Magnetic flowmeters are mainly used to measure the flow of conductive media with good fluidity. Magnetic flowmeters are divided into insertion type and pipeline type. Pipeline electromagnetic flowmeter and insertion electromagnetic flowmeter has the same requirements for installation. There are also different places. Generally speaking, there are requirements for the external environment and installation methods.

Guide: Magnetic Flowmeter Installation

A magnetic Flow Meter is a flow meter that measures the flow of conductive fluids. Abbreviated as EMF, also called Electromagnetic flowmeters. It is a kind of Volumetric flow meter. A magnetic flow meter measures the velocity of conductive liquids moving through a pipe or conduit. In the wastewater treatment industry, a Magnetic Flow Meter is the best flow meter choice.

Electromagnetic flowmeters have been used for more than 50 years and have been widely used worldwide. The fields involve water/sewage, chemical, pharmaceutical, paper, food, and other industries.

  • Water / Wastewater Industry
  • Food and Beverage
  • Metals
  • Brewing, Distilling, and Wine makening
  • HVAC
  • Chemical
  • Pulp and Paper
  • Pharmaceutical
  • Mining, Mineral Processing

Extended reading: How to Select the Right Agriculture Flow Meter

Magnetic flowmeters use the principle of Faraday’s Law of Electromagnetic Induction to measure the flow rate of liquid in a pipe. In the magnetic flowmeter pipe parts, a magnetic field is generated and channeled into the liquid flowing through the pipe. 

Faraday’s Law states that the voltage generated is proportional to the movement of the flowing liquid. A conductor moving through a magnetic field produces an electric signal within the conductor. And the singal is proportional to the velocity of the water moving through the field. 

As fluid flows through the magnetic field, conductive particles in the fluid create changes. This variation is used to measure and calculate the velocity of water flow through the pipe. When the fluid moves faster, more voltage is generated. The electronic transmitter processes the voltage signal to determine the liquid flow.

What is the principle of magnetic flow meter?

To learn more about Magnetic Flow Meters, this video by Emerson gives a good explanation.
Video source: https://www.youtube.com/watch?reload=9&v=lRSjYjg9WRo

Read more about Everything You Need To Know About Electronic Flow Meters

The premise of using an electromagnetic flowmeter is that the liquid to be measured must be conductive and cannot be lower than the threshold (ie, the lower limit). If the conductivity is lower than the threshold value, measurement errors will occur until it cannot be used. The threshold value of general-purpose electromagnetic flowmeters is between 10-4~(5×10-6)S/cm, depending on the model. The general conductivity threshold is 5×10-6S/cm=5μS/cm. the

The conductivity of industrial water and its aqueous solution is greater than 10-4S/cm. The conductivity of acid, alkali and salt solution is between 10-4 and 10-1S/cm. There is no problem in use, and the low-grade distilled water is 10-5S/cm cm is also not a problem.

Petroleum products and organic solvents cannot be used if their conductivity is too low.

Some pure liquids or aqueous solutions have low conductivity and are considered unusable. However, in the actual work of electromagnetic flowmeters, there will be instances where they can be used because they contain impurities, which are beneficial to increase the conductivity.

For the aqueous solution, the conductivity in the data is measured in the laboratory with pure water. The actual aqueous solution may be mixed with industrial water. The conductivity will be higher than that found. It is also conducive to flow measurement.

Step 1: Magnetic Flowmeter Installation environment requirements

In order to make the electromagnetic flowmeter work stable and reliable, the following requirements should be paid attention to when choosing the installation location:

  1. Try to avoid ferromagnetic objects and equipment with strong electromagnetic fields (large motors, large transformers, etc.). In order to prevent the magnetic field from affecting the working magnetic field and flow signal of the sensor.
  2. Install in a dry and ventilated place as much as possible. Avoid sun and rain. The ambient temperature should be -20 ~ +60 ℃. The relative humidity is less than 85%.
  3. There should be ample space around the flowmeter. Easy to install and maintain.

Extended reading: Ultrasonic Insertion Flow Meter for Lined/Large Pipes

Step 2: Magnetic Flowmeter Installation Location selection

The electromagnetic flowmeter can be installed on a horizontal pipe or a vertical pipe.

