number of vortices produced by the generating body. The unit is Hz.
K:Refers to the calculated or calibrated flow coefficient. It represents how many frequency signals per cube. the coefficient is usually obtained by calibration.

The formula of standard table method calibration coefficient K:

The formula can also be used for flow correction.

K coefficient of gear flow transmitter (flow coefficient) defines the number of impulses per L within the unit flow precisely.

The following formula is used:

Q=f×60/K

Q=Instantaneous flow L/min
F=Frequency of output impulse(HZ)
K= Coefficient of gear flow meter(impulse/min)

K-Factors calculation

1.What is a K-factor?

Simply stated a K-factor is a dividing factor. The term is usually encountered when dealing with pulse signals although analog K-factors are sometimes used.

2. Pulse Signal K-factors

All pulse output type flow meters when they are dispatched by their manufacturer will have a calibration certificate. The calibration certificate will show that the meter has been calibrated over its flow range and noted on the certificate will be the average K-factor for the meter.

This K-factor will be given in terms of the number of pulses produced by the meter for a given volumetric flow. (e.g.) 200 pulses per U.S. gallon, 150 pulses per liter, etc.

This K-factor is the value that is entered into a batch meter or indicator/totalizer in order to give a readout in engineering units.

Example 1

If the display on a rate meter is required in U.S. gallons per second, and the K-factor of the flow meter is 210 pulses per U.S. gallon, then the K-factor entered into the rate meter would be 210.

If a totalizer associated with the same flow meter was to be set up so as to totalize in U.S. gallons the totalizer K-factor would be 210.

If the totalizer was to be set to totalize in tenths of a gallon the K-factor would be 210/10 = 21

Example 2

If the display on a rate meter is required in U.S. gallons per minute, and the K-factor of the flowmeter is 210 pulses per U.S. gallon, then the K-factor entered into the rate meter would be: 210/60 = 3.5

3.K-factors for Analog Input Signals

When batching, indication or totalization has to be carried out using an analog input signal a KEP product first converts the 4 to 20 mA signal into a 0 to 10000 Hz. signal. The K-factor is then calculated by relating the engineering unit equivalent of 20 mA to the 10000 Hz. signal.

Example 3

A vortex meter outputs 20 mA when the flow is 2000 U.S. gallons per minute, we wish to display the rate in gallons per minute.
The rate K-factor is = 10000/2000 = 5

The value of the totalizer K-factor will depend on whether the flow rate was given in units per second, a minute, or hour and whether it is desired to totalize in whole units, tenths, hundredths, etc.

If the flow rate was given in units per second the totalizer K-factor (for whole units) is obtained by multiplying the rate K-factor by 1.

If the flow rate was given in units per minute the totalizer K-factor (for whole units) is obtained by multiplying the rate K-factor by 60.

If the flow rate was given in units per hour the totalizer K-factor (for whole units) is obtained by multiplying the rate K-factor by 3600.

The totalizer K-factor in example 3 will be = 5 x 60 = 300 in order to totalize in gallons.

If we wished to totalize in tenths of a gallon the K-factor would be 5 x 60/10 = 30

Example 4

An electromagnetic flow meter outputs 20 mA when the flow is 20 liters per second, we wish to display the flow rate in liters per second and totalize in M³.
The rate K-factor is 10000/20 = 500
The totalizer K-factor will be 500 x 1/0.001 = 500000

4.Multi-Point K-factors

Some flow applications dictate that multiple K-factors are used. Two applications that require multiple K-factors are:

  • flow meters with nonlinear outputs
  • wide turndown flow applications

KEP meters have an option available that allows the user to input from 3 to 16 K-factors. This multi-point K-factor option is available for both pulse and analog inputs.

5.Multi-Point K-factors for Pulse inputs

The first step is to calculate K-factors to cover each flow range. This is done by taking the information on the flow meter manufacturer’s calibration sheet and calculating the K-factors as per section 2. An alternative to using the manufacturers’ data is to conduct tests on-site against a calibrated standard.

The second step is to relate an incoming frequency range from the flow meter to a given calculated K-factor.

The final step is to program these values into the KEP instrument.

Example 5

A turbine flow meter has the following calibration data.

 turbine flow meter k-factor
 turbine flow meter k-factor  2
 turbine flow meter k-factor 3

6.Multi Point K-factors for Analog Inputs

The procedure for analog inputs is essentially the same as for pulse inputs.

The first step is to calculate K-factors to cover each flow range. This is done by taking the information on the flow meter manufacturer’s calibration sheet and calculating the K-factors as per section 3. An alternative to using the manufacturer’s data is to conduct tests on site against a calibrated standard.

The second step is to relate an incoming flow value from the flow meter to a given calculated K-factor.

The final step is to program these values into the KEP instrument.

Example 6

A vortex flowmeter has the following calibration data.

Base K-factor 10000/100 = 100

A vortex flowmeter has the following calibration data
A vortex flowmeter has the following calibration data2

Note that the point after the final one should have a flow value entered that is very much higher than the true maximum flow rate of the meter. Note also that as the last two K-factors are the same any flow above 100 gpm will be modified by a K-factor of 104. The setup is now complete.

Extended reading: Flow Totalizer F3000X for Data collection and calculation

You may like:

How to Select Ultrasonic flow detectors?

Ultrasonic flow detectors types Ultrasonic flow detectors can be divided into external paste type, insertion type, and pipe section type according to the installation method. A) Clamp-on type External paste type ultrasonic flowmeter is produced earlier, the user is more Read More

Irrigation Flow Meters for Agriculture Water System

Agricultural irrigation water system It consists of irrigation canal head project, water transmission and distribution project and field irrigation project. ①Irrigation canal head project has reservoirs, pumping stations, dammed diversion projects, damless diversion projects, wells and other forms. Used to Read More

Technical Guide – Thermal mass flow meter

Thermal mass flow meter working principle Thermal gas mass flow meter is designed on the basis of thermal dispersion. And adopts method of constant differential temperature to measuring gas flow. It has advantages of small size, easy installation, high reliability Read More

Beginner’s Guide: Variable area flow meter

Variable area flow meter principle The principle of the variable area flowmeter is to keep the pressure drop constant and use the change of the throttle area to measure the flow rate. It consists of a tapered tube gradually expanding Read More

Ultrasonic water flow meters | Accurate and Easy solution

Ultrasonic water flow meter types According to the measurement principle Time difference method ultrasonic flowmeter; Frequency difference method ultrasonic flowmeter; Phase difference method ultrasonic flowmeter; Doppler ultrasonic flowmeter; Ultrasonic flowmeters for partially full pipes and river channels that combine liquid Read More

How does a residential water meter work?

Residential Water Meters Types The types of water meters can be divided by the principle of measurement. The common types are mechanic water meters, mechanical water meters equipped with electronic devices, and electronic water meters. Read more about Everything You Need Read More

Chilled Water Flow Meter

Chilled Water Flow Meter Types Featured Chilled Water Flow Meters Extended reading:What is the K-factor in a flow meter?Cryogenic Flow Meters|Liquid Nitrogen-Liquid Oxygen-LNG fluids What are the limitations of electromagnetic flowmeters at low temperatures? Electromagnetic flowmeter transmitters are bound by Read More

Mechanical Flow Meters

Mechanical flow meter types There are many types of flow meters. The electromagnetic flowmeter is based on the electromagnetic principle. When a conductive fluid flows through an electromagnetic field, the velocity of the fluid can be obtained by measuring the Read More

Industrial Oil Flow Meters

Industrial oil flow meters measure the volume or mass of oil. Can realize the mutual conversion of volume and mass. The main industrial oils are hydraulic oil. Gear Oil. Turbine oil. Compressor oil. Refrigeration oil. Transformer oil. Cylinder oil, heat Read More

Sino-Inst offers over 50 flow meter for flow measurement. About 50% of these are differential pressure flow meters, 40% is the liquid flow sensor, and 20% are Ultrasonic Level Transmitter and mass flow meter.

A wide variety of flow meters options are available to you, such as free samples, paid samples.

Sino-Instrument is a globally recognized supplier and manufacturer of flow measurement instrumentation, located in China.

Request a Quote

Please provide your measurement parameters or details. Sino-Instrument support customer customization and OEM

Leave a Reply

Your email address will not be published. Required fields are marked *