  1. Choose a straight pipe section filled with liquid, such as the vertical section of the pipeline (flow direction from bottom to top is appropriate) or a liquid-filled horizontal pipe (the lowest point in the entire pipeline is appropriate). The position must ensure that the pipeline is always filled with the measured fluid . In the process of installation and measurement, there must be no partial full pipe.
  2. Select the place where the fluid flow pulse is small. That is, it should be far away from pumps, valves, elbows and other local resistance parts.
  3. When measuring two-phase (solid, liquid or gas, liquid) fluids, choose a place that is not easy to cause phase separation.
  4. Avoid negative pressure at the measurement site.
  5. The diameter or circumference of the side pipe is easy to measure, and the ovality should be small.
  6. Straight pipe length: The length of the straight pipe on the upstream side of the sensor installation pipeline should be greater than or equal to 10D, and the downstream side should be no less than 5D.
  7. There are two methods for inserting the insertion point of the plug-in electromagnetic flow sensor: one is to insert it on the central axis of the pipe under test, and the other is to insert it at 0.25D where the inner wall of the pipe is the pipe.
  8. Vertical installation: when the sensor is inserted into the pipe, the angle between the vertical diameter of the pipe section and the pipe section should be less than 5°, which is suitable for measuring clean media with small pipe vibration.
  9. Tilt installation: the angle between the axis of the sensor and the axis of the pipeline being measured is 45°. It is suitable for liquid flow measurement with large pipe diameter and other impurities in the measuring medium. This installation method has low water resistance and is not suitable for entanglement.

Step 3: Mounting flange for Magnetic Flowmeter Installation

A. Select the installation location and select the front and rear straight pipe sections of appropriate length. Cut the pipe section where the flowmeter is installed;
B. Weld a flange on each of the front and rear straight pipe sections. After adding gaskets at both ends of the sensor, connect the sensor to the flange with stud bolts (note that the direction of the arrow on the meter body should be consistent with the direction of fluid flow);
C. Weld the front and rear straight pipe sections of the sensor to the original pipe.

Note:

  1. When welding, ensure that the flange end face is perpendicular to the centerline of the pipeline;
  2. The place where the mounting hole pitch is larger is the meter rod mounting position. And the direction of the mounting holes of the two flanges should be the same;
  3. After the flange is welded, the pipeline should be cleaned up and there should be no welding slag and other sundries.

Extended reading: Magnetic Large Dia. Pipe Flow Meter

Step 4: Converter installation and connection cables

Power and signal wiring. Please refer to the product manual accompanying the goods.

The converter of the split electromagnetic flowmeter should be installed near the sensor where it is convenient for reading and maintenance. It can also be installed in the instrument room, and its environmental conditions can be much better than the sensor.

The distance between the converter and the sensor is limited by the conductivity of the measured medium and the signal of the signal cable. That is, the distributed capacitance of the cable, the cross-section of the wire, and the number of shielding layers. Use the information cable provided with the instrument by the manufacturer.

For liquids with lower conductivity and longer transmission distances, three-layer shielded cables are also specified.

The general instrument “Instruction Manual” gives the corresponding transmission distance range for liquids with different conductivity.

When a single-layer shielded cable is used for industrial water or acid-base liquids, the transmission distance is usually 100m.

In order to avoid signal interference, the signal cable must be worn separately in a well-grounded steel protection tube. Never put the signal cable and the power cord in the same steel pipe.

Guess you like: Insertion Magnetic Flow Meter-Large diameter online install

Special Magnetic Flowmeter Installation situation

For pipelines that do not allow flow interruption in the process, a bypass pipe should be installed and cleaned when the flow meter is installed. As shown in the figure, this device ensures continuous operation of the equipment system when the flow meter is withdrawn from use.

Special installation situation

The inner diameter measured by the flowmeter should be consistent with the inner diameter of the pipe. If the inner diameter cannot be the same, the inner diameter of the pipe should be greater than the inner diameter of the flowmeter. And install a tapered tube or expansion tube with a cone angle not greater than 15 between them, as shown in the figure.

Special installation situation2

When the flowmeter is installed inclined or vertically, the flow direction should be from top to bottom, as shown in the figure.

Special installation situation 3

All Magnetic Flowmeter Installations. It cannot be described in detail here. If you encounter problems with the Magnetic Flowmeter Installation. Please contact our engineers in time. We will guide the Magnetic Flowmeter Installation for you.

Featured Magnetic Flowmeters for Sale

Frequently
Asked
Questions

Generally speaking, there will be an indication of the fluid flow direction on the main body of various flowmeters. When we install the flowmeter, just follow the instructions to install it.

Generally speaking, there are two principles for the installation direction of the flowmeter.

  1. Make sure to measure full of fluid. Because absolutely most of the flowmeters need to be in a full pipe state to ensure the measurement effect.
  2. Install according to the instructions of the flowmeter.

Electromagnetic flowmeters can be installed vertically. However, vertical installation needs to pay attention to the following aspects, whether it is installed at the water inlet or the water outlet. Standard installed in the middle of the vertical position where the water flows upwards. This installation complies with gravity.

If it is installed downstream, it will not be a full pipe, and the water flow from bottom to top is always full. This facilitates accurate measurement of the flow meter. The straight pipe section is required to be 10D in front and 5D in back to ensure the use and accuracy requirements of the electromagnetic flowmeter.

Electromagnetic flowmeter vertical installation requirements:

  1. Installed at the inlet of the pipeline (that is, upstream), so that the pipeline is always full.
  2. The electromagnetic flowmeter should be installed in the lower part of the horizontal pipeline, vertically upward. Avoid installing at high places and vertically downward positions in the pipeline.
  3. Requirements for straight pipe section: inlet/outlet straight pipe section: inlet ≥ 10×DN; water outlet ≥ 5×DN
  4. In order to facilitate the detection of the flowmeter, a bypass channel is set in the measuring pipeline.
  5. Grounding point requirements: In order to make the instrument work reliably, improve the measurement accuracy, and not be disturbed by strong external electromagnetic fields, the sensor should be well grounded, and the grounding resistance should be less than 10 ohms.

Generally speaking, there is no other cost to install a flow meter.
However, the actual situation needs to be determined according to the user’s pipeline situation.

The pump outlet flow meter should be installed after the pump outlet valve. But before regulating the valve. In this way, the regulating valve will not affect the measurement of the flowmeter.

The flowmeter is not allowed to be installed in front of the pump, because there will be negative pressure in front of the pump, which will affect the accuracy of the electromagnetic flowmeter. Therefore, the electromagnetic flowmeter must be installed behind the pump.

The installation distance depends on the length and width of your pipeline, and the flowmeter has certain requirements for the straight pipe sections before and after it. At least the straight pipe section in front of the flowmeter is 10 times the diameter of the flowmeter. The straight pipe section behind the flowmeter is 5 times the diameter of the flowmeter. The farther away from the straight pipe, the better.

More Flow Measurement Solutions

Irrigation Flow Meters for Agriculture Water System

What is an irrigation flow meter? The irrigation flow meter is a flow meter designed for agricultural irrigation water counting. Agriculture, horticulture, etc. require water for irrigation. And water is…

How does a residential water meter work?

What does a residential water meter look like? A residential water meter is a legal meter for measuring water consumption in residential communities, residential buildings, bungalows, and other places. What…

Chilled Water Flow Meter

Application What is a Chilled Water Flow Meter? A chilled water flow meter refers to a flow meter that can be used to measure low-temperature water. Common chilled water flow…

3 inch (3″) Water Meter

Low cost 3″ Water Meter 3″ water meter is also DN80 water meter. Easy to read. Totalizing water volume. Intelligent large-caliber remote water meter includes wired remote transmission and wireless…

2 inch Water Flow Meter

2 inch water flow meter is also written as 2″ flow meter. If you are planning to buy a 2 inch water flow meter, please be sure to read this…

Inline water flow meters

Featured inline water flow meters Strap on flow meter X3  External clamp-on flow sensor. Easy to install. Suitable for measuring pipe diameter Φ9.53~Φ90. Ultrasonic Water Meter for Residential Water DN15-DN40,…

Hot Water Flow Meters

Hot Water Flow Meters Improve Heating-Boiler System Hot water flow meters refer to flow meters that can measure and indicate the flow of high temperature water. Hot water is widely…

Digital Water Flow Meters

What is a digital water flow meter? A Digital Water flow meter is a flow meter that can display the water flow rate, and have the output for the flow…

Sino-Inst offer over 50 Magnetic Flow Meters, with Best Price.

A wide variety of Magnetic Flow Meters options are available to you, such as free samples, paid samples.

About 13% of these are magnetic flow meter, 14% are Insertion Magnetic Flow Meter, 25% are Venturi flow meter, 13% are ultrasonic flow meter, and others are Liquid Turbine Flow Meters.

Electromagnetic flowmeters can be divided into insertion electromagnetic flowmeters and pipeline electromagnetic flowmeters. The Magnetic Flowmeter Installation methods of insertion electromagnetic flowmeters and pipeline electromagnetic flowmeters have the same place, but there are also differences.

First of all, what we need is that the shielded wire of the electromagnetic flowmeter cannot be routed together with the cable, because this will cause interference. Under normal circumstances, the parameters of the inner head of the electromagnetic flowmeter are set in advance, so no other adjustments are required.

Magnetic Flowmeter Installation should avoid places where the temperature rises and falls too much, and places where there are magnetic fields and strong vibration sources.